Section 13700
ACCESS CONTROL AND ALARM MONITORING
PART 1 - GENERAL
1.1 THE REQUIREMENT
A. The CONTRACTOR shall furnish all
tools, equipment, material, and supplies, and perform all labor
required to install all card readers, glass break detectors, infrared
sensors, door contacts, electric door hardware wiring, cables,
conduits, alarms, and connections, and shall perform all programming,
system modifications, and testing indicated on the Drawings,
specified herein, and required to support a complete and operable
Access Control and Alarm Monitoring system. A minimum of a 1 year
warranty for parts and labor for these components shall be required
under terms of this Contract.
B. The CONTRACTOR shall provide all
labor, materials, and equipment, which shall be enumerated herein,
for a complete door security system. As part of this Contract,
furnish all tools, equipment, material, and supplies, and perform all
labor required to install all card readers, glass break detectors,
infrared sensors, door contacts, electric door hardware wiring,
cables, conduits, alarms, and connections and perform all changes,
and testing indicated on the Drawings, specified herein, and required
to extend, alter and modify the existing Access Control and Alarm
Monitoring system. The modified system shall be complete and
operable, fully integrated to the existing system, and shall be
recertified in accordance manufacturer’s instructions to comply and
shall comply with local permitting requirements.
C. The Access Control and Alarm
Monitoring System will be controlled by an existing micro processor
based controller, the Casi-Rusco, Picture Perfect Unix System
installed in the OCSD Control Center. It shall be the CONTRACTOR’s
responsibility to install all card readers, glass break detectors,
infrared sensors, door contacts, electric door hardware wiring,
cables, conduits, alarms, and connections. A minimum of a 1-year
warranty for parts and labor for these components shall be required
under terms of this Contract. Any fees for manufacturer’s
representative services shall be included in the CONTRACTOR’s bid.
1.2 RELATED WORK SPECIFIED
ELSEWHERE
A. The requirements of the following
sections and divisions apply to the Work of this section. Other
sections and divisions of the Specifications, not referenced below,
shall also apply to the extent required for proper performance of
this Work.
1. Division 11, Equipment, applicable
sections
2. Section 13850, Fire Alarm System
3. Division 16, Electrical,
applicable sections
4. Section 16010, Electrical General
Provisions
5. Section 16050, Basic Materials and
Methods
6. Section 16120, Conductors and
Cables
7. Section 16130, Raceway Systems
and Pull Boxes
8. Division 17, Instrumentation and
Control, applicable sections
1.3 REFERENCE SPECIFICATIONS,
CODES, AND STANDARDS
A. All Work specified herein shall
conform to or exceed the applicable requirements of the referenced
portions of the following publications to the extent that the
provisions thereof are not in conflict with other provisions of
these Specifications.
B. Comply with the applicable
editions of the following codes, regulations and standards.
-
1.
Codes and Regulations:
Accessibility Guidelines for Buildings andFacilities.
California Code of Regulations, Title 24, BuildingStandards Code
Treatment and Collection Facilities
C. Comply with the applicable
reference Specifications as directed in the General
Requirements and Additional General
Requirements.
D. The construction and
installation of all electrical equipment and materials shall
comply with all provisions of the Codes, regulations and standards
specified above, as applicable, and other applicable federal, state
and local codes and regulations.
E. Comply with the following:
1. FC Wnx (old Casi-Rusco)
Installation Manual pertaining to each device installed under this
Contract.
2. FC Wnx (old Casi-Rusco)
programming procedures for modifying and proving software changes
for existing installations.
3. FC Wnx (old Casi-Rusco) testing
and startup procedures.
1.4 CONTRACTOR SUBMITTALS
A. Submittals shall be made in
accordance with the General Requirements, Additional General
Requirements, Section 16010, Electrical General Provisions, and as
specified herein. Include detailed information on the following:
1. Where catalog cuts and other
brochures depicting product characteristics are supplied, annotate
to show product to be used on this project.
