Section 15954
HVAC TESTING, ADJUSTING AND BALANCING
PART 1 - GENERAL
1.1 THE REQUIREMENT A. General:
1. The CONTRACTOR shall provide all
tools, supplies, materials, equipment, and all labor necessary for
testing, adjusting and balancing of the heating, ventilation and air
conditioning systems, in accordance with the requirements of the
Contract Documents.
1.2 RELATED WORK SPECIFIED
ELSEWHERE
A. Submittals shall be made in
accordance with the General Requirements, Additional
General Requirements and as specified
herein.
B. Materials and equipment furnished
and installed under other Specification sections in the Contract
Documents.
1. Division 01, Additional General
Requirements
2. Division 15, Mechanical
3. Division 16, Electrical
4. Division 17, Instrumentation and
Control
1.3 REFERENCE SPECIFICATIONS,
CODES AND STANDARDS
A. All Work specified herein shall
conform to or exceed the applicable requirements of the referenced
portions of the following publications to the extent that the
provisions thereof are not in conflict with other provisions of
these Specifications.
B. Comply with the latest editions
of the following:
1. Codes and Regulations:
NEC
National Electrical Code (National Fire
Protection Association, NFPA 70)
CCR
California Code of Regulations, Title 8, Industrial
Relations, Subchapter 5, Electrical Safety Orders
2. Other Standards:
AABC
Associated Air Balance Council - National Standards
for Field Measurements and Instrumentation, Total System Balance,
and Air Distribution-Hydronic Systems
NEBB
National Environmental Balancing Bureau - Procedural
Standards for Testing, Adjusting and Balancing of Environmental
Systems
SMACNA
Sheet Metal and Air Conditioning Contractors' National
Association, Inc. - Heating, Ventilating and Air Conditioning
Systems - Testing, Adjusting and Balancing
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning
Engineers – Standard 111, Practices for Measurement, Testing,
Adjusting, Balancing of Building Heating, Ventilation, Air-
conditioning, and Refrigeration Systems
1.4 TESTING, ADJUSTING, AND
BALANCING WORK REQUIREMENTS
A. Procure the services of an
independent air balance and testing firm belonging to and holding a
current certification from the Associated Air Balance Council or the
National Environmental Balancing Bureau. The firm shall perform air
and hydronic balancing, testing, and adjustment of building and
process air conditioning, heating, and ventilating air systems.
B. Perform balancing of new air and
hydronic systems installed as part of this contract and existing air
and hydronic systems affected by the installation of new equipment.
C. Perform testing of heating,
ventilating and air conditioning equipment, balancing of
distribution systems, and adjusting of air terminal units and
ductwork accessories to ensure compliance with the Contract
Documents. Perform tests for the following:
1. Air conditioning units.
2. Air handling unit.
3. Fans.
4. Odor control fans.
5. Condensers.
6. Air terminal units.
7. Ductwork accessories.
8. Ducting.
9. HVAC controls; Examples include
limit control, linear control, PID control, feed- forward control,
fuzzy logic, and advanced or non-linear controls. Limit control
establishes set points or limits that, when reached, cause the HVAC
controller to send a signal to stop or start a process variable.
Linear control matches a variable input signal with a
correspondingly variable control signal. Proportional, integral, and
derivative (PID) control requires real-time system feedback.
10. Other HVAC equipment as may
be specified elsewhere in the Contract
Documents.
D. Test hydronic systems and adjust
and record liquid flow at each piece of equipment to ensure
compliance with the Contract Documents. Perform test for the
following:
1. Circulating pumps.
2. Circuit setting valves.
3. 3-way mixing valves.
4. Chilled water coils.
5. Other hydronic system
components as specified elsewhere in the Contract
Documents.
E. Verify the size of the circuit
breaker, overload relay heaters, and contactor for each fan motor
and the motor current during startup and balancing when the maximum
current draw of the fan’s motor can be determined.
F. Test each mode of operation
of thermostats, electronic controllers, pneumatic, electric, or
electronic heating, ventilating, and air conditioning instruments to
ensure operation as specified.
G. Test and adjust room distribution
patterns at air outlets.
H. Provide instruments required for
testing, adjusting, balancing operations, retain possession of
instruments, and remove instruments from site at completion of
testing. Make the instruments available to the ENGINEER to
facilitate spot checks during testing.
I. Provide test holes for pressure
and pitot flow measurements and provide plugs for all test holes
after testing.
