Section 15030
PIPING IDENTIFICATION SYSTEMS
PART 1 - GENERAL
1.1 THE REQUIREMENT
A. The CONTRACTOR shall furnish,
paint, mark, and paint/install identification devices for all exposed
piping and piping in accessible chases and areas above ceilings with
panels, and valves using, lettering, flow direction arrows, and
related permanent identification devices, and all appurtenant Work,
in accordance with the requirements of the Contract Documents.
1.2 RELATED WORK SPECIFIED
ELSEWHERE
A. The requirements of the following
sections and divisions apply to the Work of this section. Other
sections and divisions of the Specifications, not referenced below,
shall also apply to the extent required for proper performance of
this Work.
1. Section 09800, Protective Coating
2. Division 11, Equipment, applicable
sections
3. Division 15, Mechanical,
applicable sections
4. Division 16, Electrical,
applicable sections
5. Division 17, Instrumentation and
Control, applicable sections
1.3 REFERENCE SPECIFICATIONS,
CODES AND STANDARDS
A. All Work specified herein shall
conform to or exceed the applicable requirements of the referenced
portions of the following publications to the extent that the
provisions thereof are not in conflict with other provisions of these
Specifications.
B. Comply with the applicable
editions of the following codes, regulations and standards.
1. Codes and Regulations:
C. OCSD – Tagging Procedure
Standard:
2. Industry Standards:
D. ASME A13.1 – Scheme for the
Identification of Piping Systems.
E. Comply with the applicable
reference Specifications as directed in the General
Requirements and Additional General
Requirements.
1.4 CONTRACTOR SUBMITTALS
A. Submittals shall be made in
accordance with the General Requirements, Additional
General Requirements and as specified
herein.
B. The CONTRACTOR shall submit
samples of all types of identification devices to be used in the
Work.
1.5 QUALITY ASSURANCE (NOT USED)
PART 2 - PRODUCTS
2.1 IDENTIFICATION OF PIPING
A. All exposed piping and piping in
accessible chases and areas above ceilings with panels, including
stainless steel, galvanized steel, copper, CPVC, and Fiberglass RTR
piping, shall be completely and totally painted for identification
purposes. Piping shall be identified with lettering or tags
designating the service of each piping system shall have flow
directional arrows. All piping scheduled to be color-coded shall
be completely painted or coated with the colors indicated in the
schedule below.
B. Each pipe identification shall
consist of color-coding in accordance with Article 3.4 entitled
“Identification Schedule”, a painted or adhesive label and a
directional flow arrow. Piping identification shall be located in
accordance with Article entitled “Pipe Identification Location”
herein.
C. For cases where there are
insulated lines wrapped with aluminum sheathing, stainless
steel sheathing, or gray fabric, the background color shall be
applied to a
24-inch length of pipe section and
color band centered within the 24-inch field of background color.
D. Paint Colors: Paint colors shall
conform to the following designations, Or Equal:
Color
Mfg./No.
Paper
White
DuPont 40P-1031
Tnemec F075-WH01A Dunn Edwards
IP630-SY-1
Dark
Brown
DuPont 40P-1039
Tnemec F075-D2526A
Dunn Edwards IP630-SY-25
Safety
Red
DuPont 333-23664
Tnemec F075-S1170A
Dunn Edwards IP630-SY-19
Color
Mfg./No.
Safety
Orange
DuPont 40P-1030
Tnemec F075-S1169A
Dunn Edwards IP630-VD9222
Light
Gray
DuPont 333-23662
Tnemec F075-A2606A
Dunn Edwards IP630-RL7422
Light
Gray
DuPont 333-23662
Tnemec F075-A2606A
Dunn Edwards IP630-RL7422
Safety
Red
DuPont 333-23664
Tnemec F075-S1170A
Dunn Edwards IP630-SY-19
Caribbean
Blue
DuPont 40P-1048
Tnemec F075-B2478A
Dunn Edwards IP630-UD10264
Safety
Blue
DuPont 40P-1048
Tnemec F075-B2477A
Dunn Edwards IP630-VD10265
Spectra Master
(Dark Blue)
DuPont 40P-1496
Tnemec F075-B2476A
Dunn Edwards IP630-SY-23
Custom Formula
(Purple)
DuPont 40P-1628
Tnemec F075-R1217A
Dunn Edwards IP630-SY-13
Cool
Green
DuPont 40P-1008
Tnemec F075-S1168A
Dunn Edwards IP630-UL9585
Color
Mfg./No.
Safety
Yellow
DuPont 333-23663
Tnemec F075-S1167A
Dunn Edwards IP630-UD9223
E. Lettering:
1. Stencils or Markers: Contents
identification labels and directional arrows shall be painted
directly on piping using stencils.