2. Test documentation shall be
provided in a three-ring binder(s) within three weeks after the
completion of the project. The binder(s) shall be clearly marked
on the outside front cover and spine with the words “Test
Results”, the project name, and the date of completion (month and
year). Scanner tests shall be printed on 8-1/2 x
11-inch paper. When repairs and
retests are performed, the problem found and corrective action taken
shall be noted, and both the failed and passed test data shall be
collected in the binder.
3. CONTRACTOR shall furnish within
15 days of acceptance of the Access Control and Alarm Monitoring
System, as-built floor plans illustrating location of components of
Access Control and Alarm Monitoring System. OCSD drawings shall be
used as the source documentation for the as-built floor plans, when
available. CONTRACTOR shall modify OCSD drawings to reflect all
changes to the security system.
4. The CONTRACTOR shall provide
hourly service rates and semi-annual inspection prices,
performed by a factory trained and authorized personal, for this
installed Access Control and Alarm Monitoring System with the
submittal.
5. A complete set of shop drawings,
including each unit subassembly that requires a field wire be
connected to it, shall be supplied. The following information shall
be provided on the shop drawings:
a. Type, size, rating, style,
catalog number, manufacturers names, photos, and/or catalog data
sheets for all items proposed to meet these Specifications.
b. Block diagram showing system
relationships of major components and quantities and
interconnecting cable requirements.
c. Plans showing equipment
locations, raceway, and conductor requirements.
d. Control console and panel
arrangements, equipment outlet devices, and special mounting
details.
e. Wiring diagrams showing terminal
identification for field-installed wiring.
f. Catalog literature for all
components.
g. Control logic, electrical
schematic, and connection diagrams for the complete Access Control
and Alarm Monitoring System. The diagrams shall include all
devices.
h. Field testing procedures and
requirements
1.5 QUALITY ASSURANCE A.
General:
1. Comply with the requirements
specified herein and the applicable reference
Specifications of the General
Requirements and Additional General Requirements.
B. The system manufacturer shall be
able to provide an upgrade path from earlier systems produced by
that manufacturer and be able to demonstrate an upgrade path to
successive generation systems of greater capacity and functionality.
C. Any fees for manufacturer’s
representative services shall be included in the
CONTRACTOR’s bid.
D. An existing system that is altered
shall be retested in accordance with manufacturer’s instructions.
E. The CONTRACTOR shall obtain all
city, county, or other permits required by the governing authority.
OCSD Plant 1 is located in Fountain Valley.
F. Contractor Qualifications:
1. Comply with the requirements
for the certifications, licenses, training, skills, experience,
and other qualifications specified in Paragraph entitled “Asbestos”
of this Specification.
2. Comply with the requirements
for the certifications, licenses, training, skills, experience,
and other qualifications specified in Article entitled
“Installation” of this Specification.
3. Pursuant Article entitled “The
Requirement” above, all final wiring between connecting door and
card readers to the security multiplexer and the multiplexer to the
existing controller shall be performed by a certified representative
of Casi-Rusco.
1.6 WARRANTY
A. The CONTRACTOR shall provide a
system warranty covering the installed Access Control and Alarm
Monitoring System against defects in workmanship, components, and
performance, and follow-on support after project completion.
1. The CONTRACTOR shall warrant the
Access Control and Alarm Monitoring System against defects in
workmanship for a period of one year from the date of beneficial
occupancy of the Work pursuant to “Use Prior to Final Completion”
of the General Conditions. The warranty shall cover all labor and
materials necessary to correct a failed portion of the system and to
demonstrate performance within the original installation
specifications after repairs are accomplished. This warranty shall
be provided at no additional cost to OCSD.
2. The CONTRACTOR shall facilitate a
15-year component warranty between the manufacturer and OCSD. An
extended component warranty shall be provided, which warrants
functionality of all components used in the system for 15 years from
the date of acceptance.
3. The CONTRACTOR shall
maintain current status with the warranting manufacturer,
including all training requirements.
4. Comply with warranty
requirements indicated in Part 1, Article entitled “The
Requirement” of this Specification
PART 2 - PRODUCTS
2.1 MANUFACTURER
A. The Access Control and
Alarm Monitoring System components shall be manufactured
by UTC/GE/Lenel (old Casi-Rusco) with no exception unless specified
otherwise herein.
