Section
04230
REINFORCED
HOLLOW UNIT MASONRY
PART 1 - GENERAL
1.1
THE
REQUIREMENT
A. The CONTRACTOR shall
furnish all tools, equipment, materials, and supplies and shall
perform all labor required to complete the reinforced hollow unit
masonry work as indicated on the Drawings and specified herein.
1.2
RELATED
WORK SPECIFIED ELSEWHERE
A. The requirements of
the following sections and divisions apply to the Work of this
section. Other sections and divisions of the Specifications, not
referenced below, shall also apply to the extent required for proper
performance of this Work.
1. Section 03200,
Reinforcement Steel
2. Section 03300,
Cast-in-Place Concrete
3. Section 03600,
Grouts
4. Section 03360,
Concrete Curing, Finishing and Dampproofing
5. Section 04155,
Masonry Accessories
6. Section 04510,
Masonry Cleaning
7. Section 07130,
Concrete Sealer and Hardener
8. Section 09905,
Architectural Paint Finishes
1.3
REFERENCE
SPECIFICATIONS, CODES AND STANDARDS
A. All Work specified
herein shall conform to or exceed the applicable requirements of the
referenced portions of the following publications to the extent that
the provisions thereof are not in conflict with other provisions of
these Specifications.
B. Comply with the
applicable provisions of the following codes, regulations and
standards.
1. Codes and
Regulations:
CCR
California Code of Regulations, Title 24, Part
2, California Building Code (CBC), 2010 Edition
2. Industry Standards:
ASTM C 33
Standard Specification for Concrete Aggregates
ASTM C 90
Standard Specification for Load-Bearing
Concrete Masonry Units
ASTM C 140
Standard Test Methods for Sampling and
Testing Concrete Masonry Units and Related Units
ASTM C 144
Standard Specification for Aggregate for
Masonry Mortar
ASTM C 150
Standard Specification for Portland Cement
ASTM C 207
Standard Specification for Hydrated Lime for
Masonry Purposes
ASTM C 331
Standard Specification for
Lightweight
Aggregates for Concrete
Masonry Units
ASTM C 404
Standard Specification for Aggregates for
Masonry Grout
ASTM C 476
Standard Specification for Grout for Masonry
ASTM C 595
Standard Specification for Blended Hydraulic
Cements
SSPWC Sections 202-2
“Green Book”, Standard Specifications for
Public Works
Construction, Concrete Block
SSPWC Sections 303-4.1
“Green Book”, Standard Specifications for
Public Works Construction, Concrete Block Masonry
C. Comply with the
applicable reference Specifications as directed in the
General
Requirements and the
Additional General Requirements.
1.4
CONTRACTOR
SUBMITTALS
A. Submittals shall be
made in accordance with the General Requirements, Additional
General
Requirements and as specified herein.
B. The following
submittals and specific information shall be provided.
1. Manufacturer's
Literature:
Submit information illustrating the horizontal joint
reinforcement and preformed control joint materials proposed for
use.
2. Samples:
Before starting Work, samples of blocks to be used shall be
submitted to the ENGINEER for acceptance. Materials used on the
project shall conform to accepted samples.
3. Sample
Panel:
Lay up a sample panel for each type of masonry at the site to show
the accepted bond and method of finishing joints. Sample panels
shall be at least 4 feet high and at least 4 feet long, and shall
remain intact after the panel acceptance until acceptance of the
permanent masonry work and then shall be removed by the CONTRACTOR.
The accepted sample panels shall serve as a basis of color, texture,
and workmanship for acceptance of the permanent construction. The
sample panel shall demonstrate the ability to receive grout in
certain cells in any sequence of placement and demonstrate that the
materials will be restricted to the cells and bond beams intended to
receive that material. The sample panel construction shall show
all areas required to receive mortar. The sample panel shall
demonstrate the proper use of running bond or stacked bond meeting
the requirements hereinafter specified.
