Section
01332
SEISMIC
DESIGN CRITERIA
PART 1 - GENERAL
1.1
SUMMARY
A. This Section
includes seismic design criteria for the following
1. Seismic design and
anchorage of pre-engineered metal structures and canopies.
2. Seismic design and
anchorage of mechanical and electrical equipment and items.
3. Seismic design of
tanks and anchorage of tanks.
4. Seismic support of
piping, cable tray, conduit, bus duct and ductwork.
5. Seismic design of
other structures or items as specified or indicated on the
Drawings.
1.2
REFERENCES
A. Project
Geotechnical Report:
“Final Geotechnical Study Report: Proposed Sludge Thickening,
Dewatering and Odor Control, P1-101”; December 7, 2010; by Converse
Consultants; Project Number 05-32-115-01.
B. California
Code of Regulations:
Title 24, Part 2, Volume 2, 2007, California Building
Code (CBC).
C. California Building
Code (CBC) 2010 Edition with references to ASCE 7 – 05, as
indicated in the CBC.
1.3
SEISMIC
REQUIREMENTS FOR ABCHORING EQUIPMENT
1. General:
All equipment, including machinery, pumps, fans, tanks,
piping, electrical panels, and their components and appurtenances,
including their anchorages, supplied by manufacturers or
suppliers, shall be designed for the following seismic forces in
accordance with ASCE 7-05 Chapter 13 with a Seismic Importance Factor
IP = 1.5
2. All liquid storage
tanks, including their supports and anchorages, shall be
designed as essential facilities in conformance with AWWA D100
latest edition, Section 13. Tanks shall be designed for seismic
forces including hydrodynamic forces indicated in AWWA D100 or ACI
350.3-06 Seismic Liquid Containing Concrete Structures. See general
structural notes for all seismic information not indicated herein.
3. Seismic forces shall
be considered acting at the center of gravity of the piece under
consideration.
4. Anchorage of
equipment shall be coordinated with the concrete subcontractor so
that anchorage may be installed at the time of concrete placement.
If calculations and anchorage details are not submitted prior to
placement of concrete, the Contractor shall be responsible for any
strengthening of concrete elements because of superimposed seismic
loading.
5. Equipment with
vibration isolators shall be provided with snubbers capable of
retaining the equipment in its designated location without any
material failure or deformation of the snubbers when exposed to a
vertical or horizontal force at the contact surface equal to 100
percent of the operating weight of the equipment. Air gaps between
retainer and equipment base shall not exceed 1/4 IN. Deflection
must be considered with respect to piping attached to the equipment.
Equipment without vibration isolators shall be anchored directly to
the supporting floor system.
6. In addition to the
anchorage, all equipment shall be internally designed so that all
static and moving parts are anchored to the supporting framework to
resist the imposed seismic forces. All forces must be transmitted
to the base in order to be anchored as required.
7. All piping,
raceways, ductwork, accessories, appurtenances, and other items
furnished with equipment shall be anchored to resist lateral
considered acting at the center of gravity of the piece under
consideration.
8. Lighting fixtures
shall be provided with safety cable attached to the structure and to
the fixture at each support point capable of supporting four times
the vertical load.
9. All piping
installed shall be anchored to the floor system(s) to resist
lateral seismic forces without excessive deflection. This force
shall be considered acting at the center of gravity of the pipe
under consideration.
10. Piping with flexible
connections and/or expansion joints shall be anchored such that the
intended uses of these joints are maintained in the piping system.
11. Do not use
friction to resist sliding due to seismic forces. (per
CBC
requirements)
12. Do not use more than
60 percent of the operating weight of mechanical and electrical
equipment for designing anchors for resisting overturning due to
seismic forces. (per DISTRICT requirements)
13. Do not use more
than 60 percent of the weight of tankage for resisting
overturning due to seismic forces. (per DISTRICT requirements)
14. Use anchor bolts,
bolts, or welded studs for anchors for resisting seismic forces.
Anchor bolts embedded in concrete or masonry and used to resist
seismic forces shall have a standard or heavy hex bolt head. Do not
use anchor bolts fabricated from rod stock with an L or J shape.