2. Pipe identification markers
shall be vinyl or polyester construction with an adhesive
strip, coiled to wrap completely around the pipe (no straps) and
have subsurface printing. Pipe less than 6 inches shall be have
lettering to meet ASME A13.1 standard and shall be Marking Services
Inc., MS-970 or MS-995; Accuform Subsurface Snaptite; Or Equal.
Pipe 6 inches or larger shall have 2-inch lettering on a 12-inch
field minimum and shall be Marking Services Inc., MS-995; Accuform
Subsurface Snaptite; Or Equal.
3. The size of the letters for
identification labels shall be as follows:
-
Pipe Outside Diameter* (inches)
Letter Size(inches high)
5/8 to 1-1/4
1/2
1-1/2 to 3
1
Over 3
2
*Outside pipe diameter shall include
insulation and jacketing.
4. Identification markers shall have
letters, directional arrows and colors as follows: Plant Water
Black Letters on Yellow Field
Industrial Water
Black Letters on Yellow Field Potable Water
White Letters on Green Field Reclaimed Water
Black Letters on Yellow Field Fire Protection Water
White Letters on Red Field High Pressure Air
White Letters on Blue Field Instrument Air
White Letters on Blue Field Sludge
Black Letters on Yellow Field Steam
Black Letters on Yellow Field Drain
Black Letters on Yellow Field Acid
Black Letters on Yellow Field
Caustic Solution
Black Letters on Yellow Field Polymer
Black Letters on Yellow Field Ferric Chloride
Black Letters on Yellow Field Sodium Hypochlorite
Black Letters on Yellow Field Hydrogen Peroxide
Black Letters on Yellow Field Digester Gas
Black Letters on Yellow Field Natural Gas
Black Letters on Yellow Field
Electrical
per Section 16130, Raceway Systems and Pull
Boxes
2.2 IDENTIFICATION OF VALVES AND
SHORT PIPE LENGTHS
A. Identifying devices for valves
and the sections of pipe that are too short to be identified with
lettered labels, and arrows shall be identified with engraved metal
tags as specified in the OCSD Tagging Procedure standard and
elsewhere in Division 16 and 17.
2.3 IDENTIFICATION OF PIPE
5/8-INCH OR SMALLER
A. Where the outside diameter of
pipe or pipe covering is 5/8 inch or smaller, metal tags shall be
provided instead of lettering. Tags shall have the specified
identifying lettering stamped in the tag and shall be fastened to
the pipe with suitable chains. Metal tags and chains shall be
stainless steel. Where tags are used, pipe shall be color-coded as
specified in Article entitled “Identification Schedule” herein.
2.4 REMNANTS OF ABANDONED PIPE
A. Remnants of buried abandoned pipe
that extend into tunnels or are otherwise visible shall be
identified at the point of emergence by original service, job number
of original installation, and job number of demolition project.
B. The information shall be
stenciled on the wall adjacent to the remaining penetration.
Lettering shall be black, 1 inch high, and painted on a white
background. If no adjacent surface is suitable for the lettering,
an engraved metal tag shall be used.
2.5 MISCELLANEOUS
A. Vent lines shall be painted to
match the surfaces that they adjoin. B. Hoist hooks and blocks
shall be painted yellow with black stripes.
PART 3 - EXECUTION
3.1 GENERAL
A. All labels shall be installed in
accordance with the manufacturer's printed instructions, and shall
be neat and uniform in appearance. All such tags or labels shall be
readily visible from all normal working locations.
3.2 VALVE TAGS
A. Valve tags shall be permanently
attached to the valve or structure as specified in the
OCSD Tagging Procedure standard and
elsewhere in Division 16 and 17.
B. The wording on the valve tags
shall describe the exact function of each valve, e.g.,
"HWR-BALANCING," "CLS THROTTLING," "RAS-PUMP
SHUT-OFF," etc.
3.3 PIPE IDENTIFICATION LOCATION
A. Straight lines of pipe shall be
identified at intervals of 20 feet maximum, and at least once in
each room unless otherwise directed by the ENGINEER.
B. Piping shall also be identified
at a point approximately within 2 feet of all turns, ells, valves,
and the upstream side of all distribution fittings or branches and
on both sides of each floor, wall or barrier through which the line
passes.
3.4 IDENTIFICATION SCHEDULE
A. Application of identifying
devices shall conform to the following color codes, or match
existing color code as directed by the ENGINEER.