2.2 MICRO/5 FIELD PANEL
A. Overview: The field
panel shall incorporate microprocessor-based, digital
technology, using high speed processing for maximum reliability.
The system shall use distributed intelligence architecture, with
controller operating independently of one another. All database
information shall be stored at the field panel level. All decision-
making shall be performed at the field panel, eliminating degraded
mode operation. Proprietary software programs and control logic
information used to coordinate and drive the system hardware shall
be stored in Flash Read Only Memory (ROM). The field panel shall be
ROM (field) that can be upgraded from the host computer. The system
shall be flexible and modular in design, allowing easy expansion.
B. System Configuration: The field
panel shall communicate to the host server over Ethernet network ..
The system shall support up to 32 field panels that control up to
256 readers and will monitor up to 1,536 alarm points. The
distance between the badge reader and the field panel shall be 200
feet (depending on the reader this distance can be extended to 5,000
feet).
C. Digital Badge Imaging System: A
separate digital badge imaging system shall be provided. The
Imaging System shall be fully integrated with the access control
system application such that the images can be viewed from the
access control system and that badge holder information carried in
the access control system shall be available to the Imaging System.
The Imaging System shall provide support for badge design, image
capture and badge print functions. The badge design function shall
provide all supporting drawing, text input and manipulation tools
and for the import of bit-maps for use in creating the badge design.
2.3 FIELD PANEL OPTIONS
A. Input Points: A controller
supporting eight badge readers shall provide one door status point
and one request to exit point for each reader. The field panel is
to be easily field expandable in increments of 20 input points and
to have the capacity to support two
20 digital input options for a total
of 40 additional inputs. The input on the expansion boards shall be
supervised with end-of-line resistors, which shall allow the
software to determine the difference normal, ground, short, and
alarm conditions.
B. Output Points: A controller
supporting eight card readers shall provide one door strike output
for each reader. The field panel is to be easily field
expandable in increments of 16 digital output points and to have
the capacity to support two 16 digital output options for a total of
32 additional outputs.
2.4 CARD READER/KEYPAD
A. Option 1 - Proximity Reader:
1. The system shall support the use
of a proximity reader. The reader shall have a read range of up to
6 inches. There shall be communications between the reader and the
controller such that if the reader to field panel wire is cut, or
the reader is disabled or the reader tamper switch is tripped, an
alarm message will be sent to the system to inform the operator of
the condition. The reader shall communicate to the controller
through four wires. The reader shall operate acceptably using
unshielded cable, though use of shielded cable is recommended. The
reader shall be capable of incorporating the digital inputs for the
door contact and the exit device into the four- wire communications
architecture. The reader shall be able to be mounted against
nonmetal walls. The reader shall mount to a standard single gang
electrical box. The reader shall be powered by +12 V dc, supplied by
the controller. The proximity access control badge compatible with
the proximity reader shall include an externally visible number,
which can be referenced to the internal encoded badge ID number. The
reader shall be the GE/Lenel Model 941 Proximity Perfect Reader.
2.5 CARD ACCESS DOOR SECURITY
ELECTRIFIED HARDWARE
A. Each of the doors requiring the
GE/Lenel card readers shall be operated and/or monitored with
electrified hardware. All the locks shall be compatible with the
OCSD existing Schlage master-key-only system (Schlage Model No.
EL9080), except use Von Duprin Series E99, Advantex ER, Or Equal
electrified panic hardware exit devices and Schlage locks to
maintain compatibility. The specified electrical hardware will be
configured for fail secure (FSE) operation in the event of a power
outage. This will require a field conversion. This system will
allow a combination of Schlage keys, card access readers, or
automatic programming for locking/unlocking on demand. Each door
specified for electrical hardware shall require the CONTRACTOR to
install the following:
1. The installation of a passive
infrared sensor above and on the inside of each card reader door to
allow the shunting of any alarms as programmed.
2. A small step-down transformer,
120 V ac to 9 V ac, mounted inside a pullbox enclosure above the
ceiling for each card reader door to provide power to the card
reader.
