Section
03431
PRECAST
CONCRETE
PART 1 - GENERAL
1.1
SUMMARY
A. Section Includes:
1. Precast and
prestressed concrete.
B. Related Sections
include but are not necessarily limited to:
1. Division 01,
Additional General Requirements
2. Section 03200,
Reinforcement Steel
3. Section 03300,
Cast-In-Place Concrete
4. Section 03350,
Concrete Testing
5. Section 09905,
Architectural Paint Finishes
1.2
QUALITY
ASSURANCE
A. Referenced
Standards:
1. American Association
of State Highway and Transportation Officials (AASHTO):
a. Standard
Specification for Highway Bridges.
2. American Concrete
Institute (ACI):
211.2
Standard Practice for Selecting Proportions for
Structural
Lightweight Concrete
318
Building Code Requirements for Structural Concrete
350
Building Code Requirements for Environmental Engineering
Concrete Structures
3. ASTM International
(ASTM):
A36
Standard Specification for Carbon Structural Steel
A108
Standard Specification for Steel Bars, Carbon, Cold-Finished,
Standard Quality
A416
Standard Specification for Steel Strand, Uncoated Seven-Wire for
Prestressed Concrete
A496
Standard Specification for Steel Wire, Deformed, for Concrete
Reinforcement
C33
Standard Specification for Concrete Aggregates
C150
Standard Specification for Portland Cement
C330
Standard Specification for Lightweight Aggregates for Structural
Concrete
E329
Standard Specification for Agencies Engaged in Construction
Inspection and/or
Testing
4. American Welding
Society (AWS):
A5.1
Specification for Carbon Steel Electrodes for Shielded Metal Arc
Welding
A5.5
Specification for Low-Alloy Steel Electrodes for Shielded Metal
Arc Welding
D1.1
Structural Welding Code - Steel
D1.4
Structural Welding Code - Reinforcing Steel
5. Occupational Safety
and Health Administration (OSHA)
6. Precast/Prestressed
Concrete Institute (PCI):
MNL 116 Manual
for Quality Control for Plants and Production of Precast and
Prestressed Concrete Products
PCI Design Handbook -
Precast and Prestressed Concrete
7. Building Code:
a. International Code
Council (ICC):
1) International
Building Code and associated standards, 2009 Edition including
all amendments, referred to herein as Building Code.
B. Qualifications:
1. Provide precast and
prestressed concrete units produced by an active member of PCI.
2. Provide units
manufactured by plant which has regularly and continuously
engaged in manufacture of units of same type as those required for a
minimum of three (3) years.
3. Assure
manufacturer's testing facilities meet requirements of ASTM E329.
4. Welding operators
and processes to be qualified in accordance with:
a. AWS D1.1 for
welding steel shapes and plates. b. AWS D1.4 for welding
reinforcing bars.
5. Welding operators
to have passed qualification tests for type of welding required
during the previous 12
months prior to commencement of welding.
1.3
SUBMITTALS
A. Submittals shall be
made in accordance with the General Requirements, Additional
General Requirements,
and as specified herein.
B. Shop Drawings:
1. Product technical
data including:
a. Acknowledgement
that products submitted meet requirements of standards referenced.
b. Manufacturer's
installation instructions.
c. Sizes, types and
manufacturer of neoprene bearing pads.
d. Hardware to be
utilized to support suspended appurtenances.
2. Shop drawings and
erection plans for precast units, their connections and
supports showing:
a. Member size and
location.
b. Size,
configuration, location and quantity of reinforcing bars and
prestressing strands.
c. Initial prestress
forces.
d. Size and location
of openings verified by CONTRACTOR.
e. Size, number, and
locations of embedded metal items and connections. f. Required
concrete strengths.
g. Identification of
each unit using same standard marking numbers as used to mark actual
units.
3. Calculations for
members and connections designed by fabricator. Architectural panel
elevations are marked with suggested support and tie details
indicated on structural drawings. CONTRACTOR may use these
suggested details but shall provide calculations to verify the
design.
a. Calculations to be
sealed by a professional civil or structural engineer registered in
the state of California.
b. Perform calculations
using the dead load of the members plus the superimposed uniform and
concentrated loads shown on the Drawings and indicated in this
Specification section.
c. Indicate the
following:
1) Design for maximum
moment, maximum shear and maximum torsion.
