Thursday, July 24, 2014

Section 15000 PIPING, GENERAL

Section 15000

PIPING, GENERAL

PART 1 - GENERAL

1.1 THE REQUIREMENT

A. The CONTRACTOR shall furnish and install all piping systems specified herein and shown on the Drawings. Pipe material, class, joints, fittings, lining, and coating shall be as indicated in the Pipe Schedule. Each system shall be installed complete with all applicable fittings, hangers, supports, anchors, expansion joints, flexible connections, valves, and accessories to provide a functional system as designed. All insulation, lining, coating, heat tracing, testing, disinfection, supports, excavation, backfill and encasement, shall be included in the piping system.

1. Alternative Pipe Types: Where more than one type of pipe is indicated in the schedule or Drawings, the type of pipe material to be installed may be selected by CONTRACTOR. The details on the Drawings cover only one type of pipe for each line. If a different material is selected by CONTRACTOR, all details of connections, jointing, wall fittings, support, anchorage, and harnesses shall be modified as necessary to produce an equivalent design acceptable to ENGINEER.

B. Piping shown on Drawings and specified herein is intended to define the general layout, configuration, and routing, required method of support, pipe size and type only. It is the responsibility of the CONTRACTOR to provide a complete system in accordance with the Drawings and requirements set forth herein. All details necessary to provide a complete system as specified herein are the responsibility of the CONTRACTOR. The CONTRACTOR shall provide all spools, spacers, adapters, connectors, and supports necessary to provide a complete and functional system. The CONTRACTOR shall furnish pipe supports, hangers, anchors, etc., in addition to those shown on the Drawings or described in the Specifications, when necessary to provide a system as specified herein. The CONTRACTOR shall provide layout drawings of all piping systems prior to installation showing all piping, equipment, accessories, pipe supports, etc.

C. The CONTRACTOR shall examine the site of the Work, including all existing facilities where new Work is required, and shall verify the exact routing of piping required to construct the intended piping system. The alignment of pipes may be varied from that indicated on Drawings at no additional cost to OCSD, where necessary, to avoid obstructions not shown on the Plans. The piping arrangement shall provide adequate access to all devices for maintenance and clearance at passageways.

D. The CONTRACTOR shall provide all tools, equipment, materials, and supplies necessary and shall perform all labor necessary to complete the Work specified herein and indicated on the Drawings. The CONTRACTOR shall provide all testing apparatus necessary to perform testing as required by the Contract Documents. The CONTRACTOR shall provide any equipment necessary for inspection of and testing of piping systems specified.

E. Pipe Service: Piping for specific services shall be as listed in the Standard Pipe Schedule unless otherwise indicated. Buried piping is only that piping actually buried in the ground or cast in concrete. Exposed piping includes that within buildings, tunnels or other structures regardless of elevation.
1.2 RELATED WORK SPECIFIED ELSEWHERE

A. The requirements of the following sections and divisions apply to the Work of this section. Other sections and divisions of the Specifications, not referenced below, shall also apply to the extent required for proper performance of this Work.

1. Section 01332, Seismic Design Data

2. Section 02200, Earthwork

3. Section 02666, Water Pipeline Testing and Disinfection

4. Division 02, Site Work, applicable sections

5. Section 03300, Cast-in-Place Concrete

6. Section 05500, Miscellaneous Metalwork

7. Section 07600, Flashing and Sheet Metal

8. Section 09800, Protective Coating

9. Section 15010, Mill Piping - Exposed and Buried

10. Section 15020, Pipe Supports

11. Section 15250, Pipe and Equipment Insulation

12. Section 15430, Plumbing Specialties

1.3 REFERENCE SPECIFICATIONS, CODES, AND STANDARDS

A. All Work specified herein shall conform to or exceed the applicable requirements of the referenced portions of the following publications to the extent that the provisions thereof are not in conflict with other provisions of these Specifications.

B. Comply with the applicable editions of the following codes, regulations and standards.


1. Codes and Regulations:

CCR California Code of Regulations, Title 24, Part 2, California Building Code (CBC)

CCR California Code of Regulations, Title 24, Part 5, California Plumbing Code

2. Industry Standards:

ASME B1.20.1 Pipe Threads, General Purpose (Inch)

ASME B16.1 Gray Iron Pipe Flanges and Flanged Fittings
(Classes 25, 125, and 250)
ASME B16.5 Pipe Flanges and Flanged Fittings: NPS 1/2 through 24 Metric/Inch Standard

ASTM A 307 Standard Specification for Carbon Steel Bolts and Studs, 60,000 psi Tensile Strength

ASTM A 325 Standard Specification for Structural Bolts, Steel, Heat Treated, 120/105 ksi Minimum Tensile Strength

ASTM D 792 Standard Test Methods for Density and Specific Gravity (Relative Density) of Plastics by Displacement

ASTM D 2000 Standard Classification System for Rubber
Products in Automotive Applications

AWS D1.1 Structural Welding Code- Steel

AWWA C105 Polyethylene Encasement for Ductile-Iron Pipe
Systems

AWWA C207 Steel Pipe Flanges for Waterworks Service - Sizes 4 Inch through 144 Inch

AWWA C209 Cold-Applied Tape Coatings for the Exterior of Special Sections, Connections, and Fittings for Steel Water Pipelines

AWWA M11 Steel Pipe - A Guide for Design and Installation

AWWA C606 Grooved and Shouldered Joints

C. Comply with the applicable reference Specifications as directed in the General
Requirements and Additional General Requirements.