3. A Von Duprin Model PS872,
Detex 82-800, Or Equal power supply, which provides 24-V dc
current to the electrical hardware on demand, shall normally be
mounted above the suspended ceiling. This power supply will be
wired to the nearest GE/Lenel (old Casi-Rusco) card reader via
conduits. All signals for opening doors will come from the GE/Lenel
(old Casi-Rusco) card reader and then into the power supply above
each specified door.
4. A Mont-Hard, Stanley, Or Equal
four-wire electrified hinge shall be installed in the center of the
door to provide current from the Von Duprin power supply to the Van
Duprin electrified door hardware. This electrified hinge transfer
the 2-V dc electrical current from the door jamb into the interior
of the door and ultimately to the electrical hardware.
5. Provide one set of Sentrol
DPDT series (double pole – double throw), Model 1076D,
recessed magnetic contacts for monitoring the open or closed
position of the specified doors through the card access door
security system. All magnetic door contacts as well as the control
signals to the specified electrical hardware shall be wired to the
nearest GE/Lenel (old Casi-Rusco) card reader using accepted cable
inside of electrical conduits.
2.6 DOOR SECURITY MAGNETIC
CONTACTS
A. The CONTRACTOR shall provide and
install one set of Sentrol DPDT series (double pole–double throw)
Model 1076D, Honeywell 947, Or Equal, recessed magnetic door
contacts for each of the doors that receive alarm point-monitoring.
All of these contacts will be wired with cable in conduit such that
each point will be wired to and monitored by the nearest card
reader.
2.7 DOOR SECURITY PASSIVE
INFRARED SENSORS
A. The CONTRACTOR shall provide and
install one Passive Infrared Sensors (PIR’s), for each card reader
door. Each PIR shall be Pulnix America Model No. PS-500 B/S,
Honeywell IS320WH, Or Equal. Each PIR shall be mounted above and on
the inside of each door. Each PIR shall be adjusted onsite to
properly cover either a single door or a double door as needed. The
PIR shall detect the presence of a person approaching the card
reader door upon exiting from the inside. If the security system is
programmed to alarm upon opening the card reader door, the PIR shall
be wired to cause the alarm to be shunted before the detected person
exits the door.
2.8 WINDOW SECURITY GLASS BREAK
SENSORS
A. The CONTRACTOR shall provide and
install dual technology glass break sensors, Blue Grass Model No.
9100, Honeywell 2500, Or Equal. Each glass break sensor will sense
both shock vibration and sound frequency of breaking glass and
signal an alarm through the nearest Casi-Rusco security system door
card reader. Each window zone for alarm monitoring shall consist of
approximately 25 feet of lateral coverage along the length of the
window. The glass break sensor shall normally be mounted above the
window on the inside just below the suspended ceiling and be wired
to the nearest card reader with accepted “plenum wire” cable.
2.9 BATTERY BACKUP
A. The CONTRACTOR shall provide
battery backup power for all modems, communications devices, and
door strikes. The battery shall be sized to provide 3 hours minimum
operation. The battery backup shall be sealed gelled electrolyte
rated to provide
120 percent of the system
requirements. The system battery shall have sufficient capacity
to operate the entire system for a period of at least 24 hours with
no outside source of power. Capacity shall include operation of
alarm horns and flashing lights for a period of 10 minutes during
any portion of the 24-hour period.
PART 3 - EXECUTION
3.1 GENERAL
A. Project Management:
1. The CONTRACTOR shall establish a
single point of contact (POC) with OCSD who shall be responsible for
reporting progress and updating the ENGINEER with issues that OCSD
shall address to facilitate the Access Control and Alarm Monitoring
System installation. The CONTRACTOR’s POC shall provide weekly
written reports to the ENGINEER detailing progress. Requests for
access to limited access or restricted areas shall be made the day
prior to the required access. Information critical to the
completion of the task and/or project shall be communicated to the
ENGINEER, as the requirement becomes known. Routine information
shall be passed during the scheduled progress report.