4. Manufacturer's
Certificate:
Provide manufacturer's certificate(s) for the masonry units
specified herein.
1.5
QUALITY
ASSURANCE A. General:
1. The CONTRACTOR
shall hire an independent test laboratory to visit the jobsite to
sample and test the masonry units, to make samples of grout and
mortar, and to cure and test these samples as herein specified. A
copy of all testing reports shall be furnished to the ENGINEER
within 5 days of the tests.
2. After delivery to
the jobsite, the masonry units will be sampled and tested in
accordance with ASTM C 140. Masonry construction shall not proceed
until test results are known and the masonry units are certified by
an accepted testing agency as complying with ASTM C 90 and this
Specification.
3. Grout and mortar
samples for strength testing shall be taken at the beginning of the
masonry work and thereafter at the discretion of the ENGINEER. The
samples shall be taken as hereinafter specified.
a. Field
Compressive Test Specimen for Grout:
On a flat nonabsorbent base, form a space approximately 3 inches x
3 inches x 6 inches high (i.e., twice as high as it is wide) using
masonry units having the same moisture conditions as those being
laid. Line the space with a permeable paper or porous separator so
that water may pass through the liner into the masonry units.
Thoroughly mix or agitate grout to obtain a fully representative mix
and place into molds in two layers, and puddle each layer with a
1-inch x 2-inch puddling stick to eliminate air bubbles. Level off
and immediately cover molds and keep them damp until taken to the
laboratory. After 48 hours to set, carefully remove masonry units
and transport and place grout samples in a fog room until tested.
b. Field
Compressive Test Specimen for Mortar:
Spread mortar on the masonry units 1/2 inch to 5/8 inch thick,
and allow to stand for 1 minute. Then, remove mortar and place in a
2-inch x 4-inch cylinder in two layers, compressing the mortar into
the cylinder using a flat-end stick or fingers. Lightly tap mold on
opposite sides, level off and immediately cover molds and keep them
damp until taken to the laboratory. After 48 hours to set, have the
laboratory remove molds and place them in the fog room until tested
in the damp condition.
c. Requirements:
1) Each such mortar
test specimen shall exhibit a minimum ultimate compressive
strength of 1,800 pounds per square inch.
2) Each such grout
test specimen shall exhibit a minimum ultimate compressive
strength of 2,000 pounds per square inch.
PART 2 - PRODUCTS
2.1
MASONRY
UNITS A. General:
1. Units shall be of
size shown. Provide or cut special shapes for corners, jambs,
lintels, and other areas shown or required. Special units shall
match color and texture of standard units. Where masonry units are
placed so that the end of a unit is exposed, such as at a corner or
intersection, the end of that block shall have a surface to match
the color or texture of the sides of the other units.
2. Units shall be
sound, dry, clean, and free of cracks and shall have reached the
specified moisture content and compressive strength prior to placing
in the structure.
3. Vertical cells to
be grouted in all units covered under this Specification shall have
vertical alignment sufficient to maintain a clear, unobstructed
continuous vertical cell measuring not less than 2 inches by 3
inches.
4. The color of the
units shall be gray and the surface texture shall be smooth on all
exposed surfaces.
B. Hollow Concrete
Units (CMU):
1. Hollow concrete
masonry units (CMU) shall be Grade N Type I in accordance with ASTM
C 90.
2. Tests for
conforming to the above Specifications shall be made in accordance
with ASTM C 140.
3. Blocks shall have
dense faces suitable for painting.
4. The manufacturer
shall certify that the masonry units meet all requirements of ASTM C
90 including the moisture content and linear shrinkage requirements
for humid conditions.
2.2
CEMENT
A. Portland
Cement:
All cement to be used or furnished shall be Type II low alkali
Portland cement conforming to ASTM C 150, or Type IP (MS)
Portland-pozzolan cement conforming to ASTM C 595, unless otherwise
specified. Either cement shall conform to the low alkali
requirements of Table IA of ASTM C 150. Type IP (MS) cement shall
contain no more than 20 percent pozzolan, which shall be interground
with the clinker.