1.4 CONTRACTOR SUBMITTALS

A. The CONTRACTOR shall complete shop drawings of all piping systems, equipment, accessories, and supports in accordance with the General Requirements, Additional General Requirements and as specified herein. The shop drawings shall include all necessary dimensions and details on pipe joints, fittings, fitting specials, valves, appurtenances, design calculations, and material lists. The submittals shall include detailed layout, spool, or fabrication drawings that show all pipe spools, spacers, adapters, connectors, fittings, and pipe supports necessary to accommodate the equipment and valves provided in a complete and functional system. Layout drawings shall include all dimensions and spacing for pipe joints, fittings, fitting specials, valves, appurtenances, connectors, adapters, supports, hangers, anchors, etc. necessary to provide a complete and functional system as specified herein.

B. All expenses incurred in making samples for certification of tests shall be borne by the CONTRACTOR.
C. CONTRACTOR Qualifications:

1. Manufacturer's Service Representative.

2. Comply with the requirements for the certifications, licenses, training, skills, experience, and other qualifications specified in Article entitled “Cutting Pipe” of this Specification.

3. Comply with the requirements for the certifications, licenses, training, skills, experience, and other qualifications specified in Article entitled “Pipe Insulation” of this Specification.

4. Comply with the requirements for the certifications, licenses, training, skills, experience, and other qualifications specified in Article entitled “Coating Inspection” of this Specification.

1.5 DELIVERY, HANDLING, AND STORAGE

A. All piping materials, fittings, valves, and accessories shall be delivered in a clean and undamaged condition and stored off the ground, to provide protection against oxidation caused by ground contact. All defective or damaged materials shall be replaced with new materials.

1.6 PIPE MATERIAL ABBREVIATIONS

AC Asphaltic Coating Bl Bituminous Lining BC Bituminous Coating
BS Bell and Spigot Joint

BSP Black Steel Pipe

CC Cement-Mortar Coating

CI Cast Iron

CML Cement Mortar Lined

CPVC Chlorinated PVC DI Ductile Iron
EC Encased In Concrete

EXC Epoxy Coated

EXL Epoxy Lined

EXS Extra Strength or Extra Heavy

FC Flexible Coupling, Harnessed As Required
FLG Flanged Joint

GALV Galvanized

GE Grooved End Joint

GL Glass Lining

GSP Galvanized Steel Pipe HDPE High Density Polyethylene I Insulated
J Jacket on Pipe Insulation

MI Malleable Iron

MJ Mechanical Joint

NOH No-Hub Joint

P Painted

PCW Plastic Coating or Wrapping

PE Plain End

PEN Polyethylene Encased

PL Plastic Liner (PVC) PO Push-On Joint
PP Polypropylene

RCP Reinforced Concrete Pipe

RG Rubber Gasket RL Rubber Lined SC Screwed Joint
SP Cast Iron Soil Pipe

STD Standard

STL Steel

ST STL Stainless Steel

SW Solvent Welded Joint
TF Thermo-Fusion VCP Vitrified Clay Pipe W Welded
WC Water Column

1.7 PIPE SERVICE ABBREVIATIONS

BS Bottom sludge CENT Centrate CHEMD Chemical drain
CL SOL or CS Chlorine solution

CW City water

C Chilled water

DS Digested sludge DC Digester cleaning DG Digester gas
DAFTU Dissolved Air Floatation Underflow

D Drain

FECL3 Ferric chloride FECL2 Ferrous chloride FD Floor drain
FM Force main

FA Foul air

HPA High pressure air

HPDG High pressure digester gas HPNG High Pressure natural gas HW Hot water
HWR Hot water return

HWS Hot water supply



IW
Industrial water



IA

Instrument air



LPA

Low pressure air



LPDG

Low pressure digester gas



LO

Lube oil



NG

Natural gas



PW

Plant water



POL

Polymer



POTW

Potable water



PE

Primary effluent



PI

Primary influent



PS

Primary sludge



RAS

Return activated sludge



S

Scum



SD

Sanitary drain



SFW

Surface Waste



SE

Secondary effluent



SI

Secondary influent



STEAM

Steam



SN

Supernatant



TWAS

Thickened waste activated sludge



V

Vent



WAS

Waste activated sludge

1.8

PIPE SCHEDULE



A. Refer to drawing M0-5001 for pipe schedule.
PART 2 - PRODUCTS

2.1 GENERAL

A. All pipes, fittings, and appurtenances shall be furnished in accordance with the requirements of the applicable sections of Divisions 02 and 15 and as specified herein.

B. Miscellaneous Small Pipes: Miscellaneous small pipes and fittings shall be in accordance with the requirements of Section 15010, Mill Piping - Exposed and Buried, and as specified herein.

C. Joints: All aboveground pipe shall have screwed, flanged, grooved-end, or welded joints. Mechanical and push-on joints shall be installed only underground unless otherwise noted.

D. Pipe Supports: All pipes shall be adequately supported in accordance with the requirements of Section 15020, Pipe Supports, and as shown.

E. Lining: Requirements pertaining to material, thickness, application, and curing of pipe lining are specified in the section of these Specifications governing the type of pipe.

F. Coating: Coatings shall be as indicated in the Pipe Schedule. Requirements pertaining to thickness, application, and curing of pipe coating systems are specified herein, in the sections of these Specifications governing the type of pipe, and in Section
09800, Protective Coating. Pipes aboveground or in structures shall be field-painted prior to installation.

G. Pressure Rating: All piping systems shall be tested at the test pressure indicated in the piping schedule.

H. Gaskets: Shall be manufactured by, Or Equal:

a. John Crane

b. Garlock

2.2 THREADED INSULATING CONNECTIONS

A. General: Threaded insulating bushings, unions, or couplings, as appropriate, shall be used for joining threaded pipes of dissimilar metals and for isolating piping systems where corrosion control and cathodic protection are involved.