J. Test the interface signals to the
OCSD SCADA System. This includes signals such as HVAC Unit “ON”
and Room Air Temperature (High).
K. Test and or verify any interfaces
to/from the Fire Protection System.
1.5 SUBMITTALS
A. Submit the following to the
ENGINEER:
1. Resumes of proposed
companies, supervisor and personnel indicating
certifications, training, and qualifications.
B. The reports shall be as specified
below and shall be on SMACNA, NEBB or AABC forms that indicate
information addressing each of the testing methods, readings and
adjustments.
C. Interim Reports: At least 30 days
prior to starting fieldwork, submit the following:
1. Deficiency Report: Following
examination of installed systems and prior to balancing, submit a
report indicating system deficiencies that would prevent proper
testing, adjusting, and balancing of systems and equipment to meet
specified performance.
2. Schematics: Develop heating,
ventilating and air conditioning system schematic similar to Figure
6.1 in SMACNA “Testing, Adjusting and Balancing”. In addition,
the CONTRACTOR shall also develop schematics of the FRP and metal
ducting systems including odor control, general ventilation, HVAC
units, and associated ducting. The schematics shall show the
condensate drains and traps, their locations in the ducting systems,
and their routings. Include hard copy and electronic file of the
schematics using latest version of AutoCAD.
3. Complete list of instruments
proposed to be used and organized in appropriate categories, with
data sheets for each indicating the following:
a. Manufacturer and model number.
b. Description and use when needed to
further identify instrument. c. Size or capacity range.
d. Latest calibration date.
D. Final Testing Report: At least 15
days prior to CONTRACTOR's request for final inspection, submit three
copies of final reports on applicable reporting forms. Include the
following information:
1. Set of report(s) submit 3 copies
of the completed testing report including the following:
a. The design flow values and
installed equipment pressure drops. b. Required cubic feet per
minute for air terminals.
c. Testing, adjusting, and balancing
report, including drawings indicating air outlets, thermostats, and
equipment identified to correspond with the associated data sheets.
2. Identify instruments that were
used and last date of calibration of each.
3. Procedures followed to perform
testing, adjusting and balancing.
4. Identification and succinct
description of systems included in the report.
5. Initial balance test results made
with all dampers and air control devices in full open positions.
6. Description of final locations
and sizes, including opening area and dimensioned configuration of
orifices and other restrictions used to achieve final balanced
flows.
7. Description of final location and
opening positions of dampers, registers, louvers, and valves.
8. Schematics of systems included in
the report; use schematics as part of the testing, adjusting and
balancing report to summarize design and final balanced flows.
9. Testing, adjusting and balancing
report forms.
10. Final field results established
for system balancing including air flow, fan speeds, and fan static
pressures at the fan inlet and outlet.
11. Include appendices for the
following:
a. Raw field data taken during
testing.
b. Sample calculation sheet for each
type of calculation made to convert raw field data to final results.
c. Initial air balance results with
dampers and registers in full-open position; include air flow at all
inlets and outlets, initial fan speed, and fan suction and discharge
pressures.
12. Proposed schedule for testing and
balancing.
1.6 QUALITY ASSURANCE
A. Test, balance, and adjust
environmental systems in accordance with either:
1. AABC: National Standards for
Field Measurements and Instrumentation, Total
Systems Balance, and Air
Distribution-Hydronics System.
2. NEBB: Procedural Standards
for Testing, Adjusting and Balancing of
Environmental Systems.
B. Perform services under direction
of AABC-certified or NEBB-certified supervisor.
C. Calibrate and maintain instruments
in accordance with the requirements of AABC or
NEBB standards. Make calibration
histories of the instruments available for examination.
D. Make measurements in accordance
with accuracy requirements of AABC or NEBB
standards.
1.7 SITE CONDITIONS
A. Prior to start of testing,
adjusting and balancing, verify that the following is true:
1. Systems installation is complete
and in full operation.
2. Outside conditions are within
reasonable range relative to design conditions.
3. Lighting fixtures are energized.
4. All equipment such as
computers, laboratory equipment and electronic equipment are
in full operation.
5. Requirements for preparation
for testing and balancing have been met for elements of each
system that requires testing.
6. All Fire Protection System
Equipment has been bypassed as directed by OCSD. B. Prior to start
of testing, adjusting and balancing, perform the following:
1. Air Handling Systems: Adjust to
within plus 10 percent of outlet total, plus allowable leakage rate.
2. Air Outlets and Inlets: Adjust
total to within plus or minus 10 percent of design for the space.