(Per DISTRICT requirements)
a. Do not use
concrete anchors, flush shells, chemical anchors, powder
actuated fasteners, or other types of anchors unless indicated on
the Drawings or accepted in writing by the ENGINEER. (per DISTRICT
requirements)
b. Seismic forces must
be resisted by direct bearing shear or tension on the fasteners used
to resist seismic forces. Do not use connections which use friction
to resist seismic forces. (per DISTRICT requirements)
1.4
SUBMITTALS
A. Shop Drawings and
Documentation: Submit complete shop drawings and documentation for
equipment, fabrications and construction subjected to seismic loads,
including anchorage criteria.
B. Calculations:
Calculations for equipment, fabrications, construction, and
anchorages subject to seismic loads shall be prepared, signed, and
sealed by a civil or structural Professional Engineer licensed to
practice in the State of California. These seismic calculations
shall not be submitted unless specifically requested by the ENGINEER
or the Building Code Official.
C. Foundation
and Support Load Summaries:
All foundation and support load summaries for equipment,
fabrications, and construction supported on structures designed by
others shall include the seismic load reactions applicable to the
foundations and supporting structures.
D. Design
Certification:
Two (2) copies of written certification, prepared and signed by a
Registered Professional Engineer licensed to practice in the State
of California, shall be submitted by the building, equipment, or
item supplier attesting that their tankage, mechanical and
electrical equipment, pre-engineered metal structures and canopies,
and their anchorage systems have been designed to meet the specified
seismic requirements of the CBC and these project documents.
1.5
PROJECT
CONDITIONS
A. Seismic
(Earthquake) Loads:
1. Seismic use group:
III
2. SS:
1.644g
3. S1:
0.586g
4. Fa: 1.0
5. Fv: 1.5
6. SMS:
1.644g
7. SM1:
0.879g
8. SDS:
1.096g
9. SD1:
0.586g
10. Site Class: D
11. Seismic design
category: D
PART 2 - PRODUCTS
2.1
ACCEPTABLE
MANUFACTURERS
A. Subject to
compliance with the Contract Documents, the following manufacturers
are acceptable:
1. Pre-engineered
suspended bracing systems:
a. International
Seismic Application Technology (ISAT) “Engineered Seismic
Bracing of Suspended
Utilities”. b. Unistrut.
c. Tolco. d. B-Line.
e. Or Equal.
2. Custom engineered
systems designed using specified criteria and common building
materials.
2.2
EQUIPMENT
ANCHORS AND SUPPORTS
A. Drilled-in-place
concrete anchors shall have an approved ICC Evaluation Services
Report.
B. Cast-in-place
anchors shall comply with ASTM A36, ASTM A307, or ASTM F1554,
36
ksi.
C. Anchors permanently
exposed to weather or corrosive environments shall be A 316
stainless steel
D. Structural
steel for supports:
ASTM A992 or ASTM A36.
E. Cold
Formed Metal and Connection Material:
Unistrut or equal.
F. Any details
provided are based on assumed equipment and arrangement.
1. Contractor shall be
responsible for design and acquiring approval for support and
anchorage of equipment and arrangement which varies from equipment
and arrangement assumed in detail provided.
PART 3 - EXECUTION
3.1
GENERAL
REQUIREMENTS
A. Every run which
requires bracing shall have a minimum of two (2) transverse braces
and one (1) longitudinal brace.
1. A “run” is
defined as suspended pipe, conduit, ductwork, cable tray, bus-duct,
or trapeze rack having a minimum 5 feet straight run length.
B. Brace spacing shall
not exceed the maximum allowable brace spacing as engineered by the
manufacturer or custom bracing designer.
C. Bracing may be
omitted from conduit, ductwork, cable tray, and bus-duct runs less
than 5 feet in length.
D. Bracing may be
omitted from conduit, cable tray, and bus duct runs where rod hung
supports of less than 12 IN. in length are required.
1. All unbraced
suspended utility systems having 2-inch conduit and larger or
systems weighing more then 5 pounds/foot shall be installed with a
minimum 6-inch clearance to suspended ceiling vertical hanger wires.
