Section 11079
PUMPING EQUIPMENT: DIAPHRAGM METERING
PUMPS
PART 1 - GENERAL
1.1 SUMMARY
A. The CONTRACTOR shall furnish and
install chemical feed diaphragm pumps and necessary appurtenances as
shown on the Drawings and specified herein, including speed and
stroke controls, calibration cylinders, back pressure valves and
pulsation dampeners for complete operation.
1.2 RELATED SECTIONS
A. The Work of the following
Section applies to the Work of this Section. Other Sections,
not referenced below, shall also apply to the extent required for
proper performance of this Work.
1. Division 01, Additional General
Requirements
2. Section 11005, Equipment: Basic
Requirements
3. Section 11210, Pumps, General
4. Section 15885, Odor Reduction
System
5. Section 16010, Electrical and
General Provisions
6. Section 16220, Electric Motors
7. Section 16442, Control Panels
8. Section 17300, Control Strategy
9. Section 17405, Process
Instrumentation and Control
1.3 CONTRACTOR SUBMITTALS
A. Shop Drawings: The
CONTRACTOR shall submit shop drawings showing fabrication,
assembly, foundation, and installation details, along with detailed
specifications and data covering materials of
construction, devices, and other accessories forming a part of
the equipment. The shop drawings shall be provided in accordance
with this Section and the requirements of Section 11005, Equipment:
Basic Requirements, and Section 11210, Pumps, General.
B. Documentation: The CONTRACTOR
shall submit documentation that all equipment and piping is
compatible with chemical in service.
C. Diaphragm Metering Pumps: For
diaphragm metering pumps, the CONTRACTOR shall submit capacity,
discharge pressure, HP and data on assembly, anchor bolts, and
mounting. The CONTRACTOR shall provide data on variable speed
drives that shall include catalogue cuts on all drive equipment,
controls, accessories, and wiring requirements.
D. Motors: For motor driven
equipment, the CONTRACTOR shall submit motor data meeting the
requirements of Section 16220, Electric Motors.
E. Instrumentation: For
instrumentation associated with chemical feed equipment, the
CONTRACTOR shall submit catalogue cuts,
wiring diagrams, and equipment data.
F. Instructions: The CONTRACTOR
shall provide field assembly, installation and operation and
maintenance instructions in conformance with Section 11005,
Equipment: Basic Requirements.
1.4 QUALITY ASSURANCE
A. All equipment furnished shall be
new and of best quality entirely suitable for the purpose intended.
1.5 WARRANTY
A. The metering pump drive train,
including gear reducer, transmission, hydraulic make- up system, and
housing and all components specified in this Section shall be
warranted by the manufacturer for a minimum five (5) year period
after beneficial occupancy of the Work pursuant to “Use Prior to
Final Completion” of the General Conditions, against defects in
workmanship and materials. Other components shall have a one (1)
year warranty period after beneficial occupancy.
PART 2 - PRODUCTS
2.1 DIAPHRAGM METERING PUMPS
A. General: The metering pumps
shall be hydraulically balanced diaphragm type with non-loss motion
drive. The drive motor shall actuate a flat, Teflon diaphragm. The
liquid ends shall provide for easy maintenance. The feed pumps shall
be capable of feeding the indicated fluid of service from the
corresponding storage tank to the injection point as shown on the
Drawings.
B. Pump Features:
1. Pumps shall accept readily
available "off-the-shelf" NEMA 56C flange motor in
accordance with requirements of Section 11005, Equipment: Basic
Requirements.
2. Capacity adjustment shall be 0 to
100 percent by calibrated external stroke adjustment accurate to
approximately 1 percent which shall show stroke length setting.
3. Valves shall be flange-mounted or
union coupled to permit easy access for cleaning and service so
that piping does not have to be disconnected. Valve
chambers shall be such that individual components can be replaced
rather than entire assemblies.
4. Pumps shall have a manual stroke
adjustment from 0 to 100 percent that can be accomplished while idle
or operating. An auto-lock for the manual stroke adjustment shall be
provided.
5. The drive mechanism and gearing
shall be of hardened and ground steel and bronze. Gear box shall be
water resistant. Plastic gear boxes will not be acceptable.