B. The CONTRACTOR
shall furnish a Certificate of Compliance signed by the
manufacturer identifying the cement and stating that the cement
complies with these requirements. Supporting test data shall be
furnished when requested by the ENGINEER.
C. Whenever suitable
facilities accepted by the ENGINEER are available for handling and
weighing bulk cement, such facilities shall be used. Otherwise,
the cement shall be delivered in original unopened sacks that have
been filled by the manufacturer. They shall be plainly marked with
the manufacturer's name or brand, cement type and weight.
D. Cement shall be
stored in such a manner as to permit ready access for the purpose of
inspection and sampling, and suitably protected against
contamination or moisture. Should any cement delivered show evidence
of contamination or be otherwise unsuitable, the ENGINEER may reject
it and require that it be removed from the site.
E. All Portland cement
used in concrete for any individual structure shall be of the same
brand and type unless otherwise accepted by the ENGINEER.
2.3
LIME
A. Lime putty shall
be made from Type S hydrated lime and shall conform to
ASTM C 207. Lime shall
be kept dry.
2.4
AGGREGATES
A. Hollow
Concrete Units:
Aggregates for hollow concrete units shall conform to ASTM
C 33 and ASTM C 331 or shall be blended from aggregates conforming
to these Specifications. Use the same type or types of aggregate
throughout the project unless otherwise indicated or written
permission is received from the ENGINEER. Aggregates used for the
project shall produce concrete with a dry density of 105
to 125 lbs. per cubic foot, normal weight.
B. Mortar:
Aggregate for mortar shall conform to ASTM C 144.
C. Grout:
Aggregate for grout shall conform to ASTM C 404.
2.5
WATER
A. Water used for
concrete shall not contain deleterious substances. Water shall not
contain an amount of impurities that will cause a change in the time
of setting of Portland cement of more than 25 percent nor a
reduction in relative mortar strength at 7 and 28 days of more than
10 percent compared to results obtained with distilled water.
B. In conventionally
reinforced concrete work, water shall not contain more than
1,000
ppm of chlorides calculated as Cl or more than 1,000 ppm of sulfates
calculated as
SO4.
2.6
MORTAR
A. Mortar shall be
freshly prepared and uniformly mixed in the ratio portioned by a
loose volume of 1 part Portland cement and 2-1/2 to 3 parts sand to
which 1/4 to 1/2 part, maximum, lime putty or hydrated lime has been
added. Mortar shall attain a minimum compressive strength of 1,800
pounds per inch in 28 days. Test results verifying the compressive
strength shall be submitted to the ENGINEER.
2.7
MORTAR
ADMIXTURE
A. Water repellent
admixture shall be added to all mortar in the quantity recommended
by the manufacturer. Water repellent admixture shall be Hydrophobe
31, manufactured by W. R. Grace and Company; Sika Red Label,
manufactured by Sika Chemical Corporation; Omicron Mortar Proofing,
Master Builders Corporation; Or Equal.
B. Inert coloring
pigments may be added, but shall not to exceed 6 percent by weight
of the cement. Color shall be as selected by ENGINEER.
C. Quantity of
admixture per mortar batch shall be in accordance with
manufacturer's recommendations.
2.8
GROUT
A. Conform to ASTM C
476 except as hereinafter specified.
B. General:
Grout shall be sufficiently fluid to ensure complete filling of all
sections of masonry requiring grout, but not so thin as to allow
separation of aggregate.
C. Proportions:
1. Grout for pumping
shall be of fluid consistency and shall have not less than seven
sacks of cement in each cubic yard of grout. The mix design shall
be subject to ENGINEER’s acceptance.
2. Fluid consistency
shall mean a fluid suitable for pouring without segregation.
