Section
02666
WATER
PIPELINE TESTING AND DISINFECTION
PART 1 - GENERAL
1.1
THE
REQUIREMENT
A. The CONTRACTOR shall
furnish all tools, equipment, materials, and supplies and shall
perform all labor required to complete the Work, as indicated in
the Contract Documents.
B. The CONTRACTOR shall
flush and test all pipelines and appurtenant piping and disinfection
of all pipelines and appurtenant piping for city or potable water,
including conveyance of test water from OCSD-designated source to
point of use and all disposals thereof, in accordance with the
requirements of the Contract Documents.
1.2
RELATED
WORK SPECIFIED ELSEWHERE
A. The requirements of
the following sections and divisions apply to the Work of this
section. Other sections and divisions of the Specifications, not
referenced below, shall also apply to the extent required for proper
performance of this Work.
1. Section 02200,
Earthwork
2. Division 15,
Mechanical
1.3
REFERENCE
SPECIFICATIONS, CODES AND STANDARDS
A. All Work specified
herein shall conform to or exceed the applicable requirements of the
referenced portions of the following publications to the extent that
the provisions thereof are not in conflict with other provisions of
these Specifications.
B. Comply with the
current provisions of the following Codes and Standards.
ANSI/AWWA B300
Hypochlorites ANSI/AWWA B301
Liquid Chlorine ANSI/AWWA C651 Disinfecting
Water Mains
1.4
CONTRACTOR
SUBMITTALS
A. General:
Submittals shall be made in accordance with the General
Requirements, Additional General Requirements, and as specified
herein.
B. The following
submittals and specific information shall be provided.
1. A testing schedule,
including proposed plans for water conveyance, control, disposal,
and disinfection, shall be submitted in writing for acceptance a
minimum of
48 hours before testing
is to start.
1.5
QUALITY
ASSURANCE
A. Comply with the
applicable reference Specifications of the General Requirements and
Additional General Requirements.
PART 2 - PRODUCTS
2.1
MATERIALS
REQUIREMENTS
A. All test equipment,
chemicals for disinfection, temporary valves, bulkheads, or other
water control equipment and materials shall be determined and
furnished by the CONTRACTOR subject to the ENGINEER’s acceptance.
No materials shall be used which would be injurious to the
construction or its future function.
B. Chlorine for
disinfection shall be in the form of liquid chlorine, sodium
hypochlorite solution, or calcium hypochlorite granules or tablets.
C. Liquid chlorine
shall be in accordance with the requirements of ANSI/AWWA B301.
Liquid chlorine shall be used only:
1. In combination with
appropriate gas flow chlorinators and ejectors;
2. Under the direct
supervision of a certified testing laboratory;
3. When appropriate
safety practices are observed.
D. Sodium hypochlorite
and calcium hypochlorite shall be in accordance with the
requirements of ANSI/AWWA B300.
PART 3 - EXECUTION
3.1
GENERAL
A. Unless otherwise
provided herein, water for testing and disinfecting water pipelines
inside the treatment plants will be furnished by OCSD; however, the
CONTRACTOR shall make all necessary provisions for conveying the
water from OCSD-designated source to the points of use.
B. All pipeline
trenches shall be backfilled and compacted per Section
02200, Earthwork, prior hydrostatic testing of pipe.
C. All pressure
pipelines shall be tested. Disinfection shall be accomplished by
chlorination. All chlorinating and testing operations shall be
performed by a certified laboratory in the presence of the ENGINEER.
D. Disinfection
operations shall be scheduled by the CONTRACTOR as late as possible
during the contract time period so as to assure the maximum degree
of sterility of the facilities at the time the Work is accepted by
the ENGINEER. Bacteriological testing shall be performed by a
certified testing laboratory approved by the ENGINEER and at the
expense of the CONTRACTOR. Results of the bacteriological testing
shall comply with the requirements of the Orange County Health Care
Agency or other appropriate regulatory agency.
3.2
HYDROSTATIC
TESTING OF PIPELINES
A. Prior to
hydrostatic testing, all pipelines shall be flushed or blown out at
6-8 feet per second or as approved by the ENGINEER. The CONTRACTOR
shall test all pipelines either in sections or as a unit. No
section of the pipeline shall be tested until all field- placed
concrete or mortar has attained an age of 14 days. The test shall
be made by closing valves when available, or by placing temporary
bulkheads in the pipe and filling the line slowly with water. The
CONTRACTOR shall be responsible for ascertaining that all test
bulkheads are suitably restrained to resist the thrust of the test
pressure without damage to, or movement of, the adjacent pipe. Care
shall be taken to see that all air vents are open during filling.
