Thursday, July 24, 2014

Section 13850 FIRE ALARM SYSTEM

Section 13850

FIRE ALARM SYSTEM


PART 1 - GENERAL

1.1 SUMMARY

A. Provide a complete, electrically supervised, addressable intelligent, manual and automatic fire alarm system. Provide a system that will be in full compliance with the required and advisory portions of NFPA 72, National Fire Alarm Code, the UL listings or FM approvals, the ADA, and the recommendations of the equipment manufacturer.

1. System includes but is not limited to the Fire Alarm Control Panel (FACP), FACP interface boards, FACP power supplies, FACP batteries, remote annunciators, smoke detectors, duct smoke detectors, manual pull stations, audible and visual alarms, wiring, conduits, signs, and appurtenances, and interface with the existing Main Fire Alarm Control Panel (MFACP), located in the existing Blower Building.

2. Provide addressable duct smoke detectors suitable for the full range of air velocity conditions in the air handling systems in which they are installed. Provide addressable duct smoke detectors, with auxiliary contacts, for all combination fire/smoke dampers in walls and floor slabs. See fire protection and mechanical floor plan drawings for locations of combination fire/smoke dampers.

3. FACP shall monitor all fire alarm system functions through addressable interface devices.

4. The FACP shall provide software activated smoke detector alarm verification capability on a detector-by-detector basis

1.2 THE REQUIREMENT

A. The CONTRACTOR shall furnish all tools, equipment, material, and supplies and perform all labor required to install a complete and operable fire alarm system as indicated on the Drawings and specified herein.

B. CONTRACTOR submittals for the fire alarm system as specified herein shall be subject to review and acceptance by the Fountain Valley Fire Department. Any required revisions, to the proposed fire alarm system to obtain acceptance, shall be incorporated by the CONTRACTOR at no additional cost to OCSD.

C. The Contract Drawings are diagrammatic in nature, subject to change, based on final certified prints of the equipment and instruments to be purchased and based on actual field condition. Fire alarm devices are located on the Drawings. CONTRACTOR shall design and install cable/conduit system.

1.3 RELATED WORK SPECIFIED ELSEWHERE

A. The requirements of the following sections and divisions apply to the Work of this section. Other sections and divisions of the Specifications, not referenced below, shall also apply to the extent required for proper performance of this Work.

1. Division 11, Equipment, applicable sections

2. Division 16, Electrical, applicable sections

3. Division 17, Instrumentation and Control, applicable sections
1.4 REFERENCE SPECIFICATIONS, CODES, AND STANDARDS

A. All Work specified herein shall conform to or exceed the applicable requirements of the referenced portions of the following publications to the extent that the provisions thereof are not in conflict with other provisions of these Specifications.

B. Comply with the applicable editions of the following codes, regulations and standards.

1.
Codes and Regulations:

ADAAG


Americans with Disabilities Act of 1990 (ADA)




Accessibility Guidelines for Buildings and
Facilities.


CCR
California Code of Regulations, Title 8, Div. 1, Chap. 4, Subchap. 5, Electrical Safety Orders


CCR
California Code of Regulations, Title 8, Div. 1, Chap. 4, Subchap. 7, Article 108, Confined Spaces


CCR
California Code of Regulations, Title 8, Div. 1, Chap. 4, Subchap. 20, Tunnel Safety Orders


CCR
California Code of Regulations, Title 24, Building
Standards Code


NFPA 70
National Electrical Code (NEC)


NFPA 72
National Fire Alarm Code


NFPA 820
Standard for Fire Protection in Wastewater
Treatment and Collection Facilities


SCAQMD
South Coast Air Quality Management District
2.
Industry Standards:




UL 38
Standard for Manually Signaling Boxes for Fire
Alarm Systems


UL 217
Standard for Single and Multiple Station Smoke
Alarms


UL 268
Standard for Smoke Detectors for Fire Alarm
Signaling Systems


UL 268A
Standard for Smoke Detectors for Duct
Applications


UL 346
Standard for Waterflow Indicators for Fire
Protective Signaling Systems


UL 864
Standard for Control Units and Accessories for
Fire Alarm Systems


UL 1481
Standard for Power Supplies for Fire Protective
Signaling Systems


UL 1638
Standard for Visual Signaling Appliances - Private-Mode Emergency and General Utility Signaling


UL 1711
Standard for Amplifiers for Fire Protective
Signaling Systems
UL 1971 Standard for Signaling Devices for the Hearing
Impaired

ISO 9001 Quality Management Systems - Requirements

3. Other Standards:

EIA Electronic Industries Alliance

FM FM Approvals (formerly, Factory Mutual
Research Corporation)

NEMA National Electrical Manufacturers Association

NFPA National Fire Protection Association

TIA Telecommunications Industry Association

C. Comply with the applicable reference Specifications as directed in the General
Requirements and Additional General Requirements.

