Section 15330
FIRE PROTECTION SPRINKLER SYSTEM
PART 1 - GENERAL
1.1 THE REQUIREMENT
A. The CONTRACTOR shall furnish all
tools, equipment, materials, and supplies and shall perform all labor
required to complete the Work as indicated on the Drawings and
specified herein.
B. The Drawings indicate the extent
and general arrangement of the systems. If any departure from the
Drawings is deemed necessary by the CONTRACTOR, details of such
departure and the reason therefore shall be submitted to the ENGINEER
for review. No such departure shall be made without the prior
written concurrence of the ENGINEER.
C. This section covers the design,
furnishing, and installation of an automatic wet pipe fire protection
system, including all associated piping, valves, fittings, controls,
accessories, and appurtenances necessary for proper operation of the
system.
1.2 RELATED WORK SPECIFIED
ELSEWHERE
A. The requirements of the following
sections and divisions apply to the Work of this section. Other
sections and divisions of the Specifications, not referenced below,
shall also apply to the extent required for proper performance of
this Work.
1. Section 01332, Seismic Design Data
2. Section 02200, Earthwork
3. Section 02666, Water Pipeline
Testing and Disinfection
4. Section 13850, Fire Alarm System
5. Section 15000, Piping, General
6. Section 15005, Ductile Iron Pipe
7. Section 15010, Mill Piping –
Exposed and Buried
8. Section 15020, Pipe Supports
9. Section 15030, Piping
Identification Systems
10. Section 17034, Gauges
1.3 REFERENCE SPECIFICATIONS,
CODES, AND STANDARDS
A. All Work specified herein shall
conform to or exceed the applicable requirements of the referenced
portions of the following publications to the extent that the
provisions thereof are not in conflict with other provisions of these
Specifications.
B. Comply with the applicable
editions of the following codes, regulations and standards.
1. Codes and Regulations:
CCR
California Code of Regulations, Title 24, Part 2, California
Building Code (CBC)
CCR
California Code of Regulations, Title 24, Part 3, California
Electrical Code
NFPA 13
Standard for the Installation of Sprinkler
Systems
NFPA 70
National Electrical Code (NEC)
2. Other Standards:
FM
FM Approvals (formerly, Factory Mutual
Research Corporation)
UL
Underwriters Laboratories
C. Comply with the applicable
reference Specifications as directed in the General
Requirements and Additional General
Requirements.
1.4 CONTRACTOR SUBMITTALS
A. Submittals shall be made in
accordance with the General Requirements, Additional
General Requirements and as specified
herein.
B. Provide the certifications and
other submittal documentation that confirm compliance with Section
01332, Seismic Design Data, this Specification and Paragraph
entitled “Seismic Requirements” of this Specification.
C. Shop drawings and other submittals
shall include all information required to indicate compliance of
system with design criteria and other Contract requirements:
1. Coordination with structural
elements, lighting fixtures, HVAC outlets, ductwork
2. Underground plan and riser plan.
3. Submit dated, certified reports
of the following tests:
a. Flow test.
b. Pressure Tests: Static and
residual.
4. Engineering Calculations.
5. Product data for the following:
a. Indicator valves. b. Other
valves.
c. Fire department connection. d.
Gauges.
e. Pipe and fittings. f. Hangers.
g. Alarm and supervisory monitoring
devices. h. Alarm bell.
i. Sprinkler heads.
6. Miscellaneous Data:
a. Concise instructions for
emergency shutdown of each section of system and for entire system.
b. Valve chart locating and
numbering all control valves and visually identifying area (section)
controlled by each. Use color to permit rapid emergency
comprehension.
c. Head removal and replacement
instructions.
d. Manufacturer's data for each
piece of equipment furnished.
1.5 QUALITY ASSURANCE A.
General:
1. Conduct tests as recommended in
NFPA 13.
2. Follow code-required observation
during testing.
3. Hydrostatic Tests:
a. Test system or parts of
system at a minimum 200 pounds per inch hydrostatic pressure
or system pressure plus 50 pounds per inch, whichever is higher for
a minimum of two (2) hours with no change in pressure indicated.
b. Repair leaks.
c. Retest until all criteria are
met.
4. Acceptance Tests:
a. Conduct code-required flow tests
of completed systems. b. Leave system in operating condition.
B. CONTRACTOR Qualifications:
1. Comply with the requirements
for the certifications, licenses, training, skills, experience,
and other qualifications specified in Paragraph entitled “Seismic
Requirements” of Article entitled “Site Conditions” of this
Specification.