B. Housekeeping:
1. The CONTRACTOR shall maintain
OCSD facilities in a neat and orderly status during the installation
of the Access Control and Alarm Monitoring System. All CONTRACTOR
tools, materials, and personal effects shall be stored in an OCSD-
provided staging area when not in use. OCSD facilities shall be
maintained in broom clean condition at the completion of work each
day. At the completion of Work in each area, the CONTRACTOR shall
perform a final cleaning of debris prior to moving the installation
crew to the next work area.
C. Special Work Sequence and
Constraints:
1. The existing treatment plant
facilities shall be maintained in full operation during the
execution of the Work. If downtime of utilities or equipment occurs
due to lack of schedule, CONTRACTOR's error, or other items that are
CONTRACTOR's fault, CONTRACTOR shall work continuously (24 hours per
day) until the utility or equipment is in operation. All costs for
such work shall be the responsibility of the CONTRACTOR.
2. Downtime for electrical panel
connections shall be kept at a minimum and shall require prior
written acceptance by the ENGINEER, 72 hours in advance of the
requested downtime. The CONTRACTOR shall submit its request for
shutdown in writing a minimum of one week prior to the date the
above acceptance is requested. All equipment, device, and wiring
installations that occur in office areas shall be performed after
5:30 p.m. on weekdays and between 7:00 a.m. and 4:30 p.m. on the
weekends. This Work shall be scheduled with OCSD staff. The
CONTRACTOR shall submit a written schedule detailing the connections
to existing facilities.
3. Any Work that must be
accomplished in the vicinity of operating systems within the plant
shall be done within a schedule that will accommodate plant
operating requirements. The schedule shall be submitted to the
ENGINEER for review and concurrence prior to the beginning of any
construction.
4. Any Work that blocks roadways,
access to buildings and parking lots shall require written
ENGINEER’s acceptance following the requirements above for
notification and acceptance.
5. The OCSD lockout/tagout
procedures shall be followed for isolation of equipment for Work.
OCSD will provide tags and the CONTRACTOR shall provide lockout
device.
6. Prior to commencing each
task, the task will have a job hazard analysis performed in
which the CONTRACTOR, ENGINEER, and OCSD inspection and safety
personnel will be involved. All safety issues will be addressed and
verification will be made that all required safety measures will be
carried out and required safety equipment is available. At the job
hazard analysis meeting, the CONTRACTOR shall submit a Work Plan
that describes the number of people involved in the Work, the Work
procedures, materials and equipment to be used, and any applicable
Material Safety Data Sheets.
D. Asbestos:
1. It is the specific intent of
these Contract Documents to exclude from the Work any and all
products and/or materials containing asbestos. No products
containing asbestos shall be incorporated in the Work.
2. It is not expected that the
CONTRACTOR will encounter any existing asbestos materials. If
asbestos materials are encountered during any Work, the CONTRACTOR
shall promptly notify the ENGINEER in writing. Removal of existing
asbestos material shall be performed by a CONTRACTOR or
Subcontractor registered by Cal/OSHA and certified by the
Contractors State License Board in the State of California. Copies
of the certification shall be submitted to the ENGINEER. The
CONTRACTOR or Subcontractor shall comply with all federal, state and
local laws and regulations regarding handling and removal of
asbestos materials.
3. If asbestos materials are
encountered, the cost for removal and disposal shall be by change
order.
3.2 INSTALLATION
A. All equipment and devices shall
be installed in accordance with the requirements of the Contract
Documents and the manufacturer's recommendations.
B. All wiring shall be checked and
tested to ensure that there are no grounds, opens, or shorts.
C. The CONTRACTOR shall integrate
Access Control and Alarm Monitoring Systems with the Fire Alarm
System in Section 13850, Fire Alarm System.
D. The CONTRACTOR shall have the
manufacturer of the Access Control and Alarm Monitoring System
equipment provide the services of a qualified and authorized
technical representative to supervise and instruct the CONTRACTOR in
installation procedures, to inspect the entire Access Control and
Alarm Monitoring System after installation has been completed, and
assist in the performance of all field tests.