D. The construction and installation of all electrical equipment and materials shall comply with all provisions of the Codes, regulations and standards specified above, as applicable, and other applicable federal, state and local codes and regulations.

1.5 CONTRACTOR SUBMITTALS

A. Submittals shall be made in accordance with the General Requirements, Additional General Requirements, Section 16010, Electrical General Provisions, and as specified herein. Include detailed information on the following:

1. Fire Alarm Control Panels

2. Local Control and Display Annunciators

3. Remote System Point Annunciators

4. Fire Alarm Operations Interface

5. Control and Signal Modules

6. System Intelligent Detectors

7. Stobe and Horn

8. Outdoor Rotating Light

9. Fire Alarm Pull Stations

10. Fire Alarm Cables

11. Conduit and Junction Boxes

B. Certification and verification as required elsewhere herein. The proposed equipment shall be subject to acceptance by the ENGINEER and acceptance by the local Fire Department. No equipment shall be ordered or installed on the premises without the acceptance and approval, respectively.

C. Where catalog cuts and other brochures depicting product characteristics are supplied, annotate to show product to be used on this project.

D. Test documentation shall be provided in a three-ring binder(s) within three weeks after the completion of the project. The binder(s) shall be clearly marked on the outside front cover and spine with the words “Test Results”, the project name, and the date of completion (month and year). Scanner tests shall be printed on 8-1/2- x 11-inch paper. When repairs and retests are performed, the problem found and corrective action taken shall be noted, and both the failed and passed test data shall be collected in the binder.
E. CONTRACTOR shall furnish within 15 days of project acceptance As-built Floor
Plans illustrating location of components of the fire alarm system.

F. CONTRACTOR shall comply with the provisions of SCAQMD Rule 1107 and shall submit daily reports to OCSD on the usage of asphalt primers, paints, plastic cements, varnished and other items identified under SCAQMD Rule 1107. The daily report shall be on forms furnished by OCSD. OCSD shall have the right to delay or limit the amount of paint to be applied in any 24-hour period, as specified by SCAQMD rules and regulations, with no change in Contract Price.

G. The CONTRACTOR shall provide hourly Service Rates and semi-annual inspection prices, performed by a factory trained and authorized personal, for this installed Fire Alarm System with the submittal.

H. A complete set of shop drawings, including each unit subassembly that requires a field wire be connected to it, shall be supplied. The following information shall be provided on the shop drawings:

1. Type, size, rating, style, catalog number, manufacturers names, photos, and/or catalog data sheets for all items proposed to meet these Specifications.

2. Block diagram showing system relationships of major components and quantities and interconnecting cable requirements.

3. Plans showing equipment locations, raceway, and conductor requirements

4. Control console and panel arrangements, equipment outlet devices, and special mounting details.

5. Wiring diagrams showing terminal identification for field-installed wiring.

6. Catalog literature for all components.

7. Control logic, electrical schematic, and connection diagrams for the complete fire alarm system. The diagrams shall include all devices, (i.e., manual stations, bells, fire alarm panel, emergency power unit, remote station modules, zone distribution, and detector requirements).

8. Written certification by the CONTRACTOR stating that the system and its component parts are as listed and approved by the California State Fire Marshal and that the installation conforms in all aspects to requirements of the local fire departments and NFPA.

9. Experience, licensing and Edwards System Technology authorization of installer.

10. Field testing procedures and requirements.

1.6 QUALITY ASSURANCE

A. CONTRACTOR Qualifications:

1. Comply with the requirements for the certifications, licenses, training, skills, experience, and other qualifications specified in Article entitled “Contractor Submittals” of this Specification.

2. Comply with the requirements for the certifications, licenses, training, skills, experience, and other qualifications specified in Article entitled “Installation” of this Specification.

3. Comply with the requirements for the certifications, licenses, training, skills, experience, and other qualifications specified in Paragraph entitled “Asbestos” of this Specification.

4. Comply with the requirements for the certifications, licenses, training, skills, experience, and other qualifications specified in Article entitled “Warranty” of this Specification.
1.7 WARRANTY

A. The CONTRACTOR shall provide a system warranty covering the installed fire alarm system against defects in workmanship, components, and performance, and follow-on support after project completion.

1. The CONTRACTOR shall warrant the fire alarm system against defects in workmanship for a period of one (1) year from the date of beneficial occupancy of the Work pursuant to “Use Prior to Final Completion” of the General Conditions. The warranty shall cover all labor and materials necessary to correct a failed portion of the system and to demonstrate performance within the original installation Specifications after repairs are accomplished. This warranty shall be provided at no additional cost to OCSD.