2) Final top and
bottom flexural stresses resulting from the stresses due to maximum
moment and prestress force.
3) Ultimate moment
capacity.
4) Final top and
bottom flexural stresses, ultimate moment capacity, and ultimate
shear capacity, if affected, for members with reduced cross sections
due to openings or penetrations.
5) When required on
Drawings, a check for no tension in top and bottom of members due to
prestress force and member dead load plus superimposed loads
indicated on Drawings and in this Specification section.
6) Column design for
maximum axial load and maximum moment.
4. Submit test
results, when so required on Drawings, showing that embedded
connection items will adequately support the indicated loads.
a. Connection items to
have an ultimate load capacity of at least two (2) times the
required indicated load.
5. Concrete mix
design(s) including submittal information defined in Section 03350,
Testing.
6. Copies of source
quality control tests.
7. Certification of
manufacturer's testing facility qualifications.
PART 2 - PRODUCTS
2.1
ACCEPTABLE
MANUFACTURERS
A. Subject to
compliance with the Contract Documents, the following manufacturers
are acceptable:
1. Headed studs and
deformed bar anchors: a. Nelson Stud Welding Div., TRW, Inc. b.
KSM Division, Omark Industries.
c. Or Equal.
2. Precast vault:
a. Jensen Precast, Old
Castle Precast, or Equal.
2.2
MATERIALS
A. Embedded
Steel Plates and Shapes:
ASTM A36. B. Bearing Pads:
1. Neoprene.
2. Section 18,
Division 2 of the AASHTO Standard Specification for Highway
Bridges.
3. 60 durometer
strength.
C. Cement:
1. Comply with ASTM
C150, Type I or III.
2. Type II cement to
be used in the following precast units:
a. Precast weir
troughs.
D. Aggregates for
Normal Weight Concrete:
1. ASTM C33 with
coarse aggregate meeting the gradation for size 67 as stated in
ASTM C33.
2. Provide aggregates
accepted for bridge construction by the State Highway Department in
the state where the precast units are fabricated or in the state
where the Project is located.
3. All fine aggregate
to be natural not manufactured. E. Aggregates for Lightweight
Concrete:
1. ASTM C330 with 3/4
inch maximum size coarse aggregate.
2. All fine aggregate
to be natural not manufactured.
3. Provide aggregates
accepted for bridge construction by the State Highway
Department in
California.
F. Water:
1. Potable, clean.
2. Free of oils,
acids, and organic matter.
G. Maximum total
chloride ion content contributed from all ingredients of
concrete including water, aggregates, cement and admixtures measured
as a weight percent of cement to not exceed 0.06 for prestressed
concrete and 0.10 for all other precast concrete.
H. Prestressing
Strands:
1. Either 250K or 270K
high tensile strength uncoated seven (7) wire strand.
2. Manufacture and
test strands in accordance with ASTM A416.
I. Reinforcing
Steel and Welded Wire Reinforcement:
See Section 03200, Reinforcement Steel.
J. Headed Studs:
1. ASTM A108.
2. Minimum
yield strength:
50,000 pounds per inch.
3. Minimum
tensile strength:
60,000 pounds per inch.
K. Deformed Bar
Anchors:
1. ASTM A496.
2. Minimum
tensile strength:
80,000 pounds per inch.
3. Minimum
yield strength:
70,000 pounds per inch.
L. Electrodes:
1. E70 series
conforming to AWS A5.1 or AWS A5.5 for welding steel shapes and
plates.
2. E90 series
conforming to AWS A5.5 for welding rebar.
M. Concrete sand cement
grout in keyways between hollow core slabs.
1. See Section 03600,
Grouts.
2.3
MIXES
A. See Section 03300,
Cast-in-Place Concrete.
B. Maximum water
cement ratio for lightweight concrete to be determined in accordance
with recommendations of ACI 211.2 to provide required 28 day
compressive strength and maximum slump of 3 inches.
C. Do not begin
fabrication of units until concrete mix design(s) have been accepted
by
ENGINEER.