3. Grout for use in
spaces less than 4 inches clear in any dimension, grout proportioned
by volume shall be 1 part Portland cement and 2-1/4 to 3 parts sand.
For spaces 4 inches or larger in all horizontal directions,
grout shall be 1 part Portland cement, 2 to 3 parts sand and 1-1/4
to 2 parts No. 4 concrete aggregate.
D. Grout
Admixture:
Grout admixture shall be Sika Grout Aid, Type II, manufactured by
Sika Chemical Corporation; Grout Aid GA-II, manufactured by Concrete
Emulsions; Or Equal. Amount of admixture and method of introducing
admixture shall be in accordance with manufacturer's
recommendations.
E. Compressive
Strength:
The average 28-day compressive strength of the grout
samples for each grout pour tested shall not be less than 2,000
pounds per inch. Test results verifying the compressive strength
shall be submitted to the ENGINEER.
2.9
HORIZONTAL
JOINT REINFORCEMENT
A. Two parallel No. 9
wires, uncoated, weld connected to No. 9 perpendicular cross wire at
15 inches on center. Special manufactured corner and wall
intersection pieces shall be used at these locations. Horizontal
joint reinforcement shall be ladder-type masonry wall reinforcement,
manufactured by Dur-O-Wall National, Inc., Cedar Rapids, IA; AA Wire
Products Company, Chicago, IL; Or Equal.
2.10
PREFORMED
CONTROL JOINT
A. Joint material
shall be a solid rubber extrusion such as regular Rapid Control
Joint, manufactured by Dur-O-Wall National Company, Cedar Rapids,
IA; Sonneborn Control Joint, manufactured by Sonneborn-Contech
Company, Oakland, CA; Or Equal.
PART 3 - EXECUTION
3.1
GENERAL
A. All Work shall be
performed in a workmanlike manner and in full compliance with the
applicable building ordinances.
B. The foundation on
which a masonry wall is to be built shall have a clean, smooth
surface with aggregate exposed. Sandblasting shall be done if the
surface has laitance or other foreign material lodged in the pores
of the foundation surface.
C. All masonry walls
shall be laid true, level, and plumb in accordance with Subsection
3.4 and the Drawings.
D. Masonry units shall
be cured and dry, and surfaces shall be clean when laid in the
walls.
E. During
construction, all partially laid walls, as well as units in storage
shall be protected from moisture. All concrete blocks units and any
partially laid walls that become wet during the construction shall
be permitted to dry for at least 1 week, or longer if required by
weather conditions, before recommencing Work.
F. Proper masonry
units shall be used to provide for all windows, doors, bond beams,
lintels, pilasters, etc. with a minimum of unit cutting. Where
masonry unit cutting is necessary, all cuts shall be neat and
regular, and edges exposed in the finished Work shall be cut with a
power-driven abrasive saw.
G. Where no bond
pattern is shown, the wall shall be laid up in straight uniform
course with regular running bond with alternate header joints in
vertical alignment.
H. Intersecting masonry
walls and partitions shall be bonded by the use of 1/4 inch
minimum-diameter steel ties at 24 inches on centers (maximum).
I. Where stack bond
is indicated on the Drawings, accepted metal ties shall be provided
horizontally at 24 inches on centers (maximum).
J. Mortar joints shall
be straight, clean, and uniform in thickness. Unless otherwise
specified or detailed on the Drawings, horizontal and vertical
joints shall be approximately
3/8 inch thick with full
mortar coverage on the face shells and on the webs surrounding cells
to be filled. Units shall be laid with "push joints." No
slushing or grouting of a joint will be permitted, nor shall a joint
be made by working in mortar after the units have been laid.
K. Exposed walls shall
have joints tooled with a round bar (or V-shaped bar) to produce a
dense, slightly concave surface well bonded to the block at the
edges. Tooling shall be done when the mortar is partially set but
still sufficiently plastic to bond. All tooling shall be done with
a tool that compacts the mortar, pressing the excess mortar out of
the joint rather than dragging it out.
