Section 15030 PIPING IDENTIFICATION SYSTEMS

Section 15030

PIPING IDENTIFICATION SYSTEMS

PART 1 - GENERAL

1.1 THE REQUIREMENT

A. The CONTRACTOR shall furnish, paint, mark, and paint/install identification devices for all exposed piping and piping in accessible chases and areas above ceilings with panels, and valves using, lettering, flow direction arrows, and related permanent identification devices, and all appurtenant Work, in accordance with the requirements of the Contract Documents.

1.2 RELATED WORK SPECIFIED ELSEWHERE

A. The requirements of the following sections and divisions apply to the Work of this section. Other sections and divisions of the Specifications, not referenced below, shall also apply to the extent required for proper performance of this Work.

1. Section 09800, Protective Coating

2. Division 11, Equipment, applicable sections

3. Division 15, Mechanical, applicable sections

4. Division 16, Electrical, applicable sections

5. Division 17, Instrumentation and Control, applicable sections

1.3 REFERENCE SPECIFICATIONS, CODES AND STANDARDS

A. All Work specified herein shall conform to or exceed the applicable requirements of the referenced portions of the following publications to the extent that the provisions thereof are not in conflict with other provisions of these Specifications.

B. Comply with the applicable editions of the following codes, regulations and standards.

1. Codes and Regulations:

C. OCSD – Tagging Procedure Standard:

2. Industry Standards:

D. ASME A13.1 – Scheme for the Identification of Piping Systems.

E. Comply with the applicable reference Specifications as directed in the General
Requirements and Additional General Requirements.
1.4 CONTRACTOR SUBMITTALS

A. Submittals shall be made in accordance with the General Requirements, Additional
General Requirements and as specified herein.

B. The CONTRACTOR shall submit samples of all types of identification devices to be used in the Work.

1.5 QUALITY ASSURANCE (NOT USED)

PART 2 - PRODUCTS

2.1 IDENTIFICATION OF PIPING

A. All exposed piping and piping in accessible chases and areas above ceilings with panels, including stainless steel, galvanized steel, copper, CPVC, and Fiberglass RTR piping, shall be completely and totally painted for identification purposes. Piping shall be identified with lettering or tags designating the service of each piping system shall have flow directional arrows. All piping scheduled to be color-coded shall be completely painted or coated with the colors indicated in the schedule below.

B. Each pipe identification shall consist of color-coding in accordance with Article 3.4 entitled “Identification Schedule”, a painted or adhesive label and a directional flow arrow. Piping identification shall be located in accordance with Article entitled “Pipe Identification Location” herein.

C. For cases where there are insulated lines wrapped with aluminum sheathing, stainless steel sheathing, or gray fabric, the background color shall be applied to a
24-inch length of pipe section and color band centered within the 24-inch field of background color.

D. Paint Colors: Paint colors shall conform to the following designations, Or Equal:


Color Mfg./No.
Paper

White
DuPont 40P-1031
Tnemec F075-WH01A Dunn Edwards IP630-SY-1


Dark

Brown
DuPont 40P-1039

Tnemec F075-D2526A

Dunn Edwards IP630-SY-25


Safety

Red
DuPont 333-23664

Tnemec F075-S1170A

Dunn Edwards IP630-SY-19
Color Mfg./No.

Safety

Orange

DuPont 40P-1030

Tnemec F075-S1169A

Dunn Edwards IP630-VD9222



Light

Gray
DuPont 333-23662

Tnemec F075-A2606A

Dunn Edwards IP630-RL7422


Light

Gray
DuPont 333-23662

Tnemec F075-A2606A

Dunn Edwards IP630-RL7422


Safety

Red
DuPont 333-23664

Tnemec F075-S1170A

Dunn Edwards IP630-SY-19


Caribbean

Blue
DuPont 40P-1048

Tnemec F075-B2478A

Dunn Edwards IP630-UD10264


Safety

Blue
DuPont 40P-1048

Tnemec F075-B2477A

Dunn Edwards IP630-VD10265


Spectra Master

(Dark Blue)
DuPont 40P-1496

Tnemec F075-B2476A

Dunn Edwards IP630-SY-23

Custom Formula

(Purple)
DuPont 40P-1628

Tnemec F075-R1217A

Dunn Edwards IP630-SY-13


Cool

Green
DuPont 40P-1008

Tnemec F075-S1168A

Dunn Edwards IP630-UL9585
Color Mfg./No.


Safety

Yellow
DuPont 333-23663

Tnemec F075-S1167A

Dunn Edwards IP630-UD9223

E. Lettering:

1. Stencils or Markers: Contents identification labels and directional arrows shall be painted directly on piping using stencils.