Material in Pipe
Color
Potable Water (RP Device)
Caribbean Blue Fresh Water (Air Gap)
Caribbean Blue
Industrial and/or Cooling Water
LPE
Purple (Custom Formula) MPE
Purple (Custom Formula) HPE
Purple (Custom Formula) HPE
(continuously chlorinated) Purple
(Custom Formula) Fire Water
Caribbean Blue
Industrial Water
Dark Blue Cooling Water
Supply-Plant Effluent Safety Blue Cooling
Water Return-Plant Effluent Safety Blue
Cooling Water Return-Industrial Water Dark Blue
Cooling Water Supply-Industrial Water Dark Blue
Reclaimed Water
Purple (Custom Formula) Final Effluent
Safety
Blue
Irrigation (continuously chlorinated
eff.) Purple (Custom Formula)
Chemical Supply Lines (Extremely
Dangerous)
Chlorine (gas or liquid)
Cool Green Chlorine Solution
Cool Green Sodium
Hydroxide Cool
Green Chlorinator Vent and Detection Lines Cool
Green Hydrazine
Cool Green Lime Slurry
Cool Green Sodium Hypochlorite
Cool Green Ferric Chloride
Cool Green
Ferrous Chloride
Cool Green Phosphoric Acid
Cool Green Concentrated Sulfuric Acid
Cool Green Dilute Sulfuric Acid
Cool Green Chemical Draw and Vent
Cool Green Dilute Acid
Cool Green
Chemical Supply Lines
Polymer-Anionic
Cool Green
-Cationic
Cool Green
-Nonionic
Cool Green
-Dist.
Cool Green
-Effluent
Cool Green Chemical Draw and Vent
Cool Green Sulfite/Bisulfite
Scrubbing Liquid Cool Green Stratford
Solution (Scrubbing Liquor) Cool Green
Sludge/Ash Transport and Process Lines
Blended Sludge
Light Gray Bottom Sludge
Light Gray Centrate
(from digested sludge dewatering) Light Gray
Centrate (H2 S Scrubbing)
Light Gray Circulated Sludge
Light Gray Digested Sludge
Light Gray Sulfur
Slurry (H2 S Scrubber) Light Gray
Filtrate
Light Gray Raw Sludge
Light Gray Screened Digested Sludge
Light Gray Activated Sludge
Light Gray
Digester Cleanings
Light Gray Digested Sludge to
Screenings Light Gray Digested Sludge
to Blending Tanks Light Gray Digested Sludge
Recirculated/Transfer Light Gray Digested Sludge
Withdrawal Light Gray Thickened
Waste Activated Sludge Light Gray Return
Activated Sludge Light
Gray Thickener Subnatant
Light Gray Thickener Subnatant Overflow
Light Gray Cyclone Effluent
Light Gray Grit
Light Gray Mixed Liquor
Light Gray
Thickener Pressurized Recycle Light
Gray Scum
Light Gray Ash (hydraulic)
Light Gray Processed Condensate
Safety Blue Process Effluent
Safety Blue Final
Clarifier Influent
Safety Blue
Pneumatic Transport Lines
Sludge Derived Fuel
Cool Green
Hot Ash
Cool Green
Sand Transport
Cool Green
Air and Vacuum Supply Lines
Oxygen (gaseous)
Cool Green Oxygen (liquid)
Cool Green Combustion Air
Paper White
Compressed Air (non-instrument) Paper
White Instrument Air
Paper White Process Air
Paper White Product Air
Paper White Foul Air
Paper White Nitrogen (liquid)
Cool Green Nitrogen (gaseous)
Cool Green Vacuum
Paper White Vent Duct
Paper
White
Boiler Waters
Boiler Feedwater Makeup
Caribbean Blue Boiler Feedwater
Caribbean Blue Continuous
Blow-down Dark Blue
Demineralized Water
Dark Blue
H. P. Condensate
Dark Blue L. P. Condensate
Dark Blue M. P. Condensate
Dark Blue
Intermittent Blow-down
Dark Blue Softened Water
Dark Blue
Reverse Osmosis Treated Water
(permeate) Purple (Custom Formula) Steam
L. P. Steam
Safety Red
M. P. Steam
Safety Red
H. P. Steam
Safety Red
Lube and Hydraulic Oils
Hydraulic Oil Supply
Safety Yellow Hydraulic Oil Return
Safety Yellow Lube Oil
Safety Yellow Drain Oil
Safety Yellow Oil Vapor
Safety Yellow Grease
Safety Yellow Defoamant-Sludge Blending Tanks (Kerosene)
Safety Yellow
Fuel Supply
Natural Gas/LNG/Propane
Safety Yellow
Digester Gas: LP, MP, and HP
Safety Yellow
Diesel
Safety Yellow
Lab
Distilled Water
Dark Blue
Salt Water
Dark Blue
Miscellaneous
Equipment Vent
same as equipment
Sample Line
same as line or equipment being
sampled
Spare Chemical
same as chemical
Sanitary Sewer/Storm Drains
Roof Drain
Dark Brown or same color as bldg.
walls
Plant Drain
Dark Brown Storm Drain
Dark Brown Sump
Pump Discharge Dark Brown
Sanitary Sewer
Dark Brown
Sanitary Vent
Dark Brown Influent Raw Sewage (up
to primary tanks) Light Grey Demineralized Waste
Dark Brown Reverse Osmosis
Reject Dark Brown