L. If it is necessary
to move a block so as to open a joint, the block shall be removed
from the wall, cleaned, and set in fresh mortar.
3.2
WEATHER
CONDITIONS
A. Protect the tops of
walls at all times. Cover the tops of walls with waterproof paper
when rain is imminent and Work is discontinued.
B. Protect masonry
construction from loss of moisture during the curing period when
ambient air temperature of 90 degrees F (37 degrees C) or greater
exists and when relative humidity is less than 50 percent. Use light
fog spray nozzles to cure the mortar when these conditions exist.
Provide a demonstration of the fog spray nozzles prior to starting
the Work.
3.3
BONDING
WALL UNITS A. Foundation:
1. The foundation
shall be prepared for the initial mortar placement by one of the
following methods:
a. Sandblasting the
foundation and reinforcing dowels after the concrete has fully cured
to remove all laitance and spillage and to expose sound aggregate.
b. Water blasting the
foundation and reinforcing dowels after the concrete has partially
cured to remove all laitance and spillage and to expose
sound aggregate.
c. Green cutting fresh
concrete with high-pressure water and hand tools to remove all
laitance and spillage from the foundation and the reinforcing dowels
and to expose sound aggregate.
2. The foundation
shall be cleaned of all loose material prior to the initial mortar
placement.
B. Corners:
Corners shall have a standard masonry bond for overlapping units
and shall be grouted solid. Reinforcement shall be as shown.
C. Intersections:
Intersecting walls shall be bonded with reinforcement as shown.
The abutting wall shall not have a masonry bond with the straight
wall.
3.4
LAYING
REINFORCED MASONRY UNITS A. General:
1. Masonry
construction shall conform to the applicable sections of the
California Building Code, latest edition, and as supplemented by
these Specifications. Do not start laying masonry units if the
foundation horizontal or vertical alignment does not satisfy the
tolerance specified in Section 03300, Cast-In-Place Concrete.
2. The maximum
permissible variation from plumb of the wall or of a line of joints
in the wall shall be 1/16 inch per foot of height, and 1/4 inch in
the total height of the wall. The maximum permissible variation
from a horizontal line along the base of the wall or for lines of
horizontal joints shall be 1/16 inch per block, 1/4 inch per 50 feet
of wall with proportionately greater tolerance for longer walls up
to 1/2 inch in the total length of wall. Interior surfaces shall be
maintained in the plane described above and the dimension tolerances
of the units shall be taken up on exterior surfaces.
3. Units with chipped
edges or corners within permissible ASTM limits shall be placed in
the wall such that the chipped area is not exposed to view.
B. Wall Units:
1. General:
a. If it is necessary
to move a unit after it has been once set in place, the unit shall
be removed from the wall, cleaned, and set in fresh mortar.
b. Toothing of masonry
units will not be permitted unless acceptance is given by the
ENGINEER.
c. All masonry work
shall be protected from damage until Final Acceptance of the Work.
Damaged units will not be accepted.
2. Running
Bond:
Unless otherwise shown, walls shall be laid up in straight,
uniform courses using a running bond pattern. The running bond
pattern shall guarantee continuous vertical cells meeting the
requirements of this Specification with mortar joints as required to
prevent the different materials such as grout or poured insulation
from escaping from the cell being filled to adjacent cells where the
material is not intended to be placed.
C. Special
Shapes:
Provide and place such special units as corner block, door jamb
block, lintel block fillers, and similar blocks as may be required.
Use the required shapes and sizes to work to corners and openings
maintaining a proper bond throughout the wall.
3.5
BUILT-IN
ITEMS
A. Door frames,
windows, vents, and other items required to be built in the wall
shall be in position and the wall constructed around them. Standard
masonry anchors shall be used to secure the items to the wall. All
spaces around the items shall be filled with mortar or grout.