B. Materials: Threaded insulating connections shall be of nylon, Teflon, polycarbonate, polyethylene, or other nonconductive materials, and shall have ratings and properties to suit the adjoining pipe.
2.3 SLEEVE-TYPE COUPLINGS A. General:
1. Flexible sleeve-type couplings shall be installed with all appurtenances necessary to provide a complete functional system.

2. All flexible joints and couplings shall be restrained across the joint to prevent slippage of pipe ends. Flanged coupling adapters shall have not less than two anchor studs each.

3. When flexible type couplings are used as expansion joints, the ends of the pipe shall be separated to allow for expansion.

4. Where indicated on the Plans, flexible couplings shall be suitable for connecting pipes with different outside diameters.

5. Buried sleeve-type couplings shall be factory-applied coal tar epoxy-coated as specified in Section 09800, Protective Coating.

B. Construction: Sleeve-type couplings shall be of steel construction with steel bolts, and of sizes to fit the pipe and fittings. The middle ring shall be not less than 1/4 inch in thickness and 5 or 7 inches long for standard couplings, and 16 inches long for long- sleeve couplings. The followers shall be single-piece contoured mill section welded and cold expanded to fit for the middle rings. They shall be of sufficient strength to accommodate the number of bolts necessary to obtain adequate gasket pressures without excessive rolling. The shape of the follower shall be designed as to provide positive confinement of the gasket. Bolts and nuts shall be Type 316 stainless steel in buried locations and heat-treated Grade 5 or better for aboveground piping and gallery piping inside structures.

C. Pipe Preparation: The ends of the pipe shall be prepared to fit steel couplings. Plain ends for use with couplings shall be smooth and round for a distance of 12 inches from the ends of the pipe, with outside diameter not more than 1/64 inch smaller than the nominal outside diameter of the pipe. The ends of connected piping shall be coated as specified in Section 09800, Protective Coating.

D. Gaskets: Gaskets for sleeve-type couplings shall be rubber-compound material that will not deteriorate from age or exposure to air under normal storage or use conditions. Gaskets for wastewater and sewerage applications shall be Neoprene, or equivalent suitable elastomer. The rubber in the gasket shall meet the following specifications:

1. Color: Jet Black

2. Surface: Non-blooming

3. Durometer Hardness: 74 plus or minus 5

4. Tensile Strength: 1000 pounds per inch minimum

5. Elongation: 175 percent minimum

The gaskets shall be immune to attack by impurities normally found in water or wastewater. All gaskets shall meet the requirements of ASTM D 2000, AA709Z, meeting Suffix B13 Grade 3, except as noted above. All gaskets shall be compatible with the piping service and fluid utilized.
E. Insulating Couplings: Where insulating couplings are required, both ends of the coupling shall have a wedge-shaped gasket that assembles over a rubber sleeve of an insulating compound in order to obtain complete insulation of all coupling metal parts from the pipe.

F. Restrained Joints: Restrained joints for sleeve-type couplings shall be in accordance with AWWA M11.

G. For cast iron and ductile iron pipes, flexible couplings shall be manufactured by Or
Equal:

1. Dresser Style 138 or 38

2. Baker series 4228

H. For steel pipe, flexible couplings shall be manufactured by, Or Equal:

1. Dresser Style 38

2. Baker series 4200

2.4 FLEXIBLE CONNECTORS

A. Flexible Rubber Connections: Flexible rubber connections, unless otherwise noted, shall be a 3/8-inch-thick neoprene rubber tube with full-faced flanged ends rated at 150 pounds per inch working pressure. Flexible rubber connections shall be Diversipipe as made by the Goodyear Tire and Rubber Company; Style 100 Vibraflex of neoprene rubber, as manufactured by the Mercer Rubber Company, Or Equal.

B. Flexible Vibration Joints:

1. All pipe going to or from each piece of mechanical equipment, for any purpose whatsoever, shall have a flexible connecting joint in that pipe near the equipment at points between vibration and no vibration.

2. Flexible connectors shall be installed in all piping connections to engines, blowers, compressors, and other vibrating equipment, and where shown. Flexible connectors shall be flanged, braided stainless steel spools with inner, annular, corrugated stainless steel hose, rated for minimum 150 pounds per inch working pressure, unless otherwise shown. The connectors shall be a minimum of 9 inches long, face-to-face flanges, unless otherwise shown. The CONTRACTOR shall submit manufacturer's shop drawings and calculations.

3. Flexible vibration joints 1/2 inch and smaller shall be braided bronze, Type KFCB as manufactured by U.S. Flexible Metallic Tubing Company; Nelson Dunn Series NDB, Or Equal.

4. Flexible vibration joints, 3/4 inch through 2 inches, shall be braided bronze as manufactured by U.S. Flexible Metallic Tubing Company, Type KFCB; Nelson Dunn Series NDB, Or Equal. Joints shall be suitable for working pressure of not less than
250 pounds per inch.

5. Flexible vibration joints larger than 2 inches shall be manufactured by U.S. Flexible Metallic Tubing Company, Series 151-TR-1215, with ASME B16.1 Class 150 flanges, stainless steel bellows and shall be suitable for a working pressure of 150 pounds per inch, except that in high pressure air lines, Type BH8 shall be used; Nelson Dunn Type NDF, Or Equal.
2.5 EXPANSION JOINTS A. General:
1. All piping subject to expansion and contraction shall be provided with expansion joints to compensate for movement, without exertion of undue forces to equipment or structures. Expansion joints shall be of stainless steel, Monel, rubber, or other materials, suitable for each individual service. The CONTRACTOR shall submit detailed calculations and manufacturer's shop drawings and information on materials, temperature and pressure ratings.