3. Hydronic Systems: Adjust to
within plus or minus 10 percent of design flow.
4. Hydronic Terminal Devices:
Adjust to within plus or minus 10 percent of design flow.
1.8 SPECIAL WARRANTY
A. Provide warranty for a period of
90 days following submission of completed final testing report,
during which time OCSD may request a recheck of up to 10 percent of
total number of terminals, or/and resetting of any outlet, coil, or
device listed in the test report.
B. Warranty shall meet the
requirements of the following program(s):
1. TABB – International Quality
Assurance Program.
2. AABC – National Project
Performance Guarantee.
3. NEBB – Conformance
Certification.
PART 2 - PRODUCTS (NOT USED) PART 3 -
EXECUTION
3.1 FIELD QUALITY CONTROL
A. Testing, Adjusting and Balancing
Acceptance Criteria: Consider testing, adjusting, and balancing
procedures successful and complete when heating, ventilating and air
conditioning systems and components are functioning properly and
system air and water flows are within specified tolerances of design
flows.
3.2 TESTING, ADJUSTING AND
BALANCING
A. Test, adjust and balance separate
complete heating, ventilating and air conditioning systems.
B. Testing, adjusting and balancing
shall include the related existing heating, ventilating and air
conditioning components.
C. Perform testing, adjusting and
balancing cycles until air flows meet acceptance criteria
specified above.
D. Ascertain air flow balance between
overall requirements and flow in individual supply and exhaust
grills.
E. Initial Testing, Adjusting and
Balancing: Perform first test on each system with dampers, grills,
orifices, and other variable air flow devices in their full-open
position; measure and report initial air flows, fan speed, and fan
static pressures at fan inlet and outlet.
1. Adjust total system flow downward
or upward by adjusting fan speed until one inlet or outlet is at
indicated flow and all other flows exceed indicated flows.
2. Adjust fan speed by changing fan
drives or sheaves as necessary.
F. Subsequent Testing, Adjusting and
Balancing: Perform adjustments in subsequent testing, adjusting and
balancing by adjusting dampers, louvers, or size of orifices or
plates.
1. Measure and record air volume
discharged at each inlet and outlet and adjust air inlets and
outlets to design air volumes within 5 percent to 10 percent over
design rates.
2. Adjust fan speeds and motor
drives within drive limitations, for required air volume.
3. Measure air velocity and static
pressures and adjust air supply and exhaust fan units to deliver at
least 105 percent to 110 percent of the design air volume.
4. Measure and record static air
pressure conditions on fans, including filter and coil pressure
drops, and total pressure across the fan.
5. Evaluate building and room
pressure conditions to determine adequate supply and return air
conditions.
6. Evaluate space and zone
temperature of conditions to determine adequate performance of
the systems to maintain temperatures without draft.
7. Permanently mark final balance
positions of balancing dampers.
G. Accurately record the required
data on Associated Air Balance Council or National
Environmental Balancing Bureau test
and balance report forms.
H. Measure voltage and amperage draw
of fan and pump motors for final balance.
I. Following completion of
balancing procedures for air systems, test, adjust, and balance
hydronic systems:
1. Measure flow and adjust circuit
setter valves so pumps deliver at least 100 percent of the design
water flow.
2. Measure and adjust water flow at
coils for design conditions, within 10percent. Check conditions at
cooling and heating coils for required performance at design
conditions.
3. Lock balance valves in the
adjusted position and permanently mark the design set point. Record
valve settings in the design report.
J. Test primary source equipment in
accordance with AABC or NEBB procedures:
1. Primary source equipment shall
include the items listed in Part 1 not previously tested as part of
this testing, adjusting and balancing work.
2. Complete appropriate AABC or NEBB
equipment test forms for each piece of equipment.
3. Calculate cooling and heating
capacities to show conformance with specified capacities.
4. Adjust equipment as needed to
deliver specified cooling and heating loads.
5. Record final equipment performing
characteristics and adjustment settings in the final design report.
3.3 ADJUSTING
A. Recorded data shall represent
actual measured or observed conditions.
B. Permanently mark setting of
valves, dampers, and other adjustment devices allowing for settings
to be restored. Set and lock memory stops.
C. Leave systems in proper working;
replace belt guards, close access doors, close doors to electrical
switch boxes, and restore thermostats to specified settings.
D. Return Fire Protection System
Equipment to back to the normal operating condition.
3.4 TRAINING
A. Comply with the requirements of
Specification section 01820, Training of OCSD
personnel.
No comments:
Post a Comment