6. Pumps shall be able to operate
dry indefinitely without damage.
7. All pumps, fittings, gear boxes,
etc. shall be chemical and corrosion resistant.
8. A relief valve shall be provided,
which, in the event of discharge line stoppage, shall recycle
hydraulic fluid back to the reservoir.
9. At a constant motor speed, the
metering pumps shall feed within plus or minus 1 percent of the set
rate throughout a 10:1 feed range. The repeatability of the set
point shall be within plus or minus 1 percent of actual.
10. Pulsation dampeners shall be
provided.
11. Pump head shall have gravity
seated ball-type check valves on the inlet and outlet sides. Valve
ball shall be ceramic with PTFE seats. Spring loaded check valves
are not acceptable. Valves and seat shall be individually
replaceable and sealed with PTFE O-ring or flat gasket.
C. Pump Quality: All pumping
equipment furnished under this Section including the variable speed
drives shall be of a design and manufacture of:
1. MilRoyal by Milton Roy.
2. Pulsar by Pulsafeeder.
3. Or Equal.
D. Sodium Hypochlorite Feed Pump
1. Design Conditions:
a. Tag Numbers:
17GPMP270,17GPMP275, 17GPMP280, 17GPMP285,
17GPMP290, 17GPMP295
b. Capacity (gallons/hour): 12
c. Minimum Flowrate (gallons/hour):
4
d. Operating Backpressure (pounds
per inch): 50 e. Maximum Backpressure (pounds per inch): 150 f.
Fluid: Sodium Hypochlorite 12.5 percent
g. Wetted Parts: PVDF
h. Diaphragm: PTFE
i. Inlet/Outlet Size NPT: 1 inch ID
2. Pump Requirements:
a. Pump shall be equipped with
auto-degassing device to prevent gas locking the pump. Degassing
device shall be integral to pump and supplied by pump manufacturer.
b. Pump shall be equipped with leak
detection to detect diaphragm failure. Leak detection shall be by
the original pump manufacturer.
c. All wetted parts, O-rings and
seals shall Teflon. E. Sodium Hydroxide Feed Pump:
1. Design Conditions:
a. Tag Numbers: 15KPMP250,
15KPMP260, 15KPMP270, 15KPMP280,
15KPMP290, 15KPMP300
b. Capacity (gallons/hour): 5
c. Minimum Flow rate (gallons/hour):
0.5
d. Operating Backpressure (pounds
per inch): 50 e. Maximum Backpressure: 150
f. Fluid: Sodium Hydroxide 25
percent g. Wetted Parts: CPVC or PVDF
h. Diaphragm: PTFE
i. Inlet/Outlet Size NPT: 1 inch ID
2. Pump Requirements:
a. Pump shall be equipped with leak
detection to detect diaphragm failure. Leak detection shall be by
the original pump manufacturer.
b. All wetted parts, O-rings and
seals shall be Teflon.
F. Sulfuric Acid Feed Pump:
1. Design Conditions:
a. Tag Numbers: 15KPMP310,
15KPMP320, 15KPMP330 b. Capacity (gallons/hour): 12
c. Minimum Flowrate (gallons/hour):
0.3
d. Operating Backpressure (pounds
per inch): 50 e. Maximum Backpressure (pounds per inch): 150 f.
Fluid: Sulfuric Acid 93 to 98 percent
g. Wetted Parts: PVDF or PTFE
h. Diaphragm: PTFE
i. Inlet/Outlet Size NPT: 1 inch ID
2. Pump Requirements:
a. Pump shall be equipped with leak
detection to detect diaphragm failure. Leak detection shall be by
the original pump manufacturer.
b. All wetted parts, O-rings and
seals shall be Teflon. G. Pump Controls:
1. Metering pumps shall be
controlled as described in Section 17300, Control Strategies and
as shown on the P&IDs. Failure of the duty pump shall close a
set of contacts and actuate alarms. The speed of the feed pumps
shall be controlled through speed indicating controllers and shall
be flow paced from a 4-20 mA DC signal from the programmable logic
controller (PLC). The speed indicating controllers shall be mounted
in the field control panel (FCP). Remote contacts shall be provided
to indicate operating lights and alarms on the face of the UCP. The
chemical pumps shall be capable of remote starting and stopping
through two sets of voltage free contacts from the PLC. The chemical
pumps shall be provided with a low suction pressure switch and a
high discharge pressure switch for pump protection. The pump shall
be shutdown in either condition. Reset switches shall be provided to
reset alarms.