2. Any visible damage whatsoever to an expansion joint shall be sufficient cause for rejection. A rejected joint shall be replaced with a like joint in a new and undamaged condition at no extra cost to OCSD.

B. Sludge Piping:

1. Sludge pipe expansion joints shall be installed between anchors as shown on the Contract Documents. At least one expansion joint shall be installed in each run of primary sludge piping that exceeds 20 feet in length. Spacing of expansion joints shall not exceed 200 feet.

2. Sludge pipe expansion joints shall have packing suitable for temperatures greater than 212 degrees F. Where sludge expansion joints are installed in glass- lined pipe, the slip pipes shall be glass lined. The interior of the body and exterior of the slip pipe shall be coated with coal tar epoxy. On pipe not glass lined, the interior of the slip pipe shall also be coated with coal tar epoxy.

3. Primary sludge piping shall have steamer connections as shown on the Contract Documents. Steamer connections shall be located near an anchor away from an expansion joint.

4. Sludge Pipe Expansion Joint Manufacturers, Or Equal:

a. Dresser Style 63, Type 2 b. Red Valve Inc., Redflex
C. Expansion Joints, Steam and Hot Water:

1. Expansion joints shall be furnished and installed, as specified and where shown on the Contract Documents. Expansion joints shall be of the flexible bellows type and shall be rated for 150 pounds per inch, 500 degrees F service. The bellows shall be made of laminated stainless steel liner. The axial traverse of the expansion joint shall not be less than 3 inches. The end connections shall be ASME B.16.1, Class
150 flanges.

2. At least one expansion joint shall be installed in each run of steam or hot water piping that exceeds 20 feet in length. Spacing of expansion joints shall not exceed
150 feet for steam piping and 200 feet for hot water piping. Where possible, expansion joints shall be installed adjacent to an anchor. Each run of piping shall
have two concentric guides, the first being within 2 feet of the end of the joint
opposite the anchor. Any expansion joint not installed adjacent to an anchor shall have two concentric guides on piping within 2 feet of both ends of the expansion joint.
3. Care shall be taken in packing, shipping and installing expansion joints to prevent damage to the joint bellows. The expansion joint shall also be locked against movement in any direction until the hydrostatic pressure test of the pipe is completed.

4. Steam and hot water pipe expansion joint manufacturers, Or Equal:

a. Keflex Series 308-1215

b. Flexonics Inc. Control-Flex CFB expansion joint

2.6 PIPE THREADS

A. All pipe threads shall be in accordance with ASME B1.20.1.

2.7 PIPE INSULATION

A. Hot and cold liquid piping, flues, and engine exhaust piping shall be insulated as shown on the Drawings. Pipe insulation shall be in accordance with Section 15250, Pipe and Equipment Insulation.

2.8 HEAT TRACING

A. Where so specified or shown, pipes shall be protected by heat tracing.

2.9 STEAM TRAPS

A. Steam traps shall be installed as specified in Section 15120, Piping Specialties.

2.10 PIPE SLEEVES

A. Where specified or as indicated on the Drawings, pipe sleeves shall be provided for piping passing through concrete or masonry walls or floors.

B. Pipe sleeves shall be stainless steel with a welded water-stop ring.

C. Wall sleeves are to be sealed using modular casing seals ("link seals") and approved caulking on both sides of the penetration.

PART 3 - EXECUTION

3.1 GENERAL

A. All piping and appurtenances shall be installed in accordance with the requirements of all applicable and related divisions of these Specifications.

B. Any deviation from lines, grades, or elevations shown on the Drawings shall be subject to a written acceptance by the ENGINEER.

C. Where core drilling is required for pipes passing through existing concrete, all core drilling locations shall be determined by radiograph of the concrete construction to avoid damage to embedded raceways, conduits, and reinforcing steel.

D. Prior to any core drilling of existing concrete, the CONTRACTOR shall obtain acceptance of all locations, in writing, from the ENGINEER.
E. All pipe to be coated shall be coated prior to installation. After installation, the coating shall be repaired where damaged. Bolts and other steel joint hardware shall be free from rust when installed and primed within 24 hours after installation.

3.2 HANDLING

A. All pipe, fittings, and related appurtenances shall be handled in a manner that will insure installation in sound, undamaged, like new condition.

B. Handling: All pipe, fittings and accessories shall be loaded and unloaded by lifting with hoists or skidding in order to avoid shock or damage. Under no circumstances shall such material be dropped. Pipe handled on skidways shall not be rolled or skidded against pipe on the ground.

C. Pipe and fittings with cement mortar or epoxy lining or special coatings shall be handled with rubber-covered hooks, or other type of equipment to prevent damage. Slings, hooks, or pipe tongs shall be padded and used in such a manner as to prevent damage to the exterior surface or internal lining of the pipe.

D. Pipe and fittings in which the lining or coating has been damaged shall be immediately removed from the jobsite and replaced. In instances where damage is minimal, the CONTRACTOR may, with acceptance from the ENGINEER, have the damage repaired by a qualified representative of the pipe manufacturer or fabricator.

3.3 STORAGE

A. The interior of all pipe, fittings, and other appurtenances shall be kept free from dirt or foreign matter at all times.

1. All pipe shall be stored off the ground at all times, even during installation.

2. Pipe ends shall be covered to prevent foreign matter from entering the pipe during storage.

a. Threaded ends of pipe shall be covered to protect the threads. b. Flanged pipe shall have the flange faces protected.
B. Pipe shall be stacked using suitable lumber between rows to prevent damage to pipe. Store coated pipe on extra-wide skids to protect the coating.