3.6
EMBEDDED
CONDUITS
A. Electrical,
instrumentation, or water conduits shall not be placed in a cell
containing reinforcement unless accepted by the ENGINEER.
3.7
MORTAR
PREPARATION
A. Mortar shall be
mixed by placing 1/2 the water and aggregate in the operating mixer.
Add cement. Add the remaining aggregate and water, and mix for at
least 2 minutes. Add lime and continue mixing as long as needed to
secure a uniform mass, but no less than
3 minutes after the
addition of lime. The addition of the admixture shall be timed in
strict accordance with the manufacturer's instructions, and the
procedure used for adding it to the mix shall provide good
dispersion.
B. The mortar shall be
machine mixed in accepted mixers. Mixer drums shall be kept clean
and free of debris and dried mortar. The mortar shall be in place
before the initial setting of the cement has taken place.
Retempering of mortar in which the cement has started to set will
not be permitted.
3.8
MORTAR
JOINTS A. General:
1. Mortar joints shall
be straight, clean, and uniform in thickness, and shall be tooled as
shown on the Contract Documents. Where no joint detail is shown and
the wall is not to be coated or painted, exposed walls shall have
joints tooled with a round bar to produce a dense, slightly concave
surface well bonded to the masonry units at the edges. Tooling
shall be done when the mortar is partially set but still
sufficiently plastic to bond. All tooling shall be done with a tool
that compacts the mortar, pressing the excess mortar out of the
joint rather than dragging it out. Where certain joints are to be
concealed under paint, these joints shall be filled flush and then
rubbed with burlap to produce a dense surface without sheen.
2. Horizontal and
vertical mortar joints shall be straight, clean, and shall have a
uniform thickness of 3/8 inch.
3. The horizontal and
vertical mortar joints shall have full mortar coverage on the face
shells.
4. Vertical head
joints shall be buttered well on each unit for a width equal to the
face shell of the unit, and these joints shall be shoved tightly so
that the mortar bonds well to both units. Joints shall be solidly
filled from the face of the block to at least the depth of the face
shell, pointing where necessary to completely and compactly fill the
joints. Furrowing of the mortar will not be permitted.
5. All excess mortar
shall be removed from the grout space of the cells to be filled as
the units are being laid.
B. Exposed Joints:
1. Joints that will be
exposed to view after final construction shall be tooled unless
otherwise noted or shown. Joints shall be cut flush and, as mortar
takes its initial set, shall be tooled to provide a concave joint.
Tooling shall be done when the mortar is partially set but still
sufficiently plastic to bond. All tooling shall be done with a tool
that compacts the mortar, pressing the excess mortar out rather than
dragging it out. Joints that are not tight at the time of tooling
shall be raked out, pointed, and then tooled.
2. Joints at
split-face surfaces, interior and exterior, shall be raked and
tooled.
C. Concealed
Joints:
Joints that are not exposed shall be struck flush with no further
treatment required.
3.9
CONTROL
JOINTS
A. Preformed
Control Joints:
The mortar shall be omitted from the vertical joints. Place the
rubber control joint material as the wall is built. After the wall
is grouted, cured, and cleaned, install the backing rod and flexible
sealant. Place and tool sealant to match depth of typical joint.
3.10
REINFORCING
A. General:
1. Reinforcing bars
shall be straight except for bends around corners or where bends or
hooks are detailed on the Contract Documents. Vertical bars shall be
fixed in the position and at the interval shown on the Contract
Documents at each end of the bar.
2. All steel
reinforcing bars shall be as shown on the Drawings or as specified
in
Section 03200,
Reinforcement Steel of these Specifications.
3. Reinforcing steel
shall be placed as indicated on the Drawings. Splices shall be
lapped a distance sufficient to develop the yield stress in the bar,
with a minimum requirement of 40 diameters. Dowels other than
column dowels need to be lapped only 30 diameters. Column dowels
shall lap 50 diameters.