2. The CONTRACTOR shall facilitate a 15-year component warranty between the manufacturer and OCSD. An extended component warranty shall be provided that warrants functionality of all components used in the system for 15 years from the date of acceptance.

a. The CONTRACTOR shall maintain current status with the warranting manufacturer, including all training requirements.

b. The CONTRACTOR shall staff each installation crew with the appropriate number of trained personnel, in accordance with their manufacturer/warranty Contract Agreement, to support the 15-Year Performance Warranty requirements.

c. After installation, the CONTRACTOR shall submit all documentation to support the warranty in accordance with the manufacturer’s warranty requirements, and to apply for said warranty on behalf of OCSD.

d. The warranty shall cover the components and labor associated with the repair/replacement of any failed link, within the warranty period that is a valid warranty claim.

B. Comply with the requirements for the warranties and guaranties specified in
Paragraph entitled “Manufacturer” of Part 2, Article entitled “General” of this Specification.

PART 2 - PRODUCTS

2.1 GENERAL

A. Manufacturer:

1. The CONTRACTOR shall use the Edward Systems Technology (EST) Fire Alarm
System.

2. This Fire Alarm System Specification shall be conformed to in its entirety to ensure that the installed and programmed Fire Alarm System will accommodate all of the future requirements and operations required by OCSD. Any specified item or operational feature not specifically addressed prior to bid date will be required to be met without exception.

3. Service Availability: The supplier shall have sufficient stock on hand and have a fully equipped service organization capable of guaranteeing response time within 8 hours of service calls, 24 hours a day, 7 days a week to service completed systems.

B. System Description:

1. The Fire Alarm System supplied under this Specification shall be a microprocessor-based network system. All Fire Alarm Control Panel Assemblies and connected annunciators and field devices shall be both designed and manufactured by the same company, and shall be tested and cross-listed as compatible to ensure that a fully functioning system is designed and installed.
2. The system shall be capable of detecting the electrical location of each intelligent device including new and existing devices. It shall be possible to display the intelligent device map on the laptop PC.
3. All equipment furnished for this project shall be new and unused. All components and systems shall be designed for uninterrupted duty. All equipment, materials, accessories, devices, and other facilities covered by the Contract Documents shall be the best suited for the intended use and shall be provided by a single manufacturer. If any of the equipment provided under this Specification is provided by different manufacturers, then that equipment shall be recognized as compatible by both manufacturers, and “Listed” as such by Underwriters’ Laboratories.

4. It shall be possible for authorized service personnel using a Program/Service Tool or laptop personal computer to change the personality/function of device to meet changes in building layout or environment. System changes shall be verified by the manufacturer’s representative and a verification certificate presented upon completion.
2.2 FIRE ALARM SYSTEM COMPONENTS A. Fire Alarm Control Panel, EST3:
1. The Fire Alarm Control Panel shall be Edward EST3 panels with network capabilities. The Fire Alarm Control Panel shall be a self-standing control panel consisting of a card rack module, transformer, box circuit module, control modules, signal circuit modules, remote station modules, and battery charger, with lead- calcium rechargeable batteries (non-hydrogen type), capable of operating the fire alarm control panel for 24 hours without normal power. Transfer of power to battery back-up shall be automatic in both directions. The batteries shall be mounted inside the control panel. The basic control panel and batteries shall be self contained in a steel constructed cabinet with a locked door and a viewing glass to view status of LEDs. Normal power service to the panel shall be 120 V ac, single-phase, 3-wire plus ground circuits. The control panel cabinet shall conform to UL 864 and control panel requirements as outlined below.

2. Box circuit module shall provide an electrically-supervised normally open alarm initiating circuit for two-wire detectors or other normally open devices. It shall contain two alarm circuits per module, with each having a red alarm LED and an amber trouble LED. It shall also contain a power limited circuit flasher acknowledge output, alarm resound output, supervised annunciator, output on alarm, and an LED test for testing all LEDs. Upon activation of an alarm or trouble, the box circuit module shall indicate the exact zone of alarm/trouble without operator interface.

3. Remote station module shall be provided to act as interface unit between the fire alarm control and the authorized point of reception of the alarm condition, such as the computer.
4. Power supply modules (non-power limited) shall provide 24 V dc output, complete with overcurrent protection and status indicators. The power supply shall furnish power for entire system operation including remote devices such as, but not limited to, detectors, pull stations, standpipe alarm valves, etc.
5. Transformer shall be single-phase non-current limiting, rated 0.5 kVA with 120- volt primary.
6. Remote station modules shall be supplied as required, per standard manufacturer’s design, to act as interface unit between field-located detectors or alarms and the fire alarm control panel in the control room.

7. Fire alarm circuits shall be electrically supervised so that a trouble signal shall indicate the occurrence of a single open or a single ground fault that would prevent proper alarm operation.
B. Local Control and Display Annunciators:

1. Each panel in the installed system shall include local Control and Display Annunciators. These annunciators shall have integral membrane style, tactile push- button control switches, for the control of system functions, and LEDs with programmable (software-controlled) flash rates and slide-in labels for annunciation of system events.