1.6 SITE CONDITIONS
A. Seismic Requirements:
1. Equipment and Appurtenances:
a. The equipment and appurtenances
to be furnished under this Contract shall comply with the seismic
requirements of the applicable California Building Code and the
seismic provisions of the General Requirements, this Specification
and Section 01332, Seismic Design Data; or, to the extent that such
standards are not articulated or clear in the applicable
California Building Code and the seismic provisions of the
General Requirements, this Specification and Section
01332, Seismic Design Data, as
determined by the ENGINEER, then the equipment, appurtenances
shall be as outlined in Chapter 16 of the 200
Building Code, for Occupancy Category
I, Essential Services, in Seismic Zone
4; or equivalent, as established in
the sole discretion of the ENGINEER, documented in writing.
b. CONTRACTOR shall submit the
related seismic calculations, test reports, or extrapolated test
data to demonstrate compliance with the above for ENGINEER’s
acceptance in accordance with the General Requirements,
Section 01332, Seismic Design Data, and as specified in this
Specification.
c. Seismic calculations, test
reports, and/or test data reports shall be certified by a
Professional Engineer registered in the State of California.
d. CONTRACTOR shall submit
manufacturer’s certification that all equipment and auxiliaries
are capable of operating and performing their intended function
before, during, and after the design seismic event without
structural failure or deformation, malfunction, interference, or
abnormal rubbing movement of components.
e. In case of a conflict between
this Specification and Section 01332, Seismic
Design Data, the more stringent
requirements shall govern.
2. Installation:
a. The installation of the equipment
and appurtenances furnished under this Contract shall comply with
Section 01332, Seismic Design Data, and this Specification.
b. In case of a conflict between
this Specification and Section 01332, Seismic
Design Data, the more stringent
requirements shall govern.
1.7 DESIGN CRITERIA
A. Governing Standards and Codes:
All Work covered by this section shall be performed in
accordance with all the applicable federal, state and local codes,
laws, and regulations, including, but not limited to, those
indicated in this Specification. In case of conflict between these
Specifications and any code, law, or regulation, the one that is the
most restrictive shall govern.
1. Local authorities:
a. City of Fountain Valley, CA, Fire
Department
B. Design of Sprinkler Systems: NFPA
13 requirements specified herein.
C. Water Distribution: Distribution
shall be uniform throughout the area in which the sprinkler heads
will open. Variation in discharge from individual heads
in the hydraulically most remote area shall be between 100 percent
and 200 percent of the specified density.
D. Density of Application of Water:
Size pipe to provide the specified density when the system is
discharging the specified total maximum required flow.
E. Sprinkler Discharge Area: Area
shall be the hydraulically most remote 3,000-square- foot area as
defined in NFPA 13.
F. Outside Hose Allowances:
Hydraulic calculations shall include an allowance for outside hose
streams per NFPA 13.
G. Friction Losses: Calculate losses
in piping in accordance with the Hazen-Williams formula with 'C'
value of 120 for steel piping, 150 for copper tubing, and 140 for
cement- lined ductile-iron piping.
H. Location of Sprinkler Heads: Per
NFPA 13.
1.8 VALVE CHARTS AND INSTRUCTIONS
A. Provide framed, glazed copies of
valve chart and emergency shutdown instructions. Mount to wall in
acceptable location.
PART 2 - PRODUCTS
2.1 MATERIALS
A. Pipe and Fittings:
1. Fire Service Main – Exterior (5
feet outside building):
a. Pipe and Fittings: Mechanical
joint, cement-lined ductile iron, as specified under Section 15005,
Ductile Iron Pipe.
b. Exterior Piping: Extend
into building minimum of 18 inches before connecting to
interior piping.
2. Fire Service Main – Interior
Piping from Exterior Service up to Fire Sprinkler
Alarm Check Valve:
a. Pipe: Schedule 40 galvanized
steel.
b. Fittings: Galvanized 150-pound
malleable iron, screwed or Victaulic full-flow galvanized fittings
with Style 77 couplings.
3. Drain Piping:
a. Pipe: Schedule 40 galvanized
steel.
b. Fittings: Galvanized, malleable
iron, screwed.
4. Fire Department Connection:
a. Pipe: Schedule 40 galvanized
steel.
b. Fittings: Galvanized, malleable
iron, screwed.
5. Reducing Fittings:
a. One-piece pipe size reducing
fittings. Same specifications as other fittings for type of pipe.
b. Bushing reductions not
acceptable.
B. Pipe Supports: Provide pipe
support and bracing to comply with Section 15020, Pipe
Supports, NFPA 13, and California
Building Code regarding seismic restraint. C. Valves:
1. Manufacturer: Stockham,
Viking, Grinnell, Or Equal. Manufacturer's figure numbers
specified are for type, quality, and features desired. All valves
shall be UL- listed for fire protection service and Factory
Mutual-approved.
2. Control Valves: Outside screw
and yoke gate valves or butterfly valves, locked open, with
breakable shackle lock.