2. Pipe identification markers shall be vinyl or polyester construction with an adhesive strip, coiled to wrap completely around the pipe (no straps) and have subsurface printing. Pipe less than 6 inches shall be have lettering to meet ASME A13.1 standard and shall be Marking Services Inc., MS-970 or MS-995; Accuform Subsurface Snaptite; Or Equal. Pipe 6 inches or larger shall have 2-inch lettering on a 12-inch field minimum and shall be Marking Services Inc., MS-995; Accuform Subsurface Snaptite; Or Equal.

3. The size of the letters for identification labels shall be as follows:

Pipe Outside Diameter* (inches)
Letter Size
(inches high)
5/8 to 1-1/4
1/2
1-1/2 to 3
1
Over 3
2

*Outside pipe diameter shall include insulation and jacketing.

4. Identification markers shall have letters, directional arrows and colors as follows: Plant Water Black Letters on Yellow Field
Industrial Water Black Letters on Yellow Field Potable Water White Letters on Green Field Reclaimed Water Black Letters on Yellow Field Fire Protection Water White Letters on Red Field High Pressure Air White Letters on Blue Field Instrument Air White Letters on Blue Field Sludge Black Letters on Yellow Field Steam Black Letters on Yellow Field Drain Black Letters on Yellow Field Acid Black Letters on Yellow Field
Caustic Solution Black Letters on Yellow Field Polymer Black Letters on Yellow Field Ferric Chloride Black Letters on Yellow Field Sodium Hypochlorite Black Letters on Yellow Field Hydrogen Peroxide Black Letters on Yellow Field Digester Gas Black Letters on Yellow Field Natural Gas Black Letters on Yellow Field
Electrical per Section 16130, Raceway Systems and Pull
Boxes

2.2 IDENTIFICATION OF VALVES AND SHORT PIPE LENGTHS

A. Identifying devices for valves and the sections of pipe that are too short to be identified with lettered labels, and arrows shall be identified with engraved metal tags as specified in the OCSD Tagging Procedure standard and elsewhere in Division 16 and 17.

2.3 IDENTIFICATION OF PIPE 5/8-INCH OR SMALLER

A. Where the outside diameter of pipe or pipe covering is 5/8 inch or smaller, metal tags shall be provided instead of lettering. Tags shall have the specified identifying lettering stamped in the tag and shall be fastened to the pipe with suitable chains. Metal tags and chains shall be stainless steel. Where tags are used, pipe shall be color-coded as specified in Article entitled “Identification Schedule” herein.

2.4 REMNANTS OF ABANDONED PIPE

A. Remnants of buried abandoned pipe that extend into tunnels or are otherwise visible shall be identified at the point of emergence by original service, job number of original installation, and job number of demolition project.

B. The information shall be stenciled on the wall adjacent to the remaining penetration. Lettering shall be black, 1 inch high, and painted on a white background. If no adjacent surface is suitable for the lettering, an engraved metal tag shall be used.

2.5 MISCELLANEOUS

A. Vent lines shall be painted to match the surfaces that they adjoin. B. Hoist hooks and blocks shall be painted yellow with black stripes.
PART 3 - EXECUTION

3.1 GENERAL

A. All labels shall be installed in accordance with the manufacturer's printed instructions, and shall be neat and uniform in appearance. All such tags or labels shall be readily visible from all normal working locations.
3.2 VALVE TAGS

A. Valve tags shall be permanently attached to the valve or structure as specified in the
OCSD Tagging Procedure standard and elsewhere in Division 16 and 17.

B. The wording on the valve tags shall describe the exact function of each valve, e.g., "HWR-BALANCING," "CLS THROTTLING," "RAS-PUMP SHUT-OFF," etc.

3.3 PIPE IDENTIFICATION LOCATION

A. Straight lines of pipe shall be identified at intervals of 20 feet maximum, and at least once in each room unless otherwise directed by the ENGINEER.

B. Piping shall also be identified at a point approximately within 2 feet of all turns, ells, valves, and the upstream side of all distribution fittings or branches and on both sides of each floor, wall or barrier through which the line passes.

3.4 IDENTIFICATION SCHEDULE

A. Application of identifying devices shall conform to the following color codes, or match existing color code as directed by the ENGINEER.