4. Outside horizontal
steel shall lap around corners 40 diameters and be carried through
columns unless otherwise shown on the Drawings. Inside horizontal
steel shall extend as far as possible and bend into corner core. A
dowel shall be provided in the foundation for each vertical bar.
5. Where horizontal
courses are to be filled, metal stops shall be used. Use of paper
stops will not be permitted. All horizontal reinforcing steel shall
be laid in a course of bond beam blocks filled with grout.
6. Vertical cores
containing steel shall be filled solid with grout, and thoroughly
rodded.
7. Where knockout
blocks are used, steel shall be erected and wired in place before
three courses have been laid. Vertical cores at steel locations
shall be filled as construction progresses.
8. Where knockout
blocks are not used, vertical cores at steel locations shall be
filled in lifts of not more than 4 feet. The maximum height of pour
shall be 8 feet. Cores shall be cleaned of debris and mortar and
shall have reinforcing steel held straight and in place. If ordered
by the ENGINEER, inspection and cleanout holes shall be provided at
the bottom of each core to be filled.
9. Reinforcing steel
shall be inspected prior to placing grout. B. Foundation Dowels:
1. The size, number,
and location of the foundation dowels shall match the vertical wall
reinforcing unless otherwise noted.
2. When a foundation
dowel does not line up as intended, with a vertical core, it shall
not be sloped more than 1 horizontal to 6 vertical to bring it into
alignment.
3. Dowels shall be
accurately placed to match reinforcing in filled cells.
C. Vertical
Reinforcing:
Vertical reinforcing steel shall be held in position near the ends
of the bars by wire ties to dowels and/or by reinforcing
positioners. The bars shall be held in position at intervals not
exceeding 160 bar diameters by reinforcing positioners.
D. Horizontal
Reinforcing:
Horizontal bars shall be laid on the webs of bond beam units, and
shall be placed as the wall is built.
3.11
GROUTING
A. Grout
Preparation:
Grout shall be mixed as specified hereinbefore for mortar
preparation if onsite mixing is performed. Transit-mixed grout
shall meet the requirements of ASTM C 476. The grout admixture
shall be added at the site. In accordance with the specified grout
admixture manufacturer's recommendations, the admixture shall be
premixed with water and the resulting solution shall be added to
the grout mix and thoroughly mixed. Do not exceed quantity
of admixture recommended by the manufacturer.
B. General:
1. All debris and
projecting mortar shall be cleaned out before pouring grout.
2. Grout pour shall be
stopped 1-1/2 inches below the top of a course to form a key at pour
joints.
3. Grout shall not be
mixed, conveyed, or placed with equipment constructed of aluminum.
4. All vertical and
horizontal reinforcement, ties, bolts, anchors, and other required
embedments shall be secured in place, inspected, and accepted before
grouting starts.
5. Grouting of beams
over openings shall be done in one continuous operation.
6. Vertical cells to
be filled shall have vertical alignment sufficient to maintain a
clear, unobstructed, continuous vertical cell measuring not less
than 2 inches by
3 inches.
7. Grout shall be
poured as soon as possible after the mortar has cured to reduce
shrinkage and cracking of the vertical joints. Immediately after
the grouting has been completed, the scum and stains on the masonry
shall be washed off using clean water and fiber brushes. Grout and
mortar stains shall not be allowed to dry on the face of the exposed
masonry.
8. Vertical
reinforcement may be placed initially and the wall built up around
it, providing the reinforcing steel is first wire tied to the
foundation dowels. Reinforcing positioners and/or accepted cross
bracing shall be provided to secure the top of the steel in place.
The vertical steel will not be permitted to be dropped in after the
block is laid unless reinforcing positioners are provided in the
course above the previously grouted course.
C. Grouting
Requirements:
1. Solid
Grouting Requirements:
Walls that are to be solid grouted shall have vertical grout
barriers spaced not more than 30 feet apart, and which extend the
full height of the wall.