C. CPVC pipe shall be stored out of direct sunlight to prevent damage and premature deterioration.

D. Pipe with special coatings shall be stored out of direct sunlight to prevent damage to coating.

E. Exposure to sunlight prior to backfilling of wrapped pipe shall be kept to a minimum. If several weeks of exposure prior to backfilling are anticipated, Class C material shall be used (see AWWA A21.5).

F. Gaskets for mechanical and push-on joints shall be stored in a cool location, out of direct sunlight. Gaskets shall not come in contact with petroleum products. Gaskets shall be used on a first-in, first-out basis.
G. Copper and galvanized pipe shall be covered or stored indoors.

H. Pipe that has become damaged or unidentifiable due to improper storage shall be rejected and immediately removed from the jobsite.

3.4 CUTTING PIPE

A. Cutting of pipe shall be done in a neat manner, without damage to the pipe, pipe lining, or pipe coating.

B. Cuts shall be smooth, straight, and at right angles to the pipe axis.

C. Pipe shall be cut using a portable guillotine saw, abrasive wheel "cut-off" saw, or milling cutter only. Use of gas torches for cutting pipe will not be permitted.

1. Where it becomes necessary to cut steel pipe larger than 6 inches in diameter, the CONTRACTOR may, with written permission of the ENGINEER, use gas torch to cut the pipe.

2. Only a qualified pipe fitter or boilermaker shall make any approved torch cuts of pipe

D. Field cut holes for saddles shall be made utilizing a hole saw or other mechanical means. Gas torch cutting of holes will not be permitted.

E. Cut ends and rough edges shall be ground smooth, and for push-on joint connections, the cut end shall be beveled by methods recommended by the manufacturer and be subject to ENGINEER's acceptance.
F. After cutting, the end of the pipe shall be dressed with a file or power grinder to remove all roughness and sharp edges.

G. All damaged or removed lining or coating shall be repaired by a qualified representative of the pipe manufacturer or fabricator.

3.5 CLEANING

A. The interior of all pipe and fittings shall be thoroughly cleaned of all foreign matter prior to installation, and shall be kept clean until the Work has been accepted.

B. Before jointing, all joint contact surfaces shall be wire brushed, wiped clean, and kept clean until the jointing is completed.

C. Flange faces shall be wire brushed and cleaned to remove all oil, grease, loose primer, mill scale, or any other foreign matter that could affect the proper seating of the gasket.

D. Prior to testing, pipe shall be thoroughly cleaned by flushing and/or purged in accordance with these Specifications.

3.6 DISINFECTION

A. Disinfection of potable or city water piping shall be in conformance with Section
02666, Water Pipeline Testing and Disinfection, and with local (county and city) health regulations.
3.7 PURGING

A. The CONTRACTOR shall coordinate all purging with adjacent work under other contracts as necessary to preclude work interference or duplication of effort, and to eliminate any safety hazard to adjacent work.

B. All purging work shall be done in the presence of the ENGINEER, and in accordance with these Specifications and applicable codes.

C. All existing valves shall be operated by OCSD personnel only.

D. The ENGINEER shall be notified of purging operations as indicated per General Requirements. The notification shall include a detailed purging plan that includes the following:

1. Method of purging and proposed procedure.

2. Required coordination.

3. Drawings or sketches of lines to be purged.

4. Sequence of operation.

5. Anticipated flow rate in standard cubic feet per minute (scfm) of vented gas to be purged.

6. Equipment to be used.

7. Proposed method of disposing of vented gases.

E. The CONTRACTOR shall provide all necessary piping connections, temporary piping, temporary valves, sampling taps, purge nitrogen, methane and oxygen monitoring apparatus, and all other items or equipment or material required to complete this Work.

F. Pressure within the pipe shall be reduced to atmospheric pressure prior to beginning purging operations.

G. The pressure shall not exceed the normal operating pressure of the line being purged.

H. Unless otherwise accepted in writing by the ENGINEER, vent gas containing digester/natural gas shall be disposed of in accordance with all applicable city, state, and federal laws and regulations.

I. Other vent gases shall be piped outside of structures to the open atmosphere for disposal.

J. Pipelines Containing Digester/Natural Gas:

1. At least eight volume changes of nitrogen gas shall be available for purging.

2. The CONTRACTOR shall utilize a combustible gas meter to determine the methane gas content in the vented gas.
3. The pipeline shall be purged until the residual methane in the vent gas is less than 1 percent.

Note: Following this purge, the piping is filled with nitrogen, an asphyxiate. Proper ventilation shall be provided if the pipe is opened.

K. Pipelines Containing Air:

1. Pipelines initially containing air, or pipelines that have been opened to atmosphere, shall be purged twice.

2. The first purge shall displace air with nitrogen to minimize the explosive hazard of an oxygen-methane mixture.

a. At least five volume changes of nitrogen gas shall be available for the first purge.

b. An oxygen meter shall be used to determine the oxygen content in the vented gas.

c. The pipeline shall be purged until the oxygen in the vent gas is less than 5 percent.

d. The purge rate shall not exceed the capacity of the pipeline.

3. The second purge shall displace the nitrogen with digester/natural gas through the appliances or equipment to prevent supplying a noncombustible gas mixture to the equipment.

a. The product gas, digester or natural gas, shall be introduced into the pipeline for the second purge.

b. A combustible-gas meter shall be used to determine the methane gas content in the vented gas.

c. The pipeline shall be purged through the appliance/equipment until methane gas can sustain a stable flame.

d. The flow rate shall not exceed the capacity of the appliance/equipment.

L. After the piping has been purged, the CONTRACTOR shall notify the ENGINEER, in writing, that the piping is ready to be placed in service.

M. OCSD personnel will place the line in service.

3.8 PIPE SLEEVES

A. Unless otherwise specified or indicated on the Drawings, pipes passing through concrete or masonry shall be installed through stainless steel sleeves installed before concrete is placed or masonry is laid.