2. The Local Control and Display Annunciators shall provide the system with individual zone and/or device annunciation.

C. Remote System Point Annunciators:

1. The Remote Control and Display Annunciators shall provide the system with individual zone and/or device annunciation.

D. Control and Signal Modules:

1. Control module shall provide alarm resound. Upon having detected an alarm condition, a zone will report its status to the control module. This alarm condition will cause the alarm LED on the zone to flash at a rate of approximately 150 pulses per minute. It will also cause the sounding of audible alarms and the operation of the fan control relays. Single-pole double-throw, unpowered contacts are required for fan and HVAC interlocks. The CONTRACTOR shall connect the contacts to the fan and HVAC equipment controls. Fire alarm CONTRACTOR shall furnish pole relays for this purpose.

2. Signal circuit modules shall be capable of supplying 2 amps of signal capacity of dc power. It shall supervise for line supervision and shorted line supervision and provide two signal circuits with two individual amber trouble lights. It shall also
contain a protective fuse visible and accessible on the front of the module, programmed alarm input and can be used for a non-coded system. Module shall be of the 2-wire parallel circuit.

3. Relays are to be of the same manufacturer and type used throughout the facility. When the acknowledge switch is depressed, the zone alarm LED will cease to flash, but remain illuminated; the signals will also be silenced. Activation of another zone shall repeat the entire process. The control module shall include a system reset, alarm lock-in, alarm resound, acknowledge switch, alarm LED, system trouble LED, supervised annunciator outputs for trouble with an annunciator trouble LED, high pitch sound devices, and LED test. A one/two amp meter shall also be provided to indicate the supervising current for the entire system.

4. For all outdoor locations, provide a NEMA 4, 316 stainless steel box, sized to hold the module and receive all conduit. Mount the box to wall surfaces using four
316 stainless steel screws and plastic shields; to existing support pipe using two 316 stainless steel U-bolts; or to a stand fabricated from two 316 stainless steel channel
struts and driven a minimum of 36 inches into soil.

5. Waterflow/Tamper Module, SIGA-WTM:

a. The Waterflow/Tamper Module shall be factory set to support two (2) supervised Class B input circuits. Channel A shall support a Normally-Open Alarm Delayed Latching Waterflow Switch circuit. Channel B shall support a Normally-Open Active Latching Tamper Switch. The water flow/tamper module shall be suitable for mounting on North American 2-1/2 inches (64 millimeters) deep 1-gang box or 1-1/2 inches (38 millimeters) deep 4-inch-square boxes with
1-gang cover. The intelligent water flow/tamper modules shall be EST model
SIGA-WTM sensors.
b. The Waterflow/Tamper Module may be substituted with EST Model SIGA- CT1 or EST Model SIGA-CT2 as appropriate to meet the requirements of the system and Fire Departments.

6. Signal Input Module, SIGA-CT1:

a. Provide intelligent single input modules - EST Model SIGA-CT1. The Single Input Module shall provide one (1) supervised Class B input circuit capable of a minimum of 4 personalities, each with a distinct operation. The module shall be suitable for mounting on 2-1/2-inch-deep 1-gang boxes and 1-1/2-inch-deep 4- inch-square boxes with 1-gang covers. The single input module shall support the following circuit types:

Input Module
Circuit Type
Normally-Open Alarm Latching
Manual Stations
Normally -Open Alarm Delayed
Latching
Waterflow Switches
Normally Open Active Non- Latching
Monitor, Fans, Dampers, etc.
Normally-Open Active Latching
Supervisory, Tamper Switches

7. Dual Input Module, SIGA-CT2:

a. Provide intelligent dual input modules - EST Model SIGA-CT2. The Dual Input Module shall provide two (2) supervised Class B input circuits capable of a minimum of 4 personalities, each with a distinct operation. The module shall be suitable for mounting on 2-1/2-inch-deep 1-gang boxes and 1-1/2-inch-deep 4- inch-square boxes with 1-gang covers. The dual input module shall support the following circuit types:

Input Module
Circuit Type
Normally-Open Alarm Latching
Manual Stations
Normally -Open Alarm Delayed
Latching
Waterflow Switches
Normally Open Active Non- Latching
Monitor, Fans, Dampers, etc.
Normally-Open Active Latching
Supervisory, Tamper Switches

8. Control Relay Module, SIGA-CR:

a. Provide intelligent control relay modules - EST Model SIGA-CR. The Control
Relay Module shall provide one (1) form “C” dry relay contact rated at 2 amps at
24 V dc to control external appliances or equipment shutdown. The control relay shall be rated for pilot duty and releasing systems. The position of the relay contact shall be confirmed by the system firmware. The control relay module shall be suitable for mounting on 2-1/2-inch-deep 1-gang boxes and 1-1/2-inch- deep 4-inch-square boxes with 1-gang covers.
E. Fire Alarm Components:

1. The System Intelligent Detectors shall be capable of full digital communications using both broadcast and polling protocol. Each detector shall be capable of performing independent fire detection algorithms. The fire detection algorithm shall measure sensor signal dimensions, time patterns and combine different fire parameters to increase reliability and distinguish real fire conditions from unwanted deceptive nuisance alarms. Signal patterns that are not typical of fires shall be eliminated by digital filters. Devices not capable of combining different fire parameters or employing digital filters shall not be acceptable.