2. Partial Grouting
Requirements:
a. Walls that do
not require solid grouting shall have all cells containing
reinforcing steel and others as shown filled with grout.
b. Cells to be filled
shall be constructed to confine the grout within the cell. Tops of
unfilled vertical cells under a bond beam shall be covered with
metal lath to confine the grout fill to the bond beam section.
c. Grout pours shall
be limited in height to mid-depth of the course above the horizontal
bond beam, except at the top course.
D. Low-Lift Grouting
Requirements:
1. Unless otherwise
accepted by the ENGINEER prior to the start of the masonry work, all
grouting shall be low-lift grouting.
2. When grouting is
stopped for 1 hour or longer, horizontal construction joints shall
be formed by stopping the pour of grout 1-1/2 inches below the top
of the uppermost unit. Horizontal steel shall be fully embedded by
grout in an uninterrupted pour.
3. Grout pour shall be
limited to a maximum height of 4 feet. The wall shall not be
constructed more than one course above the top of the grout pour
prior to placing the grout.
4. The grout shall be
thoroughly consolidated with an internal "pencil" type
vibrator operating at 5,000 RPM, to consolidate and reduce the
amount of air voids. After waiting sufficient time to permit the
grout to become plastic, but before it has taken any set, the grout
shall be reconsolidated. The waiting period will vary depending
upon weather conditions and block absorption rates, but under
"normal" weather conditions with average masonry units,
the waiting period should be between 30 to
60 minutes.
E. High-Lift Grouting
Requirements:
1. Walls built with
open-end units as shown shall not be grouted using the high-lift
method. Standard construction masonry may be high-lift grouted if
accepted by the ENGINEER.
2. Cleanouts of
sufficient size to permit cleaning of the cell, positioning of the
reinforcing and inspection shall be provided at the bottom of
every vertical cell containing reinforcing. The location of the
cleanout shall be such that it is not exposed to view after final
construction, unless otherwise accepted by the ENGINEER.
3. After the wall
has been inspected and accepted and prior to grouting, all
cleanouts shall be capped in a manner that will seal them from grout
leakage and provide a flush finish.
4. Grout pours shall
be limited to 12-foot heights, with lifts not exceeding 4 feet. Each
lift shall be thoroughly consolidated with an internal "pencil"
type vibrator. Succeeding lifts shall not be placed until the
previous lift has become plastic. Succeeding lifts shall be vibrated
into the previous lift.
5. The last grout pour
on a wall shall be reconsolidated as specified for low-lift
grouting.
3.12
CURING
A. Masonry and mortar
joints shall be wetted frequently for at least 3 days to ensure
proper curing of mortar.
3.13
CLEANING
A. Clean all surfaces
of excess mortar, grout spillage, dirt, and other foreign substances.
B. Walls not requiring
painting or sealing shall be cleaned such that there are no visible
stains.
C. No construction
supports shall be attached to the wall except where
specifically permitted by the ENGINEER.
D. Concrete and grout
spilled on the wall shall be washed off before it can set up. At the
conclusion of the masonry work, the CONTRACTOR shall clean down all
masonry walls, remove any scaffolding and equipment used in the Work,
clean up all debris, refuse and surplus material, and remove it from
the premises.
E. Surfaces requiring
painting or sealing shall be prepared in accordance with Section
09905, Architectural
Paint Finishes.
3.14
PROTECTION
A. At the end of each
day's work, tops of walls shall be covered with building paper or by
other means that will protect the walls from becoming excessively
wet.
3.15
TEMPORARY
BRACING
A. The CONTRACTOR shall
adequately brace all walls until the walls and roof are completed.
Bracing shall be sufficient to protect the walls against damage from
the elements, including wind.
3.16
SEALING
A. All block walls,
unless otherwise indicated, shall be sealed on the exterior with a
water- repellent sealer as specified in Section 07130, Concrete
Sealer and Hardener.
No comments:
Post a Comment