E. All electrical devices, wiring,
conduits, etc. shall be provided to meet the various electrical area
classification requirements as outlined in the Drawings.
F. Existing wiring shall be modified
and used to interconnect the new system elements, as required. The
CONTRACTOR shall install additional wire and cable required for a
functional system at no additional cost to OCSD.
3.3 PROGRAMMING
A. The CONTRACTOR shall perform all
device configuration and system programming required to support new
installations or changes to the existing system.
3.4 DOCUMENTATION
A. The CONTRACTOR shall update the
system documentation to show additions and changes to the system.
The existing documentation shall be used as a starting point; the
CONTRACTOR shall integrate the changes into the
existing documentation. Supplements tacked onto the back are not
acceptable.
3.5 SYSTEM TESTING
A. Preliminary Operational Testing:
1. The CONTRACTOR shall conduct an
operational test of each equipment item or each equipment system.
The CONTRACTOR's operational test of each piece of equipment or
system shall continue for not less than 24 hours without
interruption.
2. All parts shall operate
satisfactorily in all respects, under continuous full load and in
accordance with the specified requirements, for the full duration of
the test period. If any part of a unit shows evidence of
unsatisfactory or improper operation during the test period,
correction or repairs shall be made and the full operational test,
as specified above, shall be repeated after all parts operate
satisfactorily. The CONTRACTOR shall furnish all personnel, power,
and all other necessary facilities for conducting the CONTRACTOR's
test operations.
B. Final Operational Testing:
1. After all equipment is installed
and the entire project is ready to operate, OCSD will test all
equipment for a period not to exceed seven days by operating either
under actual or simulated operating conditions before Final
Acceptance is given. At the discretion of OCSD, final test
operation and final acceptance may be given on portions of the
project prior to completion of the entire project. All defects of
material or workmanship that appear during this test period shall be
corrected by the CONTRACTOR. After such corrections are made, the
final test operation may be run again before final acceptance; this
requirement may be waived by the ENGINEER.
2. OCSD will supply all power,
operating personnel, and auxiliaries required for this final
operational test.
3. If operational completion of
portions of the project will be required prior to final completion
of the total project, OCSD shall have the right to take possession
of and use any completed portions of the Work. Use of any completed
portions of the Work shall not be construed as acceptance of those
items by the ENGINEER.
3.6 ACCEPTANCE TESTING
A. In-Progress Inspections:
1. The ENGINEER shall make periodic
inspection of the project in progress. One inspection shall be
performed at the conclusion of cable pulling, prior to closing of
the false ceiling, to inspect the method of cable routing and
support, and the penetration fire stop. A second inspection shall be
performed at completion of cable termination to validate that cables
were dressed and terminated in accordance with TIA/EIA
specifications for jacket removal and pair untwist, compliance with
manufacturer’s minimum bend radius, and that cable ends are
dressed neatly and orderly.
B. Final Inspection:
1. The ENGINEER shall perform a final
inspection of the Access Control and Alarm Monitoring System with the
CONTRACTOR’s Project Foreman. The final inspection shall be
performed to validate that all cables were installed as defined in
the drawing package, and that the installation meets the
aesthetic expectations of the ENGINEER.
C. Test Verification:
1. Upon receipt of the test
documentation, the ENGINEER reserves the right to perform spot
testing of a representative sample of the Access Control and Alarm
Monitoring System to validate test results provided in the test
document. OCSD testing shall use the same method employed by the
CONTRACTOR, and minor variations shall be allowed to account for
differences in test equipment. If significant discrepancies are found
the CONTRACTOR shall be notified for resolution.
D. System Performance:
1. During the 3-week period between
final inspection and delivery of the test and as-built documentation,
OCSD will activate the Access Control and Alarm Monitoring System.
The ENGINEER will validate operation of the Access Control and Alarm
Monitoring System during this period.
E. Final Acceptance:
1. Final acceptance of the system
shall include, but not be limited to, the following:
a. Completion of the installation
b. In-progress and final inspections
c. Receipt of the test and as-built
documentation
d. Successful performance of the
system for a 2-week period.
No comments:
Post a Comment