2. Each detector shall have an integral microprocessor capable of making alarm decisions based on fire parameter information stored in the detector head. Distributed intelligence shall improve response time by decreasing the data flow between detector and analog loop controller. Detectors not capable of making independent alarm decisions shall not be acceptable. Maximum total analog loop response time for detectors changing state shall be 0.5 second.

3. Each detector shall have a separate means of displaying communication and alarm status. A green LED shall flash to confirm communication with the analog loop controller. A red LED shall flash to display alarm status. Both LEDs on steady shall indicate alarm-standalone mode status. Both LEDs shall be visible through a full
360-degree viewing angle.

4. The detector shall be capable of identifying up to 32 diagnostic codes. This information shall be available for system maintenance. The diagnostic code shall be stored at the detector.

5. Each smoke detector shall be capable of transmitting pre-alarm and alarm signals in addition to the normal, trouble and need cleaning information. It shall be possible to program the control panel activity. Each smoke detector may be individually programmed to operate at any one of five (5) sensitivity settings.

6. Each detector microprocessor shall contain an environmental compensation algorithm that identifies and sets ambient “Environmental Thresholds” approximately six times an hour. The microprocessor shall continually monitor the environmental impact of temperature, humidity, other contaminates as well as detector aging. The process shall employ digital compensation to adapt the detector to both 24-hour long- term and 4-hour short-term environmental changes. The microprocessor shall monitor the environmental compensation value and alert the system operator when the detector approaches 80 percent and 100 percent of the allowable environmental compensation value. Differential sensing algorithms shall maintain a constant differential between selected detector sensitivity and the “learned” baseline sensitivity. The baseline sensitivity information shall be updated and permanently stored at the detector approximately once every hour.

7. The intelligent analog device and the analog loop controller shall provide increased reliability and inherent survivability through intelligent analog standalone operation. The device shall automatically change to standalone conventional device operation in the event of a loop controller polling communications failure. In the analog standalone detector mode, the analog detector shall continue to operate using sensitivity and environmental compensation information stored in its microprocessor at the time of communications failure. The analog loop controller shall monitor the loop and activate a loop alarm if any detector reaches its alarm- sensitivity threshold.

8. Each Signature Series device shall be capable of automatic electronic addressing and/or custom addressing without the use of DIP or rotary switches. Devices using DIP or rotary switches for addressing, either in the base or on the detector shall not be acceptable.
9. The intelligent analog detectors shall be suitable for mounting on any Signature
Series detector mounting base.

a. Hazardous Area Smoke Detector, System Sensor Model #1151EIS, CSFM
#7271-1209:185, Or Equal:

1) The detector shall be FM-approved for Class 1 Division 1 areas. The smoke detector shall interface with the EST3 using a Model SIGA-CT1 addressable transponder; use one transponder for each zone.

2) Smoke detectors in Class 2 areas shall be Model #1151EIS with B401 base, Or Equal.

b. Duct Smoke Detector, SIGA-DH:

1) Air Duct Smoke Detectors, SIGA-DH, shall be provide for air duct smoke detector heads capable of detecting visible and invisible products of combustion. Provide the detectors with a measuring chamber and a protected reference chamber sensitive to changes in temperature and humidity only. Protect the measuring chamber from damage and insects. Provide a built-in 5-second delay to minimize alarms due to transient smoke.

2) Variations in duct air velocity between 400 and 4,000 FPM (2 and
20.3 m/sec.) shall not cause any false alarms. Safeguard radioactive parts
and protect circuitry against electrical transients, electromagnetic interference, and polarity reversal. Factory set the detector sensitivity. Mount the detectors head in an enclosure suitable for mounting to an air
duct. Provide an air sampling tube that extends into the duct air stream.

3) Provide smoke detector duct housing assemblies to facilitate mounting an intelligent analog photoelectric detector, along with a standard, relay or isolator detector mounting base. Provide for variations in duct air velocity between 300 and 4,000 feet per minute (300 to 1,000 feet per minute for ion- photo-heat detector). Protect the measuring chamber from damage and insects. Provide an air exhaust tube and an air sampling inlet tube that extends into the duct air stream up to 10 feet. Provide drilling templates and gaskets to facilitate locating and mounting the housing. Provide five one gang knockouts for mounting optional Signature Series modules. Finish the housing in baked red enamel. Duct detectors installed on the exterior of the building shall be mounted in weather proof NEMA enclosures.

c. Strobe and Horn, Series 757:

1) Provide electronic horn/strobes manufactured by EST, Cat. No. 757
Series. In/out screw terminals shall be provided for wiring. The horn shall have a red plastic housing. A steady tone sound output level of 100 dBA peak shall be provided.