B. The pipeline shall
be filled at a rate, which will not cause any surges or exceed the
rate at which the air can be released through the air valves at a
reasonable velocity and all the air within the pipeline shall be
properly purged. After the pipeline or section thereof has been
filled, it shall be allowed to stand under a slight pressure for at
least 24 hours to allow the concrete or mortar lining, as
applicable, to absorb what water it will and to allow the escape of
air from any air pockets. During this period, bulkheads, valves,
and connections shall be examined for leaks. If leaks are found,
corrective measures satisfactory to the ENGINEER shall be taken.
C. The hydrostatic test
shall consist of holding the test pressure on the pipeline for a
continuous period of 4 hours. The test pressure for pipelines shall
be 150 percent of the pipe pressure class shown or specified,
measured at the lowest point of the pipeline section being tested.
Potable water piping shall be tested at a minimum pressure of 200
pounds per inch. The test pressure for yard piping shall be as
shown or specified on the Pipe Schedule, measured at the lowest
point of the pipeline section being tested. No pressure test will
be required for a reservoir overflow line. All visible leaks shall
be repaired in a manner acceptable to the ENGINEER.
D. The maximum
allowable leakage for pipelines shall be 10 U.S. gallons per inch of
diameter per mile of pipe per 24 hours for pipe with 40-ft or
greater joint lengths and with rubber-gasketed joints, and 20 U.S.
gallons per inch of diameter per mile of pipe per 24 hours for pipe
with 20-ft or less joint lengths and with rubber-gasketed joints.
Pipe with welded joints shall have no leakage. In the case of
pipelines that fail to pass the prescribed leakage test, the
CONTRACTOR shall determine the cause of the leakage, shall take
corrective measures necessary to repair the leaks, and shall again
test the pipelines.
3.3
DISINFECTING
PIPELINES
A. General:
All water pipelines except those appurtenant to hydraulic structures
shall be disinfected in accordance with the requirements of
ANSI/AWWA C651 disinfection of water mains using the Continuous-Feed
Method as modified herein.
B. Chlorination:
A chlorine-water mixture shall be uniformly introduced into the
pipeline by means of a solution-feed chlorinating device. The
chlorine solution shall be introduced at one end of the pipeline
through a tap in such a manner that as the pipeline is filled with
water, the dosage applied to the water entering the pipe shall be
approximately 50 mg/l. Care shall be taken to prevent the strong
chlorine solution in the line being disinfected from flowing back
into the line supplying the water.
C. Retention
Period:
Chlorinated water shall be retained in the pipeline long enough to
destroy all non-spore-forming bacteria. This period shall be at
least 24 hours. After the chlorine-treated water has been retained
for the required time, the free chlorine residual at the pipeline
extremities and at other representative points shall be at least 25
mg/l.
D. Chlorinating
Valves:
During the process of chlorinating the pipelines, all valves and
other appurtenances shall be operated while the pipeline is
filled with the heavily- chlorinated water.
E. Final
Flushing:
After the applicable retention period, the heavily chlorinated
water shall be flushed from the pipeline until chlorine measurements
show that the concentration in the water leaving the pipeline is no
higher than that generally prevailing in the system or is acceptable
for domestic use. If there is any question that the chlorinated
discharge will cause damage to the environment, a reducing agent
shall be applied to the water to neutralize thoroughly the chlorine
residual remaining in the water.
F. Bacteriological
Testing:
After final flushing and before the pipeline is placed in service,
a sample, or samples shall be collected from the end of the line, and
shall be tested for bacteriological quality in accordance with the
requirements of the Los Angeles County Department of Health Services
or other appropriate regulatory agency. For this purpose, the pipe
shall be re-filled with fresh potable water and left for a period of
24 hours before any sample is collected. Should the initial
disinfection treatment fail to produce satisfactory bacteriological
test results, the disinfection procedure shall be repeated
until acceptable results are obtained.
3.4
CONNECTIONS
TO EXISTING SYSTEM
A. Where connections
are to be made to an existing potable water system, the interior
surfaces of all pipe and fittings used in making the connections
shall be swabbed or sprayed with a one percent hypochlorite solution
before they are installed. Thorough flushing shall be started as
soon as the connection is completed and shall be continued until
discolored water is eliminated.
No comments:
Post a Comment