H. The UCP shall interface with the
PLC, as shown on the Drawings.
I. Variable Speed Drives: Variable
speed drives shall be of the direct current drive type equipped to
follow a 4 to 20 mA signal from the PLC. Variable speed drives
shall have the following features.
1. Drive controllers shall be in a
dust and oil tight enclosure with speed adjustment dial,
manual-automatic, on-off, and start-stop switches.
2. Input power shall be 115 V, 60
Hz, single phase.
3. Drives shall be capable of
overload up to 150 percent of full load torque for one minute.
4. Drives shall be equipped to
follow output signals (4 to 20 mA DC). Full motor speed shall occur
at maximum input signal; minimum motor speed shall occur at minimum
input signal. Drive shall have isolated input for receiving PLC
output signal of 4-20mA.
5. Drives shall have a tachometer
feedback for speed regulation with 1 percent accuracy over a 95
percent load change and shall provide 4-20 mA signal to pump station
PLC. Drive shall have isolated output for providing PLC input signal
of 4-
20mA corresponding to speed of the
pump with 20mA at maximum speed.
6. The drive controller shall be
provided with spare contactors for interconnection with remote
devices.
7. The drive manufacturer
shall provide isolation transformers and other accessories
to produce an operating system responsive to the requirements
herein.
8. The drive controller shall be
mounted in the corresponding UCP and each drive controller shall be
contained in a NEMA 4X 316 Stainless Steel enclosure.
9. The drive controller shall have
adjustments for maximum speed, minimum speed, current limit and
torque.
10. The pump supplier shall have
unit responsibility for the performance and operation of the
variable speed chemical feed pumps and drives.
11. EMI and RFI emissions shall not
exceed the levels referenced in FCC Rules and Regulations Volume 2
Part 15 Subpart J Class A. If after installation, any interference
or noise occurs, the supplier shall take corrective action by
installing additional equipment or corrective measures required, at
no additional cost to the OCSD.
J. Motors: Motors shall be 1/2 HP, 3
phase, totally enclosed non-ventilated (TENV) with NEMA 56C face
with mounting feet and thermal overload and 1,750 rpm base speed.
Thermal overload shall be connected to the failure alarm. Motors
shall be in accordance with Section 16220, Electric Motors.
K. Fasteners: All bolts and cap
screws shall be Type 316 stainless steel. All anchor bolts, nuts and
washers shall be Type 316 stainless steel and of sufficient length
to allow
1-1/2 inches of grout under pump
bases.
L. Guards: Guards shall be
provided at all exposed couplings, drives and shafts in compliance
with Section 11005, Equipment: Basic Requirements.
2.2 CALIBRATION CYLINDERS
A. Calibration cylinders shall be
designed for chemical pump calibration. The calibration cylinders
shall consist of a plastic, graduated cylinder with a capacity and
mounting nipple as indicated below. Calibration cylinders shall be
supplied by Griffco, Koflo, Milton Roy, Pulsafeeder, Or Equal.
-
MountingNipple, inch
ColumnMaterial
Sodium hypochlorite PumpCalibration Column
1,000
1
PVC
Sulfuric Acid PumpCalibration Column
500
1
PTFE or PVDF
Sodium hydroxide PumpCalibration Column
1,000
1
PVC
2.3 PULSATION DAMPENERS
A. Sodium Hypochlorite and Sodium
Hydroxide Service: Each diaphragm metering pump shall be equipped
with a pulsation dampener and isolation ball valves. Pulsation
dampeners shall be single diaphragm type and shall limit pressure
oscillation above and below mean pressure to a maximum of 5 percent
with the air chamber charged to a pressure of 50 percent of mean
line pressure. Pulsation dampeners shall of the chargeable type
and shall include a 2-1/2-inch stainless steel pressure gauge. The
bottom chamber shall be CPVC or PVDF, the top air chamber shall be
CPVC or PVDF, and the diaphragm shall be Hypalon. Pulsation
dampener shall be rated for 150 pounds per inch pressure. Pump
manufacturer shall submit calculation for the size of the dampener
based on stroke volume of the selected pump. Pulsation dampeners
shall be Blacoh, Milton Roy, Pulsafeeder, Or Equal.