B. The CONTRACTOR shall be responsible for coordinating the installation of sleeves for all piping.
C. Pipe sleeves installed through floors provided with a special finish, such as ceramic tile, resilient tile, or seamless flooring, shall be flush with the finished floor surface, and shall be provided with nickel or chromium plated floor plates.

D. In all other locations where pipes pass through floors, pipe sleeves shall project
2 inches above the finished floor surface, with the projection uniform throughout each floor area.
E. In the case of insulated pipes, the insulation shall be carried through the pipe sleeve. F. Where it is indicated on the Drawings to provide for future installation of pipe, sleeves
shall be provided and the ends sealed with an approved plastic cap/plug.

G. For piping passing through existing concrete or masonry floors or walls, core drilled holes will be accepted when accepted in writing by the ENGINEER.

1. Any reinforcement that is cut while drilling holes in existing concrete or masonry shall be coated with an approved epoxy coating prior to pipe being installed

H. All pipes passing through interior concrete or masonry walls or slabs shall be caulked on both sides with approved caulking.

1. Caulking in fire-rated walls shall be approved fire caulking of a color that shall be subject to acceptance by the ENGINEER.

I. All pipes passing through walls or slabs that have one side exposed to the outside, have one side in contact with earth, or have one side exposed to a water bearing or water conveying structure, shall be sealed watertight by the use of modular casing seals ("link- seals") and be caulked on both sides of the wall or slab. The pipe sleeve for these instances shall have a waterstop.

3.9 PIPE INSTALLATION

A. All piping shall be installed as specified, as indicated on the Drawings and in a manner acceptable to the ENGINEER.

B. The CONTRACTOR shall provide pipe cut from measurements made at the jobsite, and not from the Drawings.

C. Provisions shall be made in laying out all piping to provide for expansion and contraction throughout.

D. Expansion joints or fittings shall be provided on all piping as specified or otherwise indicated on the Drawings.

E. All exposed pipe shall be installed in straight horizontal and vertical runs parallel to the axis of the structures, except that gravity drain lines shall be pitched down in the direction of flow not less than 1/8 inch per foot. All digester gas pipe shall be pitched to drain to drip traps as indicated, not less than 1/8 inch per foot where condensate flows against the gas, and not less than 1/16 inch per foot where condensate flows with the gas. At high points of straight runs, tapered filler pieces between flanges shall be used to secure the reversal of pitch without springing the pipe. Lines under low head shall be laid flat or with a continuous grade so that there will be no air traps or humps in them, except at the ends where means for venting shall be provided.
F. No exposed piping shall be erected until all equipment to which the pipe is to be attached has been installed, and it can be determined where piping and fittings shall be located to make a neat, efficient arrangement.

G. The piping installation shall present no head bump or tripping hazard, or otherwise obstruct passageways or hinder reasonable access for equipment maintenance.

H. Piping shall be held free of any contact with building construction so as not to transmit noise.

I. All water, gas, and air supply piping at each fixture, or unit of equipment, shall be provided with an approved shutoff valve and union - WHETHER INDICATED ON THE CONTRACT DRAWINGS OR NOT - which will permit isolation and disconnection of each item without disturbing the rest of the system.

J. Air supply piping shall be provided with approved sectionalizing valves and valved air inlet connections as required for isolating portions of the system for periodic testing.

K. Unions shall be installed in screwed piping where indicated on the Plans and shall be installed at 50-foot maximum spacing on all 2-inch and smaller screwed piping. Unions shall be installed within 6 inches of each side of tees and valves in all screwed piping.

L. A union or flexible coupling shall be placed on all pipes that pass through walls on both sides of the wall.

M. The gas supply line to each building shall be provided with an approved shutoff valve and union located above finish grade immediately outside the building. The gas shutoff valve shall have an approved, clearly visible, sign installed indicating "GAS SHUTOFF".

N. Non-pressure piping installed above electrical panels or cabinets shall be insulated and drip shields shall be installed to contain and channel any condensate or leakage away from the panels or cabinets.

O. Pressure piping shall not be installed above electrical panels or cabinets.

P. All air and digester gas piping shall be graded to points of drainage collection and approved drip legs and valves shall be installed.

Q. Water supply piping within structures shall be arranged, and facilities provided, for complete drainage.

R. All piping serving metering equipment shall be uniformly graded so that air traps are eliminated and complete venting is provided.

S. Seal water supply shall be piped to within 3 feet of the pumping unit seal box.

1. Connection to the pump from the seal water piping shall be made using stainless steel tubing as specified.

T. Stuffing box leakage from water sealed pumps shall be piped to the nearest point of drainage collection. Seal water leakage shall not be allowed to free flow on the floor to the drainage collection point.

U. In no case shall copper or copper alloy pipes or be attached to cast iron, ductile iron, or steel pipe except by means of a dielectric coupling expressly made for this purpose and service.
V. Taps for pressure gauge connections on the suction and discharge sides of pumping units shall be provided with a nipple and an approved shutoff valve.

1. Drilling and tapping of pipe walls for installation of pressure gauges or switches will not be permitted.

2. Taps shall be provided by factory threaded taps or a factory welded boss.

3. All branch connections in horizontal runs of air, gas, or steam piping shall be made from the top of the pipe.

W. All pipe, fittings, valves, hydrants, and other appurtenances shall be examined carefully for damage and other defects immediately before installation.

X. No debris, tools, clothing, or other materials shall be placed in the pipe at any time.

3.10 PLUMBING A. General:
1. Pipe and fittings associated with plumbing fixtures shall be installed according to
California Plumbing Code.

2. All pipes shall be properly graded, according to California Plumbing Code, and securely supported with pipe brackets and insulating strips, to prevent transmission of noise through pipes.