2.4
DESIGN
A. General Design
Requirements:
1. Design units and
connections in strict accordance with ACI 318 and the PCI Design
Handbook - Precast and Prestressed Concrete.
2. Design units for
spans, dead load of members, dead and live loads indicated on the
Drawings with concentrated loads placed in their actual locations.
a. Verify weights and
locations of concentrated loads.
3. Design units taking
into account reduced cross section at openings and penetrations.
4. Provide all
reinforcing in units as indicated.
a. Where not
indicated, design and provide all reinforcing and prestressing
strands subject to acceptance of ENGINEER.
5. Due to presence of
corrosive atmosphere, design prestressed members where indicated on
Drawings for no tension in top and bottom of members resulting from
loads indicated on Drawings and in this Specification section.
B. Specific Design
Requirements: Where indicated design units for H2O
loading and lateral earth pressures.
2.5
FABRICATION
A. Do not fabricate
units until shop drawings have been accepted by ENGINEER and
returned to CONTRACTOR and support locations have been field
verified by CONTRACTOR.
B. Manufacture, quality,
dimensional and erection tolerances of all units to be in accordance
with both PCI MNL 116 and PCI Design Handbook - Precast
and Prestressed Concrete.
C. Cast all members in
smooth rigid forms which will provide straight, true members of
uniform thickness and uniform color and finish.
D. Use sand cement
grout mixture to fill all air pockets and voids, and to repair
chipped edges.
E. Finish all repairs
smooth and to match adjacent surface texture and color.
F. Where units are to
receive concrete topping, provide units having heavy broom finish on
top surface for bond.
1. Provide roughness
of top surface to provide bond with topping and design for
horizontal shear at topping and unit interface in accordance with
requirements of Paragraph 17.5 of ACI 318.
2. Make all other
surfaces smooth.
G. Incorporate embedded
plates, angles, and flange welding strips into members at time of
manufacture.
1. Provide embedded
items as shown on the Drawings unless prior acceptance is received
from ENGINEER to do otherwise.
2. Provide flange
welding strips as indicated on Drawings.
3. Provide welding
strips on all flange edges of all double tee units.
4. Space strips as
shown on Drawings.
5. Cast lifting
handles into units at or near support points.
a.
Remove lifting handles after units are erected.
H. Cast openings larger
than 6 inches square or 6 inches in diameter in units at time of
manufacture.
1. Make smaller
openings by neat cutting or neat drilling by trades requiring them.
2. Coordinate sizes
and locations of all openings before fabrication of units.
I. Make provisions
for support of suspended ceilings, lighting fixtures, ducts, piping,
conduits and other suspended work.
1. When drilled
expansion bolts or powder-driven fasteners are accepted for use,
coordinate prestress strand location with prestress concrete member
supplier so that drilled expansion bolts or powder-driven fasteners
do not hit or are drilled or driven into prestress strands.
2. Install
powder-driven fasteners by means of a low velocity powder-actuated
tool complying with requirements of OSHA.
a. Assure that the
load to be supported by each in place drilled expansion bolt or
powder-driven fastener does not exceed the maximum allowable load
recommended by the bolt or fastener manufacturer for the concrete
strength encountered and for the type, size and embedment length of
expansion bolt or driven fastener installed.
J. Automatically weld
headed studs and deformed bar anchors to members to provide full
penetration weld between studs, bar anchors and members they are
attached to.
K. Weld steel shapes
and plates per AWS D1.1 and reinforcing steel per AWS D1.4.
L. Minimum
Concrete Compressive Strength at Time of Strand Release:
3500 pounds per inch.
M. Mark each unit as
indicated on the erection plans.
1. Place mark on
non-exposed-to-view surface.
N. Coat or finish ends
of exposed prestressing strands to prevent rusting.
O. Fabricate the
following types of precast and prestressed units (all units to be
made with normal weight concrete unless noted otherwise on
Drawings):
1. Precast weir
troughs and lintels as shown on Drawings.
2. Precast concrete
beams and columns as shown on Drawings:
a. Reinforce as
indicated.
1) If reinforcement is
not indicated, design and provide reinforcement as required to
support maximum torsion, shear, moment and axial loads.
b. See Paragraph 2.4B
of this section for specific design requirements.
c. Provide beam and
column connections as indicated on Drawings and as required to
support all loads subject to ENGINEER's acceptance.