3. Drain Valves:
a. Angle globe, Stockham No. B-222,
Or Equal from Viking, Grinnell. b. Straight, globe, Stockham No.
B-22, Or Equal from Viking, Grinnell.
4. Check Valves: UL-listed,
swing check installed horizontally, Stockham
No. G-940, Or Equal from Viking,
Grinnell.
5. Indicator Valves: UL-listed, as
manufactured by Mueller, Grinnell, Or Equal, locked open, with
breakable shackle lock.
D. Fire Department Connection:
Potter-Roemer, Croker Or Equal, all bronze, Siamese, wall mount or
freestanding as indicated. 4-inch F.I.P.T. outlet, two 2-1/2-inch
spring back check valved inlets, drain cock, caps and chains,
threads per fire department requirements. Provide cast sign
plate reading "AUTOSPKR." All parts, including
exposed freestanding barrel, shall be polished chrome plated unless
noted otherwise.
E. Alarm Check Valve: UL-listed,
installed on riser, suitable for variable pressure, complete with
retard chamber and approved pressure switches for alarm bell and for
electrical supervisory system.
F. Alarm Bell: UL-listed, approved
10-inch electric bell, complete with suitable identification sign.
Provide for each riser.
G. Waterflow Indicator Switches:
1. Paddle type, inserted into
horizontal piping adjacent each section control valve. Paddle to
actuate a pneumatic time-delay mechanism between the paddle stem and
the microswitch to operate and either open or close an electrical
circuit. Time delay to be adjustable from 0 to 90 seconds.
2. Microswitches to be rated at 7.5
amperes, 120 volts, and wired to either open or closed-circuit
operation.
3. Paddle to be constructed of
corrosion-resistant Monel "K" metal. The body to be
constructed of cast metal with metal cover.
H. Valve Supervisory Switches:
1. Provide tamper switches on all
control valves with alarm signal to register on sprinkler alarm
panel.
2. Tamper switches to be
manufactured by Potter, Notifier, Or Equal. I. Sprinkler Heads:
1. Type: Miniature bulb type with
Teflon spring type coated water seal, Viking
Model M, or exposed eutectic solder
link, Viking Model H, Or Equal from Reliable.
a. All heads shall be corrosion
proof.
2. Manufacturers: Viking, Reliable,
Or Equal.
3. Configurations:
a. "Flush": Small
pendant head partially concealed within the ceiling leaving only the
link exposed.
b. "Recessed": Small
frame pendant head recessed into canopy that is recessed into
ceiling.
c. "Pendant": Small frame
exposed head with exposed telescoping canopy that installs tight
against ceilings. Provide protective devices when ceilings are less
than 8 feet in height.
d. "Sidewall": Special
frame head, with adjustable canopy, for installation on vertical or
near-vertical surface.
e. "Upright": Standard
frame head for mounting in upright position above piping system.
4. Finishes: Unless otherwise
indicated, flush, recessed pendant and sidewall heads and canopies,
polished chrome plate or white; upright head, rough brass.
5. Locations: Unless otherwise
indicated:
a. Flush: Finished space except
service areas. Includes corridors and toilets. b. Pendant and
Recessed: Finished service areas.
c. Sidewall: Where required by NFPA
13 or by code. d. Upright: Spaces without ceilings.
e. High-Temperature Fusible Links:
(1) Heads within 12 inches of
surface-mounted fluorescent lighting. (2) Where otherwise
indicated.
J. Sleeves: Shall comply with
Section 15000, Piping, General. Provide sleeves for passage of
pipe through floors, walls, and partitions. Provide appropriate
type for purpose. Seal in an acceptable manner against water,
fire, or sound, depending on type of construction penetrated.
K. Escutcheons: Provide at passage
of pipe through walls, partitions, and ceilings. Prime coated steel,
split ring of set screw type, at concealed or service areas.
Polished chrome cast brass split ring or set screw type when exposed
to view.
L. Pressure Gauges:
1. Provide per NFPA 13.
2. Comply with Section 17034,
Gauges.
3. Brass case, 4-1/2-inch dial.
4. To register twice the working
pressure of the system.
M. Identification: Identification
of valves and piping shall be in accordance with
Section 15030, Piping Identification
Systems. N. System Design Sign:
1. Locate adjacent to alarm check
valves.
2. Identify system as hydraulically
designed.
3. State Basis of Design: Discharge
density over area of discharge. O. Valve Locks:
1. Provide all-brass padlock(s) with
break-away shackle, multiple locks keyed alike, master keyed to
building key system, with chains, for each lockable control valve.
2. Provide to OCSD two keys durably
tagged and marked for identification. P. Alarm Panel: See Section
13850, Fire Alarm System.