2. The conduit, cable
tray, ductwork, or bus-duct shall be installed such that the lateral
motion of the members will not cause damaging impact with other
systems or structural members or loss of vertical support.
E. A longitudinal
brace at a 90 degree change in direction may act as a transverse
brace if it is located within 2 feet of the change in direction.
F. A transverse brace
may act as a longitudinal brace if it is located within 2 feet of a
change in direction and if the brace arm and anchorage have been
sized to meet or exceed the requirements of the longitudinal brace.
G. When bracing
equipment or a utility system that is suspended from an overhead
deck, brace back to the overhead deck or to the supporting structure
supporting the deck.
1. Do not brace to
another element of the structure which may respond differently
during a seismic event.
H. Obtain approval
from the ENGINEER prior to attaching any brace elements to
structural steel framing.
I. When utilizing
cable bracing, tension the cable to remove slack without inducing
uplift of the suspended element.
1. Tension seismic
bracing system prior to system start-up and adjust if necessary
after equipment start-up.
J. As a general rule,
do not mix rigid bracing with cable bracing in the same run.
1. However, once
bracing has transitioned a 90 degree change in run direction, the
bracing may switch from rigid to cable or vice versa if required due
to a significant change in overhead deck elevation or to provide an
implementable bracing scheme in a congested area.
K. Install brace
members at an angle of 45 degrees from horizontal within a tolerance
of plus 2 1/2 degrees or minus 45 degrees provided the brace length
is accounted for in design.
1. Brace angle may be
increased to 60 degrees provided the brace spacing is reduced to 1/2
that required for a 45 degree brace.
L. Seismic bracing may
not pass through a building separation joint.
1. Utility systems
that pass through a separation joint must be seismically restrained
no greater than 5 feet from the point of connection.
2. Any hardware
designed to accommodate seismic movement across the span of the
separation joint shall be installed per manufacturer's installation
and listing instructions.
M. With approval of
the ENGINEER, utility systems that are suspended from the
overhead deck may be braced to load bearing concrete or CMU
(concrete masonry) walls provided that the walls and the overhead
decks will respond similarly during a seismic event.
N. Each layer of a
multiple layer trapeze rack shall be braced individually based on
the weight of the individual layer.
O. Conduit, cable
tray, or bus duct constructed of non ductile material
(plastic or fiberglass), shall have brace spacing reduced to 1/2 of
the spacing allowed for ductile materials.
P. Where brace
elements are through-bolted, the mounting hole in the element is to
be no more than 1/16 inch in diameter larger then the bolt or
threaded rod.
Q. Seismic braces shall
directly brace the system and not the hanger.
3.2
SUSPENDED
ELECTRICAL SYSTEMS
A. Install seismic
bracing for all conduit 2-1/2 inches trade size or greater.
B. All trapeze
assemblies supporting conduits, cable trays, or bus ducts shall be
braced considering the total weight of the elements on the trapeze.
1. For the purposes of
calculating weight, all conduits are to be treated as full. C.
Brace all trapeze racks which support conduit 2-1/2 inches trade
size or larger.
1. Brace all other
conduit rack, cable tray, or bus duct trapezes having a minimum
weight in excess of 10 pounds/linear foot.
2. Include a minimum
10 percent additional capacity for future additions.
D. Seismic bracing may
be omitted from cable trays, conduit, and bus ducts suspended by rod
hung supports 12 inches or less in length form the top of the
element to the bottom of the structural attachment of the
hanger provided lateral motion will not cause damaging impacts
to other systems or loss of system vertical support.
E. All vertical risers
involving conduit 2-1/2 inches in diameter or larger shall include
lateral restraint at maximum 30 feet intervals and at the top and
bottom of the riser.
3.3
FLOOR
OR ROOF MOUNTED EQUIPMENT
A. Provide one (1)
anchor on each leg or corner.
1. Support with a
minimum of three (3) 3/8 inch diameter anchors.
B. Friction shall be
neglected when designing anchors for shear.
C. Vertical seismic
forces, when required, shall be presumed to act concurrently with
horizontal seismic forces.
No comments:
Post a Comment