2) The strobe shall provide 15 cd, 30 cd, 60 cd, or 110 cd synchronized flash outputs as required by area coverage. The strobe shall have lens markings oriented for wall or ceiling mounting. It shall be possible to replace the lens markings with LKW series or LKC series lens marking kits. Ceiling mounted strobes shall have lens markings with correctly oriented lettering. Removal of a installed Horn/Strobe to change the lens markings shall not be acceptable.

3) Horns/Strobes shall mount in a 4-inch electrical box with extension ring using the two screws provided with ring. It shall not be necessary to completely remove the screws to facilitate mounting.

4) All components installed in tunnels and where shown on the Drawings shall meet Class 1, Division 2 hazardous area classification requirements.
d. Hazardous Area Horn, EST Model #889D-AW, CSFM #7135-1388:133, Or
Equal:

1) Horn shall be listed for Class 1, Divisions 1 and 2, Groups C and D; Class 2, Divisions 1 and 2, Groups E, F, and G locations. The horn shall be polarized and supervised.
e. Hazardous Area Strobe, EST Model #97DEXBC-G1, CSFM #7125-
1388:210, Or Equal:
1) Strobe shall be listed for Class 1, Divisions 1 and 2, Groups C and D; Class 2, Divisions 1 and 2, Groups E, F, and G, and Class 3 locations. The strobe shall be polarized and supervised. Each strobe draws 1.4 amps. A maximum of two strobes can be connected to a single supervised circuit, and special attention shall be made to voltage drop calculations. The strobe shall include a wall-mount bracket.
f. Strobe, Series 202:
1) Provide electronic strobes manufactured by EST, Cat. No. 202 Series. The strobe shall provide 15 cd, 30 cd, 60 cd, or 110 cd synchronized flash outputs as required by area coverage. The strobe shall have lens markings oriented for wall or ceiling mounting. It shall be possible to replace the lens markings with LKW series or LKC series lens marking kits. Ceiling mounted strobes shall have lens markings with correctly oriented lettering.
g. Outdoor Rotating Light, 53R-G1:
1) Provide a minimum of one (1) outdoor rotating light (EST Model 53R-G1) for each building containing a fire alarm system. The rotating beacon shall be positioned on the building in a location suitable to the Fire Department to assist in the location of an alarm. The light shall be 24 V DC, powered by the fire alarm control panel. The beacon shall have a red lens and shall be suitable for outdoor mounting.
h. Fire Alarm Pull Stations, SIGA-270:
1) The fire alarm pull stations shall be CSFM #7150-026:11, manual type, single-action break glass rod type, with recessed pull lever, positive action sealed switch, and double-screw wiring terminals. Enclosure shall be cast metal, finished in fire alarm red, surface or semi-flush mounting as required. Fire alarm pull stations shall be provided at all entrances/exits of the facility, and as required by local fire departments, whether indicated on the Drawings or not.

2) It shall be possible to address each Signature Series fire alarm pull station without the use of DIP or rotary switches. Devices using DIP switches for addressing shall not be acceptable. The manual stations shall have a minimum of two diagnostic LEDs mounted on their integral, factory- assembled single or two-stage input module. A green LED shall flash to confirm communication with the loop controller. A red LED shall flash to display alarm status. The station shall be capable of storing up to 24 diagnostic codes that can be retrieved for troubleshooting assistance. Input circuit wiring shall be supervised for open and ground faults. The fire alarm pull station shall be suitable for operation in the proposed environment:

3) Provide intelligent single-action, single-stage fire alarm stations SIGA-270. The fire alarm station shall be of metal construction with an internal toggle switch. Provide a locked test feature. Finish the station in red with silver “PULL IN CASE OF FIRE” lettering. The manual station shall be suitable for mounting on North American 2-1/2 inches (64 millimeters) deep
1-gang box and 1-1/2 inches (38 millimeters) deep 4-inch-square box with 1- gang cover.
i. Hazardous Area Manual Station, Killark Model #XAL53, CSFM #7150-
1439:100, Or Equal

1) Manual stations shall be listed for Class 1, Divisions 1 and 2, Groups C and D; Class 2, Divisions 1 and 2, Groups E, F, and G; Class 3 locations. The manual station shall be interfaced to the EST3 using a Model #SIGA- CT1 addressable transponder. Each manual station shall report its individual location to the EST3 panel.

j. Fire Alarm Cables:

1) Fire alarm cables shall be one pair #16 AWG solid copper, vinyl or Teflon insulated, and an overall jacket insulation shall be individually color-coded. Jacket thickness per UL 1424. Cables shall be supplied and installed to interconnect the entire fire alarm system as specified herein, whether indicated on the Drawings or not, to meet local codes and requirements.

k. Conduit and Junction Boxes:

1) All fire alarm system cable shall be enclosed in raceway. The raceway systems and pull boxes shall comply with the OCSD Standard Specifications
16130 except as follows:

a) For interior, concealed ceiling plenum areas, use electrical metallic tubing (EMT) with 5-foot (maximum) lengths of steel flexible conduit, sized for the cable. Fasten conduit to structural elements using one-hole straps cadmium plated screws and plastic shields. Mount required boxes to ceiling grid using caddy-style cross bar and grid clips.

b) Cable trays shall not be used to run fire alarm wiring. For exposed conduit in wet locations, use PVC-coated galvanized rigid steel conduit per Standard Specifications. For exposed conduit in dry locations, use galvanized rigid steel, factory finish.

c) Junction boxes shall be per the requirements of Specification section
16050, Basic Materials and Methods.

F. Reflected Beam Smoke Detectors:

1. Beam smoke detectors shall be of the reflected beam type with the transmitter and the receiver in a single unit. Beam detectors shall be provided with sensitivity test feature and remote test station option. Beam detectors shall be System Sensor Beam1224(s), Gamewell Fire Ray 50RU, Or Equal.

PART 3 - EXECUTION

3.1 GENERAL

A. Project Management:

1. The CONTRACTOR shall establish a single point of contact with OCSD who shall be responsible for reporting progress and updating ENGINEER with issues that OCSD must address to facilitate the fire alarm system installation. The CONTRACTOR’s POC shall provide (daily or weekly) (verbal or written) reports to the ENGINEER detailing progress. Requests for access to limited access or restricted areas shall be made (the day prior to the required access). Information critical to the completion of the task or project shall be communicated to ENGINEER, as the requirement becomes known. Routine information shall be passed during the scheduled progress report.
B. Housekeeping:

1. The CONTRACTOR shall maintain OCSD facilities in a neat and orderly manner during the installation of the fire alarm system. All CONTRACTOR’s tools, materials, and personal effects shall be stored in an OCSD-provided staging area when not in use. OCSD facilities shall be maintained in broom-clean condition at the completion of work each day. At the completion of work in each area, the CONTRACTOR shall perform a final cleaning of debris prior to moving the installation crew to the next work area.

C. Special Work Sequence and Constraints:

1. The existing treatment plant facilities shall be maintained in full operation during the execution of the Work. If downtime of utilities or equipment occurs due to lack of schedule, CONTRACTOR error, or other items that are CONTRACTOR’s fault, CONTRACTOR shall work continuously (24 hours per day) until the utility or equipment is in operation. All costs for such work shall be the responsibility of the CONTRACTOR.

2. Downtime for panel connections shall be kept at a minimum and shall require prior written acceptance by the ENGINEER, 72 hours in advance of the requested downtime. The CONTRACTOR shall submit request for shutdown in writing a minimum of 1 week prior to the date the above acceptance is requested. All equipment, device, and wiring installations that occur in office areas shall be performed after 5:30 p.m. on weekdays or between 7:00 a.m. and 4:30 p.m. on the weekends. This work shall be scheduled with OCSD staff. The CONTRACTOR shall submit a written schedule detailing the connections to existing facilities.

3. Any Work that must be accomplished in the vicinity of operating systems within the plant shall be done within a schedule that will accommodate plant operating requirements. The schedule shall be submitted to OCSD for review and concurrence prior to the beginning of any construction.

4. Any Work that blocks roadways, access to buildings and parking lots shall require written acceptance following the requirements above for notification and acceptance.

5. OCSD lockout/tagout procedures shall be followed for isolation of equipment for
Work. OCSD will provide tags and the CONTRACTOR shall provide lockout device.

6. Prior to commencing each task, the task will have a job hazard analysis performed in which the CONTRACTOR and the ENGINEER (including OCSD inspectors and OCSD safety personnel) will be involved. All safety issues will be addressed and verification will be made that all required safety measures will be carried out and required safety equipment is available. At the work space analysis meeting, the CONTRACTOR shall submit a Work Plan that describes the number of people involved in the Work, the Work procedures, materials and equipment to be used, and any applicable Material Safety Data Sheets.

D. Asbestos:

1. It is the specific intent of these Contract Documents to exclude from the Work any and all products or materials containing asbestos. No products containing asbestos shall be incorporated in the Work.
2. It is not expected that the CONTRACTOR will encounter any existing asbestos materials. If asbestos materials are encountered during any Work, the CONTRACTOR shall promptly notify the ENGINEER in writing. Removal of existing asbestos material shall be performed by a CONTRACTOR or Subcontractor registered by Cal/OSHA and certified by the Contractors State License Board in the State of California. Copies of the certification shall be submitted to the ENGINEER. The CONTRACTOR or Subcontractor shall comply with all federal, state and local laws and regulations regarding handling and removal of asbestos materials.