2.6
SOURCE
QUALITY CONTROL
A. During production
of precast concrete units, conduct strength tests of
concrete placed in units as required in Section 03300, Cast-in-Place
Concrete and Section 03350, Concrete Testing, for concrete placed
during fabrication.
1. Results of strength
tests to be sent immediately to ENGINEER, CONTRACTOR
and
OCSD.
2. Test reports to
indicate units they represent.
B. When accepted by
ENGINEER, strength tests may be made by precast manufacturer after
he has submitted certification that his testing facilities meet the
requirements of ASTM E329.
PART 3 - EXECUTION
3.1
PREPARATION
A. Verify
acceptability and location of supports to receive units.
1. Check bearing
surfaces to determine that they are level and uniform. B. Verify
compressive strengths of concrete and masonry supports.
1. Do not start
erection of units until supports have reached their 28-day required
compressive strengths.
3.2
ERECTION
A. Sequence erection
to provide a balance of loads across beams and columns.
B. Give consideration
to possible lack of stability or capacity of partially completed
frame or structure.
C. CONTRACTOR to be
responsible for guying, shoring, and bracing of frame, walls and
individual members as necessary to resist forces due to wind,
erection, or any other source that may occur before structure is
completed.
D. Use only erection
equipment adequate for placing units at lines and elevations
indicated on Drawings.
1. Do not damage units
or existing construction during erection.
2. Erect units using
lifting handles cast into the units.
E. Place each leg of
all double tees on a 3/8 inch thick neoprene pad held 1 inch back
from edge of support.
1. Pad dimensions
equal to length of bearing -1 inch x bearing width +2 inches.
F. Place hollow core
slabs on continuous 1/4 inch thick neoprene bearing pad so that
width equals bearing length -1 inch.
G. Provide a 1/2 inch
thick neoprene bearing pad on the top of all precast concrete
columns.
1. Pad to cover entire
top surface of column except hold pad back 1 inch from face of
column all around.
H. Weir Trough:
1. Anchor weir troughs
to supports as indicated on Drawings.
2. Provide continuous
3/8 inch thick neoprene pad under troughs at support.
3. Hold back pads 1
inch from edge of support.
I. After erection,
verify that there is no direct contact between bottom of units and
supporting members.
1. Where direct
contact occurs, install additional layers of bearing material to
raise units off supports.
J. Lintels:
1. Length of lintel
bearing on supports to be as indicated on Drawings. a. If not
indicated, minimum length of lintel bearing to be 8 inches.
2. When indicated on
Drawings, fill masonry cells under lintel bearing with masonry grout
and reinforce cells if so indicated.
3. Provide minimum
3/8 inch thick full bed joint of masonry mortar between
underside of lintel and top surface of grouted masonry for complete
lintel bearing length.
4. Where masonry cells
are not required to be grouted under lintel bearing, provide minimum
3/8 inch thick face shell mortar bed joint between bottom of lintel
and top of masonry block for complete lintel bearing length.
5. See Drawing
details for required felt paper under lintel bearing at
masonry control joints.
K. Weld steel shapes
and plates per AWS D1.1 and reinforcing steel per AWS D1.4. L.
Fill all keyways between hollow core slabs with concrete sand cement
grout.
1. See Section 03300,
Cast-in-Place Concrete.
M. After all precast
units are erected and all precast unit connections have been made,
coat all exposed surfaces of the connections with the same prime and
finish paint as required on the adjacent precast concrete units.
1. See Section 09905,
Architectural Paint Finishes.
3.3
FIELD
QUALITY CONTROL
A. Causes for
rejection of units include, but are not necessarily limited to the
following:
1. Cracked units.
2. Chipped, broken, or
spalled edges.
3. Units not within
allowable casting tolerances.
4. Voids or air
pockets which, in opinion of ENGINEER, are too numerous or too
large.
5. Non-uniform finish
or appearance.
6. Low concrete
strength.
7. Improperly placed
embedded items and/or openings.
8. Exposed wire mesh,
reinforcing or prestressing strands.
No comments:
Post a Comment