3. Horizontal piping shall be given a slope of 1/4 inch per foot unless specifically indicated otherwise on the Contract Documents.

4. Traps shall utilize trap primers. B. Fittings:
1. Changes in pipe size on soil and waste lines shall be made with reducing fittings. All changes in direction shall be made by use of 40 degree wyes, half wyes, long- sweep 1/4-bends, 1/6-, 1/8-, or 1/16-bends; except that sanitary tees may be used on vertical stacks, and, on pipe 3 inches in size or larger, short 1/4-bends or elbows may be used where the change in direction of flow is from horizontal to vertical, and on the discharge from water closets.

C. Connections:

1. Union Connections: Approved unions and slip joints shall be permitted only in trap seals or on the inlet side of the traps. The use of long screws and bushings is prohibited.

2. Joints: Bell and spigot joints shall utilize neoprene gaskets. Threaded joints shall be American Standard taper screw threads, cut clean, and made up with Teflon tape or other approved pipe thread compounds.
D. Vents:

1. Vents: Vents within 10 feet of ventilation intakes shall extend up to a point at least 2 feet above the adjacent intake.

2. Flashings: Vents, roof drains, and pipes shall be flashed and made watertight at the roof with not lighter than 4-pound-sheet-lead flashings as specified in Section
07600, Flashing and Sheet Metal. Flashings shall extend not less than 6 inches up the pipes. Flashing for vents may be carried up to the top of the vent and turned down into the pipe. Flashing shields shall extend not less than 8 inches from the vent and pipe in all directions.

E. Valves:

1. Drain valves shall be provided at low points of water systems, and any other piping and connections subject to freezing; drip legs at low points of gas and air piping, to obtain a complete and workable system.

2. Individual shut-off valves shall be provided and installed in accessible location or in cast-iron valve boxes with extension and cover in all water and gas mains entering buildings or structures, and in all branch mains to groups of fixtures.

3. All fixtures shall have stops at the fixture on all services; all fixture fittings and piping that are exposed shall be chrome plated brass.

F. Insulation:

1. All hot water piping shall be insulated in accordance with Section 15250, Pipe and Equipment Insulation, except for short, exposed fixture connections. Such systems shall be provided with shut-off and drain valves at low points, with continuous grade down to drainage points, to enable evacuation of the piping back to a safe location.

G. Testing and Flushing:

1. All plumbing lines and piping shall be thoroughly flushed out and left clean, as required by the with local (county and city) health regulations.

2. All plumbing work (soil, waste, drain, vent lines, gas lines, etc.) shall be either air or water tested as specified in the California Plumbing Code. The water test requires at least 10-foot head for 15 minutes. The air test requires a pressure of 5 psig for 15 minutes. Piping shall be repaired and retested until no leakage is evident.

3. Leaks disclosed by testing shall be repaired and testing continued until all piping is tight and without leaks. All testing and repairs shall be at the CONTRACTOR’s expense.

4. All field testing shall be witnessed and be subject to ENGINEER's acceptance.
3.11 CHEMICAL PIPING
A. All chemical piping shall be installed so that lines are readily accessible for cleaning. B. At all exposed changes in direction in chemical piping, tees shall be provided with
extra threaded openings plugged to facilitate cleaning.

1. Thread tape or thread sealer shall be applied to the threads of all plugs to facilitate ease of removal.

C. Drip shields shall be installed beneath all elevated chemical piping in areas subject to pedestrian traffic to contain and transport leakage to an approved disposal area.

3.12 PIPE JOINTS

A. Pipe joints shall be provided as specified or as indicated elsewhere in the Contract
Documents.

3.13 ALIGNMENT

A. All piping shall be installed to lines, grades, and elevations indicated on the
Drawings.

B. All deviations from the line, grade, or elevation as indicated on the Drawings shall be accepted in writing by the ENGINEER.

C. The CONTRACTOR is responsible for coordinating all other work to insure that piping is installed as indicated on the Drawings.

D. Pipe and fittings shall be assembled so there will be no distortion or springing of the pipelines. Flanges, unions, flexible couplings, and other connections shall come together at the proper orientation. The fit shall not be made by springing or heating any piping nor shall orientation alignment be corrected by taking up on any flange bolts. Flange bolts, union halves, flexible connectors, etc. shall slip freely into place. If the proper fit is not obtained, the piping shall be rebuilt to fit.

E. Piping intended to be straight shall be straight. Deflections from a straight line or grade shall be accepted in writing by the ENGINEER and shall be accomplished by the use of approved fittings.

F. Concentric Pipe Guides: Pipe guides shall be installed in the steam and hot water pipes as indicated on the Contract Documents and where necessary for the proper installation of the steam and hot water piping. Each run of steam or hot water piping shall have at least two concentric pipe guides. Concentric pipe guides shall be placed at a maximum spacing of 30 feet.

G. If laser equipment is used for piping installation, periodic elevation measurements shall be made with survey equipment to verify the accuracy of grade or elevation. If such measurements indicate thermal deflection of the laser due to differences between ground or atmospheric temperature and the air temperature within the pipe, steps shall be taken to prevent further thermal deflections.
3.14 PIPE INSULATION

A. All insulation shall be installed by a qualified insulation Subcontractor in strict accordance with the manufacturer's recommendations and the requirements of Section
15250, Pipe and Equipment Insulation.

3.15 COATING INSPECTION

A. All shop-applied coatings on pipe or fittings shall be inspected for holidays and other defects after receipt of the pipe or fittings on the jobsite, and again after installation if it is determined by the ENGINEER that the coating may have been damaged.