3. If asbestos materials are encountered, the cost for removal and disposal shall be by change order.

3.2 INSTALLATION

A. All equipment and devices shall be installed in accordance with the requirements of the Contract Documents, NFPA 72, and the manufacturer's recommendations. Refer to the Drawings that represent an overall schematic of the fire alarm system to be provided.

B. No wiring other than fire alarm circuits shall be mixed into the fire alarm conduits. Wiring splices shall not be permitted except at device connections. Transposing or changing color coding on wiring shall not be permitted. All wiring shall be checked and tested to ensure that there are no grounds, opens, or shorts.

C. The CONTRACTOR shall integrate fire alarm systems from the automatic sprinkler system, halon suppression systems, elevator, and other alarm devices contained within the facility to assure a complete installation. The CONTRACTOR shall provide integration of the Casi-Rusco Access Control and Monitoring System interface for the installed fire alarm system.

D. The CONTRACTOR shall have the manufacturer of the fire alarm system equipment provide the services of a qualified and authorized technical representative to supervise and instruct the CONTRACTOR in installation procedures, to inspect the entire fire alarm system after installation has been completed, and assist in the performance of all field tests.

E. All electrical devices, wiring, conduits, etc. shall be provided to meet the various electrical area classification requirements as outlined in the Drawings.

F. Existing wiring shall be modified and used to interconnect the new system elements. The CONTRACTOR shall install additional wire and cable required for a functional system at no additional cost to OCSD.

3.3 PROGRAMMING

A. The CONTRACTOR shall update the system documentation to show additions an changes to the system programming required to support new installations or changes to the existing system.

3.4 DOCUMENTATION

A. The CONTRACTOR shall update the system documentation to show additions and changes to the system. The existing documentation shall be used as a starting point; the CONTRACTOR shall integrate the changes into the existing documentation. Supplements tacked onto the back are not acceptable.

3.5 SYSTEM TESTING

A. Preliminary Operational; Testing:

1. The CONTRACTOR shall conduct operational tests of each equipment item or each equipment system. The CONTRACTOR's operational test of each piece of equipment or system shall continue for not less than 24 hours without interruption.
2. All parts shall operate satisfactorily in all respects, under continuous full load and in accordance with the specified requirements, for the full duration of the test period. If any part of a unit shows evidence of unsatisfactory or improper operation during the test period, correction or repairs shall be made and the full operational test, as specified above, shall be repeated after all parts operate satisfactorily. The CONTRACTOR shall furnish all personnel, power, and all other necessary facilities for conducting the CONTRACTOR's test operations.

B. Final Operational Testing:

1. After all equipment is installed and the entire project is ready to operate, OCSD will test all equipment for a period not to exceed 7 days by operating either under actual or simulated operating conditions before Final Acceptance is given. At the discretion of OCSD, final test operation and final acceptance may be given on portions of the project prior to completion of the entire project. All defects of material or workmanship that appear during this test period shall be corrected by the CONTRACTOR. After such corrections are made, the final test operation may be run again before final acceptance a; this requirement may be waived by OCSD.

2. OCSD will supply all power, operating personnel, and auxiliaries required for this final operational test.

3. If operational completion of portions of the project will be required prior to final completion of the total project, OCSD shall have the right to take possession of and use any completed portions of the Work. Use of any completed portions of the Work shall not be construed as acceptance of those items by OCSD.

3.6 ACCEPTANCE TESTING

A. In-Progress Inspections:

1. The ENGINEER will make periodic inspection of the project in progress. One inspection will be performed at the conclusion of cable pulling, prior to closing of the false ceiling, to inspect the method of cable routing and support, and the firestopping of penetrations. A second inspection will be performed at completion of cable termination to validate that cables were dressed and terminated in accordance with TIA/EIA specifications for jacket removal and pair untwist, compliance with manufacturer’s minimum bend radius, and that cable ends are dressed neatly and orderly.

B. Final Inspection:

1. Upon completion of the project, the ENGINEER will perform a final inspection of the fire alarm system with the CONTRACTOR’s Project Foreman. The final inspection will be performed to validate that all cables were installed as defined in the Drawing package, and that the installation meets the aesthetic expectations of OCSD.

C. Test Verification:

1. Upon receipt of the test documentation, OCSD reserves the right to perform spot testing of a representative sample of the fire alarm system to validate test results provided in the test document. OCSD testing will use the same method employed by the CONTRACTOR, and minor variations shall be allowed to account for differences in test equipment. If significant discrepancies are found the CONTRACTOR shall be notified for resolution.

D. System Performance:

1. During the 3-week period between final inspection and delivery of the test and as-built documentation, OCSD will activate the fire alarm system. OCSD will validate operation of the fire alarm system during this period.
E. Final Acceptance:


1. Completion of the installation, in-progress and final inspections; receipt of the test and as-built documentation; and successful performance of the system for a 2-week period shall constitute final acceptance of the system.

No comments:

Post a Comment