Material in Pipe Color

Potable Water (RP Device) Caribbean Blue Fresh Water (Air Gap) Caribbean Blue Industrial and/or Cooling Water
LPE Purple (Custom Formula) MPE Purple (Custom Formula) HPE Purple (Custom Formula) HPE (continuously chlorinated) Purple (Custom Formula) Fire Water Caribbean Blue
Industrial Water Dark Blue Cooling Water Supply-Plant Effluent Safety Blue Cooling Water Return-Plant Effluent Safety Blue Cooling Water Return-Industrial Water Dark Blue Cooling Water Supply-Industrial Water Dark Blue
Reclaimed Water Purple (Custom Formula) Final Effluent Safety Blue
Irrigation (continuously chlorinated eff.) Purple (Custom Formula)
Chemical Supply Lines (Extremely Dangerous)

Chlorine (gas or liquid) Cool Green Chlorine Solution Cool Green Sodium Hydroxide Cool Green Chlorinator Vent and Detection Lines Cool Green Hydrazine Cool Green Lime Slurry Cool Green Sodium Hypochlorite Cool Green Ferric Chloride Cool Green Ferrous Chloride Cool Green Phosphoric Acid Cool Green Concentrated Sulfuric Acid Cool Green Dilute Sulfuric Acid Cool Green Chemical Draw and Vent Cool Green Dilute Acid Cool Green
Chemical Supply Lines

Polymer-Anionic Cool Green

-Cationic Cool Green

-Nonionic Cool Green

-Dist. Cool Green

-Effluent Cool Green Chemical Draw and Vent Cool Green Sulfite/Bisulfite Scrubbing Liquid Cool Green Stratford Solution (Scrubbing Liquor) Cool Green
Sludge/Ash Transport and Process Lines

Blended Sludge Light Gray Bottom Sludge Light Gray Centrate (from digested sludge dewatering) Light Gray
Centrate (H2 S Scrubbing) Light Gray Circulated Sludge Light Gray Digested Sludge Light Gray Sulfur Slurry (H2 S Scrubber) Light Gray Filtrate Light Gray Raw Sludge Light Gray Screened Digested Sludge Light Gray Activated Sludge Light Gray
Digester Cleanings Light Gray Digested Sludge to Screenings Light Gray Digested Sludge to Blending Tanks Light Gray Digested Sludge Recirculated/Transfer Light Gray Digested Sludge Withdrawal Light Gray Thickened Waste Activated Sludge Light Gray Return Activated Sludge Light Gray Thickener Subnatant Light Gray Thickener Subnatant Overflow Light Gray Cyclone Effluent Light Gray Grit Light Gray Mixed Liquor Light Gray Thickener Pressurized Recycle Light Gray Scum Light Gray Ash (hydraulic) Light Gray Processed Condensate Safety Blue Process Effluent Safety Blue Final Clarifier Influent Safety Blue
Pneumatic Transport Lines

Sludge Derived Fuel Cool Green
Hot Ash Cool Green

Sand Transport Cool Green

Air and Vacuum Supply Lines

Oxygen (gaseous) Cool Green Oxygen (liquid) Cool Green Combustion Air Paper White Compressed Air (non-instrument) Paper White Instrument Air Paper White Process Air Paper White Product Air Paper White Foul Air Paper White Nitrogen (liquid) Cool Green Nitrogen (gaseous) Cool Green Vacuum Paper White Vent Duct Paper White
Boiler Waters

Boiler Feedwater Makeup Caribbean Blue Boiler Feedwater Caribbean Blue Continuous Blow-down Dark Blue Demineralized Water Dark Blue
H. P. Condensate Dark Blue L. P. Condensate Dark Blue M. P. Condensate Dark Blue Intermittent Blow-down Dark Blue Softened Water Dark Blue
Reverse Osmosis Treated Water (permeate) Purple (Custom Formula) Steam
L. P. Steam Safety Red
M. P. Steam Safety Red

H. P. Steam Safety Red

Lube and Hydraulic Oils

Hydraulic Oil Supply Safety Yellow Hydraulic Oil Return Safety Yellow Lube Oil Safety Yellow Drain Oil Safety Yellow Oil Vapor Safety Yellow Grease Safety Yellow Defoamant-Sludge Blending Tanks (Kerosene) Safety Yellow
Fuel Supply

Natural Gas/LNG/Propane Safety Yellow

Digester Gas: LP, MP, and HP Safety Yellow

Diesel Safety Yellow

Lab

Distilled Water Dark Blue

Salt Water Dark Blue

Miscellaneous

Equipment Vent same as equipment

Sample Line same as line or equipment being sampled

Spare Chemical same as chemical

Sanitary Sewer/Storm Drains

Roof Drain Dark Brown or same color as bldg. walls

Plant Drain Dark Brown Storm Drain Dark Brown Sump Pump Discharge Dark Brown Sanitary Sewer Dark Brown
Sanitary Vent Dark Brown Influent Raw Sewage (up to primary tanks) Light Grey Demineralized Waste Dark Brown Reverse Osmosis Reject Dark Brown