1. Inspection shall be made using an electrical holiday detector.

2. The detector used, and inspection procedures, shall be in conformance with the requirements of Section 4.4 of AWWA C209.

B. All field-applied tape wrap on pipe, pipe joints, fittings and valves shall be inspected for holidays and other defects following completion of wrapping and again following installation if it is determined by the ENGINEER that the wrapping may have been damaged.

C. Holidays and other defects detected during inspection shall be repaired in accordance with the recommendations of the coating or tape wrap manufacturer, as applicable.

1. At the discretion of the ENGINEER, major areas of defects in pipe coatings may result in rejection of the pipe and its immediate removal from the jobsite.

2. At the discretion of the ENGINEER, major areas of defects in pipe coatings may be repaired onsite by a qualified representative of the manufacturer or supplier.

3.16 BURIED PIPE

A. All stainless steel, copper, and black steel pipe in buried locations shall have exterior surfaces protected with a shop-applied plastic coating.

B. All galvanized piping in buried locations shall be wrapped with an approved pipe wrap, or be coated with an approved coal tar coating.

C. Buried pipe shall be protected from lateral displacement by use of the specified pipe embedment and/or encasement.

D. Under no circumstance shall pipe be laid in water.

E. All pipe will be laid on native material unless otherwise specified or indicated on the
Drawings.

F. All pipe subgrade shall be compacted to a minimum relative density of 95 percent, unless otherwise indicated on the Drawings.

G. All pipe subgrade shall have compaction tests taken and be subject to ENGINEER's acceptance prior to pipe installation.
H. No debris, tools, clothing, or other materials shall be placed in the pipe at any time.

I. When pipe laying is interrupted, or stopped at the end of the work shift, the open ends of pipe shall be sealed with a watertight plug or other means acceptable to the ENGINEER, to prevent water from entering the pipe.

J. CPVC pipe shall be "snaked" in the trench, and shall be kept shaded and shall be covered with backfill immediately following testing.

K. Piping shall be backfilled prior to required testing. The CONTRACTOR is responsible for all costs for repair or replacement of pipe that does not pass any required tests and may perform intermediate tests prior to backfilling.

3.17 THRUST BLOCKS

A. Any piping involving joints of a type that can give or slip (which means almost any kind of joint other than a welded, screwed, or flanged joint) shall be properly blocked or tied to prevent movement wherever the piping changes direction, changes size, or ends. Thrust blocks are not allowed in this project. Provide restrained mechanical joints for all buried pipes.

3.18 CONCRETE ENCASEMENT

A. Pipe encasement shall be installed where indicated on the Plans, per the encasement detail in the Drawings.

B. Concrete and reinforcement for encasement shall be as specified in Section 03300, Cast-in-Place Concrete, of these Specifications.

C. All pipe to be encased shall be suitably supported and blocked in proper position to allow for complete encasement.

D. All pipe to be encased shall be anchored to prevent floating.

E. All piping to be encased shall be tested as specified. Obtain ENGINEER’s acceptance of the installation prior to encasement.

3.19 AS-BUILT DRAWINGS

A. The CONTRACTOR shall provide "As-built" Drawings for all piping installed. Locations shall be indicated with the plant coordinate and elevation system for the ends and all changes of direction of each piping run installed.

B. For pipe installed in tunnels, galleries, inside buildings, and aboveground outside

C. For buried pipe installations, surveyed "As-builts" shall include the elevation and location of pipe, valves, and all other pertinent information of the installation, as well as all existing piping or structures exposed in the trench.

D. For buried, encased piping, survey shall be taken both prior to encasement and after the encasement is in place.

E. As-built Drawings shall be forwarded to the ENGINEER for review and acceptance within five days after the installation is completed.

F. Progress payment will be withheld for all pipe installations if "As-built" Drawings are not received as specified.
3.20 TESTING

A. All pipe installations shall be hydrostatically tested for a period of two (2) hours at the hydrostatic test pressure listed in the Pipe Schedule.

B. All pressure testing shall be done in the presence of the ENGINEER and be subject to ENGINEER’s acceptance.

C. All pipe supports and reaction anchorage/seismic anchorage shall be installed prior to pressure testing.

D. Where pipes are encased in concrete, testing shall be done before the concrete is placed.

E. Buried pipe may be center-loaded to preclude movement prior to testing. F. The high point of all pipe installed shall be vented.
G. Testing against valves will not be permitted without specific written authorization from the ENGINEER. All sections of pipe to be tested shall be blind-flanged.

H. All joints shall be examined during the test and all visible leaks shall be repaired. The CONTRACTOR shall furnish all necessary tools, labor, materials, water, bulkheads, and appliances needed for the test.

I. All leaking piping shall be completely retested following repairs of leaks. J. Acceptable leakage is zero.
K. If changes are made to piping installation after initial testing, such as addition of valves, routing changes, branches, etc., the entire line shall be retested.

L. A Pipeline Test Report shall be completed for each test and be subject to
ENGINEER's acceptance. A sample report form follows.
PIPELINE TEST REPORT


DATE: _

JOB NUMBER:
ELEMENT:

INITIAL TEST:
RETEST: _

SYSTEM
TESTED:

SECTION
TESTED:

PLAN DRAWING#: _ PIPE MATERIAL: _ TYPE OF TEST: _
TEST MEDIUM:

TEST PRESSURE: _ TEST DURATION: _ TEST START TIME: _FINISH: _
PRESSURE LOSS/GAIN:

REASON FOR LOSS/GAIN: _



ACTION TAKEN: _

_

TEST PERFORMED BY:
Print Name
_ DATE NAME OF CONTRACTOR

TEST WITNESSED AND ACCEPTED BY:
Print Name

_ DATE ORANGE COUNTY SANITATION DISTRICT

1 comment: