Section 13205
DOUBLE WALL HORIZONTAL ABOVEGROUND FUEL
STORAGE TANKS
PART 1 - GENERAL
1.1 THE REQUIREMENT
The CONTRACTOR shall furnish and
install a double wall horizontal aboveground fuel storage steel
tank complete with accessories as specified herein and
indicated on Drawings. This Specification covers insulated
aboveground horizontal fuel storage tank which shall be supplied with
fill system and accessories necessary for the completed unit to meet
all applicable safety and code requirements. The unit shall be
pre-assembled by the manufacturer such that it is ready for operation
once power and control wiring are connected at the end user site. The
accessories may be installed on site if deemed necessary by the
manufacturer. CONTRACTOR to arrange and pay for all permits,
inspections and tests as required by federal and local codes.
1.2 RELATED WORK SPECIFIED
ELSEWHERE
A. The requirements of the following
Sections and divisions apply to the Work of this section. Other
Sections and divisions of the Specifications, not referenced below,
shall also apply to the extent required for proper performance of
this Work.
1. Division 01, Additional General
Requirements
2. Section 03300, Cast-in-Place
Concrete
3. Section 05505, Metal Fabrications
4. Section 09800, Protective Coating
5. Section 15000, Piping, General
6. Section 15100, Valves, General
7. Section 16442, Control Panels
8. DIVISION 16, Electrical
9. DIVISION 17, Instrumentation and
Control
1.3 REFERENCE SPECIFICATIONS,
CODES, AND STANDARDS
A. All Work specified herein shall
conform to or exceed the applicable requirements of the referenced
portions of the following publications to the extent that the
provisions thereof are not in conflict with other provisions of these
Specifications.
B. Comply with the latest editions of
the following codes, regulations and standards.
1. NFPA 30: Flammable and Combustible
Liquids
2. NFPA 31: Standard for Installation
of Oil Burning Equipment
3. STI: Steel Tank Institute
4. UL: Underwriter's Laboratory.
5. ASTM C-332: Standard Specification
for Lightweight Aggregates for Insulating
Concrete.
6. California Air resources Board
(C.A.R.B).
1.4 WARRANTY
A. The fuel storage tank and all
components specified in this section shall be warranted by the
manufacturer for a minimum five (5) year period after beneficial
occupancy of the Work pursuant to “Use Prior to Final Completion”
of the General Conditions, against defects in workmanship and
materials. Prorated warranties are not acceptable.
1.5 SUBMITTALS
A. Shop Drawings: CONTRACTOR shall
submit copies of shop drawings for complete tank package including
equipment datasheets, catalog cuts and electrical wiring diagrams.
The catalog cuts shall include all components including all
mechanical,electrical and control components. Provide layout of
all piping indicating location of fittings and accessories with
specific dimensions and erection drawings. Shop drawings shall
include tank supports and seismic restrains based on seismic
requirement for Zone 4 with calculations signed and stamped by a
profissional Engineer registered in the State of California.
B. Shop Drawing Approval:
CONTRACTOR shall submit shop drawings for approval and wait to
receive drawing acceptance prior to product fabrication.
C. Certification: Tank shall bear the
U.L. 142 label for aboveground liquid storage.
PART 2 - PRODUCTS
2.1 GENERAL
A. Materials:
1. Only new material shall be used in
the manufacturing process and the manufacturer shall ensure that the
material used meets all appropriate specifications and quality
assurance requirements.
B. Dimensional Requirements:
1. Nominal storage capacity of the
tank shall be 2,000 gallons.
2. Nominal height of the tank shall
not exceed 60 inches.
3. Nominal width of the tank shall
not exceed 78 inches.
4. Nominal Shell length shall shall
not exceed 144 inches.
C. Loading Conditions: Tank shall
meet the following design criteria.
1. Internal Load: Tank(s) shall
withstand an air pressure test of 5 pounds per inch.
2. Tank shall be designed to
support accessories when installed according to manufacturer's
instructions and limitations.
3. Tank shall be provided with
suitably designed and located lifting lugs which have a 2:1 safety
factor.
D. Tank Unit Description:
1. Tank unit shall be an insulated
aboveground tank (with secondary containment) used for storing
flammable liquids. All accessories shall be C. A. R. B. approved
components.
2. Tank unit shall be composed of a
horizontal steel primary storage tank with a secondary leak
containment shell of a minimum 1/4 inch thick steel plate.
3. The primary and secondary
containment steel shells shall be constructed according to UL
Standard 142 requirements of horizontal tank.
4. Tank shall be delivered as a
complete UL-listed assembly with two factory supplied, welded-on
saddles. Size and location of saddles shall be as required by tank
manufacturer to comply with seismic and wide design criteria for the
Project. Saddles to be set level on a solid concrete foundation in
the containment pad indicated on the Drawings. The saddles shall
provide a 6-inch (Nominal) space between the foundation pad and the
underside of the tank
5. Provisions shall be made to
enable heavy equipment to lift and move the entire unit.
6. Exterior Protective Coating:
a. Surface Preparation: Grit blast -
SSPC-SP-6 Commercial Blast. b. Finish coating system minimum 7 DFT
on the shell and heads.
c. Prime coat (DFT = 4 mils) Tnemec
Pota-Pok Plus Series L 140, Or Equal from Carboline Coatings
Company.
d. Finish coat (DFT = 3 mils) Tnemec
Endura-Shield Series L 1081, Or Equal from Carboline Coatings
Company.
7. Tank shall be manufactured and
labeled in strict accordance with Steel Tank Institute (STI)
Fireguard® Thermally Insulated, Double Wall Steel Aboveground
Storage Tank standards as applied by a licensee of the STI. Tank
shall be subject to the STI’s Quality Assurance program and shall
be backed by the STI 30 year limited warranty.
E. Emergency Vent:
1. Primary and secondary tanks
shall be furnished with a 6-inch diameter emergency vent
fittings.
2. Primary tank shall be furnished
with a 6-inch diameter UL listed emergency vent valve.
F. Tank Openings:
1. All tank openings (interfaces
with accessories) shall be threaded fittings with thread protectors.
G. Overfill Protection Valve:
1. The fill pipe shall be fitted
with a level control valve which terminates the flow when the fuel
level in the tank reaches 85 to 95 percent (adjustable) full. After
shut off, product shall be allowed to drain from the highest point
so fill nozzle can be removed without spilling. The valve size shall
be 2-inch diameter.
2. A lockable fill cap shall be
provided.
H. Overfill and Leak Detection Alarm
System:
1. The tank unit shall be provided
with a float type sensor, part of the overfill protection valve,
installed in the tank and pre-set to signal the 90 percent full
level fill. The overfill system shall be UL listed and meet the
requirements of NFPA 30.
2. A leak detection device shall be
installed in the interstitial space. This detector shall sense
leakage of fuel. The sensor shall provide signal to the alarm panel.
3. An Alarm panel shall be provided
in a location clearly visible to the fuel delivery operator.
4. The panel shall be provided with
a lamp (visible in sunny daylight) for each detection signal.
5. The panel shall be provided with
a warning horn that sounds continuously when a signal is received
from either sensor.
6. The Alarm Panel shall be
weatherproof constructed to meet NEMA 4X requirements for this type
of application. The panel construction, lights, switches, buttons,
etc. shall meet the requirements of Section 16442, Control Panels.
Identification of the panel and devices shall meet the requirements
of Section 16075, Electrical Identification Nameplates and Warning
Signs.
7. Operating Features of the Panel:
a. If a leak or overfill is
detected, the sensor shall provide a signal to the panel where an
identified lamp will light to show that a leak or overfill has
occurred. Two lights are required. This same signal shall
continuously sound a single common warning Horn having 80 dB output.
The horn shall be silenced by manually activating a override switch.
The lamp shall remain lit until the sensor causing the signal goes
out of alarm.
I. Tank Insulation:
1. The interstice space between
the shells shall be completely filled with a lightweight,
monolithic material. The thermal insulation material
shall be a composition of perlite, cement, water and special
materials recommended by the tank manufacturer.
J. Tank Indicator Gauge:
1. A direct reading "E- F"
tank mounted float type indicator gauge shall be provided and
located such that it is clearly visible to the fuel delivery
operator during filling. This gauge shall provide an indication of
the nominal amount of product in the tank. Indicator readout may be
in inches, or percent tank fill, or fraction of tank fill.
K. Tank Level Transmitter:
1. Provide an ultrasonic level
transmitter to measure fuel tank level. The transmitter output shall
be wired to the Plant PLC. The ultrasonic level transmitter shall be
as specified in Section 17405, Process Instrumentation and Control,
2.16.D.
L. Combination Pressure /Vacuum
Relief Valve and Vent:
1. A minimum 2-inch diameter vent
shall be provided, which terminates 12 feet above grade. The normal
vent pipe assembly will be shipped loose and installed by the
Contractor on site. A pressure/vacuum relief valve shall limit the
internal tank pressure to 1 psig and the vacuum to 1 oz psig
M. Spare Openings:
1. A 2-inch diameter capped access
port shall be provided. Location of the spare opening shall be per
tank manufacturer.
N. Fill Port:
1. The tank fill port shall have an
adapter fitting that mate with the fill hose. The adapter fitting
shall have a lockable protective cap for use when tank is not being
filled.
O. Drop Tube:
1. Drop tube shall be 3-inch
diameter aluminum. Tube shall extend to near bottom form submerged
fill.
P. Supply Pipe Strainer:
1. The strainer shall be installed
at the inlet of the supply pipe, placed at the bottom of the storage
tank. Screen shall be brass with 20 mesh stainless steel screen.
2.2 WARRANTY
A. The CONTRATOR warrants to the
OCSD that all fuel storage tanks furnished under this Specification
shall be new, and of good material and workmanship, and agrees to
replace promptly any part or parts which by reason of defective
material or workmanship shall fail under normal use, free of
negligence or accident, for a minimum of 12 months from date put in
operation.
2.3 MANUFACTURERS
A. Highland Tank, Stoystown, PA. B.
Southern Tank, Owensboro, KY. C. Or Equal.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Tank shall be installed in
strict accordance with the most recent installation
instructions provided by the tank manufacturer, PEI/RP200, UFC, NFPA
30, local ordinance, recognized engineering procedure, and other
applicable codes.
3.2 TANK UNIT IDENTIFICATION AND
INFORMATION SIGNS
A. Signs shall be provided that show
the information described below as a minimum. Additional signs may
be necessary to meet local county and municipal codes.
1. Manufacturers name.
2. UL listing labels.
3. Date of tank manufacture.
4. Type of product stored in tank,
including the API color coded symbol for the product.
5. Working capacity and tank model
number.
6. Decals per NFPA 704.
B. Rustproof signs shall be fastened
to the tank with suitable rustproof brackets and fasteners. Signs
must be removable for repainting the tank.
3.3 MANUFACTURER’S FIELD
SERVICES
A. Furnish the services of
authorized technical representatives of the Manufacturer to
assist/inspect the installed equipment and to certify that the
equipment has been properly installed and is ready to operate, train
OCSD personnel, conduct pre-operational mechanical checkout of the
equipment, place equipment into operation, optimize the performances
of the equipment and perform the field performance testing.
B. At a minimum, conduct two
separate site visits as follows:
1. A. Inspection of
equipment installation (4 hours minimum)
2. B. Training of OCSD
personnel. See Specification section 01820 for requirements.
3.4 TESTING
A. Tank shall successfully complete
an air pressure test of 5 pounds per inch prior to installation.
3.5 FIELD PAINTING
A. All components shall be shop
coated and refer to Section 09800, Protective Coating, for touch up
requirements and procedure for compatible system.
No comments:
Post a Comment