2.2 PREPARATION, LAYOUT, AND
DETAILING A. Underground Piping:
1. Prior to trenching, obtain
ENGINEER's acceptance of dimensioned location of riser(s), indicator
valve(s), and fire department connection(s).
2. Provide thrust blocks and
anchorage at elbows, bends, and tees per NFPA 13. B. Risers:
Arrange riser components as recommended in NFPA 13.
C. Overhead Piping:
Provide/coordinate clearance for:
1. Installation of HVAC ductwork,
heaters, fan coils, and other installations.
2. Lighting fixtures.
3. Plumbing mains. D. Pipe Support:
1. Provide hangers, supports, and
bracing as recommended in NFPA 13. All hangers, supports,
bracing, and anchors shall be galvanized steel.
2. Comply with code requirements for
seismic bracing.
E. Drains:
1. Unless otherwise indicated,
system and test drains shall discharge into receptors connected to a
sewer or storm drain system.
2. Do not drain onto unpaved
areas or areas that do not drain. Coordinate installation
of receptors with plumbing installer.
F. Miscellaneous Fittings:
1. Flow Indicator Switches: Locate
in horizontal piping adjacent to section control valves and 18
inches clear of nearest fitting.
2. Alarm Bell(s):
a. Locate 11 feet above grade.
b. Obtain ENGINEER's acceptance of
dimensioned location.
3. Valve Tamper Switches:
a. On OS&Y valves, locate switch
on valve stem.
b. On butterfly valves, locate
switch on gear operator.
G. Concealment: Except where
specifically indicated otherwise, conceal or prepare for concealment
piping, fittings, etc., in those spaces where wall and/or ceiling
surfaces are indicated or implied to receive present or future
finish materials.
H. Heads:
1. Spacing/Coverage: As required by
system design.
2. Lay out with respect to:
a. Lighting fixtures.
b. HVAC diffusers/returns.
c. Suspended ceiling grid/panel
pattern. d. Center of room/space.
e. Longitudinal axis of room/space.
3. Align heads in row(s) within +1/2
inch of straight line.
4. Align heads laterally in adjacent
rows to same tolerance of alignment.
5. Prevent interference of heads
with door swing.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Acceptances: Prior to
installation, obtain following acceptances of proposed system design
and equipment:
1. City of Fountain Valley, CA, Fire
Department
B. Trench and Backfill:
1. Perform as specified in Section
02200, Earthwork.
2. Perform all trenching under the
observation of the ENGINEER, as specified in Section 02200,
Earthwork. Compaction tests will be performed per direction of the
ENGINEER. No backfilling will be allowed until test results of
pipe testing and compaction tests have been accepted by the
ENGINEER.
C. Underground piping shall be
installed according to Section 15005, Ductile Iron Pipe, and as
follows:
1. Install thrust blocks.
2. Bed pipe solidly on grade.
3. Anchor to thrust blocks.
4. Extend pipe 6 inches minimum above
floor at risers.
5. Install post indicator valves and
fire department connections.
6. Partial backfill to further
anchor pipe shall be installed prior to testing and flushing.
Keep joints exposed to check leaks.
7. Seal openings and perform
hydrostatic pressure test under required observation.
8. Flush underground system prior to
installing risers.
D. Risers: Assemble components as
recommended in NFPA 13.
E. Pipe Support: Install in
accordance with Section 15020, Pipe Supports, and as recommended in
NFPA 13.
F. Overhead Piping Systems shall be
assembled according to Section 15010, Mill
Piping - Exposed and Buried, and as
described below:
1. Slope:
a. Except for pendant drops, provide
for drainage of entire system. b. Prevent traps.
c. Prevent air pockets.
2. Flushing: Prior to installation
of heads, seal openings and flush entire system to remove foreign
matter.
3. Hydrostatic Test: All
hydrostatic testing of piping shall be performed in the presence of
the ENGINEER and be subject to ENGINEER’s acceptance. In addition
to any testing and acceptance/approval required by these
Specifications, the CONTRACTOR is responsible for providing testing
as required and obtaining approval from the following local
authorities:
a. City of Fountain Valley, CA, Fire
Department
G. Disinfection:
1. Disinfecting Solution: Water
solution containing chlorine at the minimum concentration of 50
parts per million.
2. Fill entire fire protection system
with disinfecting solution.
3. Allow to stand 6 hours minimum.
4. Flush system until chlorine
content is at or below content of local water supply. H. Heads:
1. Install swing joints required for
exact alignment of heads.
2. Nipple length shall permit head to
draw canopy tight against mounting surface without deforming canopy.
3. Canopies shall telescope to or be
adjusted to midpoint in the adjustment range.
4. Replace nipples of incorrect
length.
5. Heads shall draw snug against
canopies.
I. Identification: Install signs
and tags in required locations prior to code-required test inspection
of the system.
No comments:
Post a Comment