B. Sulfuric Acid Service: Each
diaphragm metering pump shall be equipped with a pulsation dampener
and isolation ball valves. Pulsation dampeners shall be single
diaphragm type and shall limit pressure oscillation above and below
mean pressure to a maximum of 5 percent with the air chamber charged
to a pressure of 50 percent of mean line pressure. Pulsation
dampeners shall be of the chargeable type and shall include a 2-
1/2-inch stainless steel pressure
gauge. For the sulfuric acid service, the pressure gauge shall be
2-1/2-inch molded PVDF. The bottom chamber shall be PVDF, the top
air chamber shall be PVDF, and the diaphragm shall be Teflon.
Pulsation dampener shall be rated for 150 pounds per inch pressure.
Pump manufacturer shall submit calculation for the size of the
dampener based on stroke volume of the selected pump. Pulsation
dampeners shall be Blacoh, Milton Roy, Pulsafeeder, Or Equal.
2.4 ACCESSORIES
A. The CONTRACTOR shall provide
discharge pressure gauges with isolation diaphragm seals and
valves for chemical feed systems as shown on the Drawings and
specified in Section 17405, Process Instrumentation and Control.
2.5 UNIT CONTROL PANEL
A. Refer to Section 16442, Control
Panels, and applicable section of Section 17405, Process
Instrumentation and Control.
2.6 OTHER MATERIALS
A. Fabrications: Steel fabrications
for mountings and anchorages shall conform to the requirements of
ASTM A-36 for fabricated steel.
B. Shop Coatings: Shop coat exposed
ferrous metal surfaces in conformance with
Section 09800, Protective Coating.
PART 3 - EXECUTION
3.1 INSTALLATION AND STARTUP
A. The CONTRACTOR shall examine the
equipment delivered to the site to determine that it is in
conformance with the approved shop drawings. The equipment shall
be installed in conformance with Section 11005, Equipment: Basic
Requirements. The CONTRACTOR shall coordinate activities with
the instrumentation, monitoring and control work specified in
Division 17. At no additional cost to the OCSD, the CONTRACTOR shall
furnish the services of a competent factory-trained representative
of equipment supplier or manufacturer to assist in and supervise the
initial operation.
3.2 FIELD COATING
A. Field coat exterior surfaces in
conformance with Section 09800, Protective Coating. Before placement
of any equipment, the CONTRACTOR shall finish coat any exterior
surfaces which will rest on slabs or be otherwise covered up.
3.3 SPARE PARTS
A. One complete set of spare parts
to include a diaphragm, a set of check valve seats and balls,
gaskets, O-rings, and other consumable parts shall be included for
each pumping head on each of the systems.
3.4 MAINTENANCE OF INSTALLED
EQUIPMENT
A. Maintain the operability and
functionality of all installed equipment valves between the time of
installation and the commissioning period. See Specification section
01660 for requirements.
3.5 FIELD SERVICES
A. Furnish the services of authorized
technical representatives of the Manufacturer to assist/inspect the
installed equipment and to certify that the equipment has been
properly installed and is ready to operate, train OCSD personnel,
conduct pre-operational mechanical checkout of the equipment, place
equipment into operation, optimize the performances of the equipment
and perform the field performance testing.
B. At a minimum, conduct four
separate site visits as follows:
a. Inspection of equipment
installation – two trips (8 hours minimum, each)
b. Training of OCSD personnel.
See Specification section 01820, Training of
OCSD Personnel, for requirements.
c. Commissioning. See Specification
section 01810, Commissioning, for requirements. Number of hours
shall be as required to meet all testing and commissioning
requirements, but shall not be less than 16 hours.
3.6 EQUIPMENT TESTING
A. Equipment testing shall conform to
the requirements of Section 11005, Equipment: Basic Requirements.
No comments:
Post a Comment