Section 15009
STEEL PIPE – FABRICATED SPECIALS
PART 1 - GENERAL
1.1 THE REQUIREMENT
A. The CONTRACTOR shall furnish all
tools, equipment, materials, and supplies and shall perform all labor
required to complete the Work as indicated on the Drawings and
specified herein.
B. This section covers fabricating,
installing, and testing all bends, reducers, wyes, tees, crosses,
outlets, manifolds, and other steel plate specials, complete, in
place, in accordance with the requirements of the Contract Documents.
1.2 RELATED WORK SPECIFIED
ELSEWHERE
A. The requirements of the following
sections and divisions apply to the Work of this section. Other
sections and divisions of the Specifications, not referenced below,
shall also apply to the extent required for proper performance of
this Work.
1. Section 02666, Water Pipeline
Testing and Disinfection
2. Section 05500, Miscellaneous
Metalwork
3. Section 09800, Protective Coating
4. Section 15000, Piping, General
5. Section 15008, Steel Pipe –
Mortar-Lined and Mortar-Coated
6. Section 11250, Sludge Cake Pumping
System
1.3 REFERENCE SPECIFICATIONS,
CODES, AND STANDARDS
A. All Work specified herein shall
conform to or exceed the applicable requirements of the referenced
portions of the following publications to the extent that the
provisions thereof are not in conflict with other provisions of these
Specifications.
B. Comply with the applicable
editions of the following codes, regulations and standards.
1. Industry Standards:
AWWA C200
Steel Water Pipe 6 inches (150 millimeter) and
Larger
AWWA C208
Dimensions for Fabricated Steel Water Pipe
Fittings
AWWA M11
Steel Water Pipe - A Guide for Design and
Installation
ASTM A 234
Standard Specification for Piping Fittings of Wrought Carbon
Steel and Alloy Steel for Moderate and High Temperature Service
ASTM E 165
Standard Practice for Liquid Penetrant
Examination for General Industry
C. Comply with the applicable
reference Specifications as directed in the General
Requirements and Additional General
Requirements.
1.4 CONTRACTOR SUBMITTALS
A. Submittals shall be made in
accordance with the General Requirements, Additional
General Requirements and as specified
herein.
B. Shop Drawings: The
CONTRACTOR shall submit shop drawings and laying diagrams of
all pipe, joints, bends, reducers, wyes, tees, crosses, outlets,
manifolds, and other steel plate specials.
C. Design calculations shall be
submitted to the ENGINEER for review prior to manufacture of pipe
specials.
D. Certifications: A certified
affidavit of compliance shall be furnished for all steel plate
specials and other products or materials furnished
under this section of the Specifications.
1.5 QUALITY ASSURANCE A.
General
1. Shop Testing of Steel Plate
Specials: Upon completion of the welding, but prior to lining and
coating, each steel plate special shall be bulkheaded and tested
under a hydrostatic pressure of 1.5 times the design pressure;
provided that if straight pipe used in fabricating the specials has
been previously tested and meets the requirements of the applicable
piping section, no further hydrostatic testing will be required; or
provided that all other welded seams are tested by the liquid
penetrant inspection procedure conforming to ASTM E 165 under Method
"B" and "Leak Testing" or where applicable by
the soap and compressed air method at an air pressure of 25 pounds
per inch. Any pin holes or porous welds that may be revealed by the
test shall be chipped out and rewelded and the pipe or fitting
retested.
2. No outside mortar shall be
applied over a seam prior to testing; however, mortar lining may be
applied over a seam prior to hydrostatic testing, but under such
conditions said pressure test shall be held on the pipe or fitting
for a period of not less than 30 minutes.
3. Field Testing: Field testing
shall conform to the requirements of Section 15000, Piping, General.
PART 2 - PRODUCTS
2.1 GENERAL
A. Specials are defined as fittings,
closure pieces, bends, reducers, wyes, tees, crosses, outlets,
manifolds, and other steel plate specials wherever located, and all
piping aboveground or in structures.
2.2 FABRICATION AND MATERIALS
A. General: Reinforcement for
wyes, tees, outlets, and nozzles shall be designed in accordance
with AWWA M11. Reinforcement shall be designed for the design
pressure specified or shown and shall be in accordance with the
details shown. Specials and fittings shall be equal in pressure
design strength and shall have the same lining and coating as the
adjoining pipe. Unless otherwise shown, the minimum radius of
elbows shall be 2.5 times the pipe diameter and the maximum miter
angle on each section of the elbow shall not exceed 11.25 degrees.
B. Specials and fittings that cannot
be mechanically lined and coated shall be lined and coated by hand
application, using the same materials as are used for the pipe and
in accordance with Section 15008 and the applicable AWWA or ASTM
Standards. Coating and lining applied in this manner shall provide
protection equal to that specified for the pipe. Fittings may be
fabricated from pipe that has been mechanically lined and/or coated.
Areas of lining and coating that have been damaged by such
fabrication shall be repaired by hand-applications in accordance
with applicable AWWA or ASTM Standards.
C. Access maintenance holes with
covers shall be as detailed. All threaded outlets shall be forged
steel suitable for 3000 pounds per inch service.
D. Moderate deflections and long
radius curves may be made by means of beveled joint rings, by
pulling standard joints, by using short lengths or pipe, or a
combination of these methods; provided that pulled joints shall not
be used in combination with bevels. The maximum total allowable
angle for beveled joints shall be 5 degrees per pipe joint. Bevels
shall be provided on the bell ends. Mitering of the spigot ends
will not be permitted. The maximum allowable angle for pulled joints
shall be in accordance with the manufacturer's recommendations or
the angle that results from a 3/4-inch pull out from normal joint
closure, whichever is less. All horizontal deflections or
fabricated angles shall fall on the alignment. All vertical
deflections shall fall on the alignment and at locations adjacent to
underground obstructions, points of minimum earth cover, and
pipeline outlets and structures. The pipe angle points shall match
the angle points shown.
E. Outlets, Tees, Wyes, and Crosses:
Outlets 12 inches and smaller may be fabricated from Schedule 30
or heavier steel pipe in the standard outside diameters, i.e., 12-
3/4 inches, 10-3/4 inches, 8-5/8
inches, 6-5/8 inches, and 4-1/2 inches.
F. The design of outlet
reinforcement shall be in accordance with the procedures given in
Chapter 13 of AWWA M11, except that the design pressure, P, used in
the M11 procedure shall equal the greater of 1.25 Pw or 0.9375 Pt.
Unless otherwise shown, outlets 2 inches in diameter and smaller
need not be reinforced.
G. In lieu of saddle or wrapper
reinforcement as provided by the design procedure in AWWA M11, pipe
or specials with outlets may be fabricated in their entirety of
steel plate having a thickness equal to the sum of the pipe wall
plus the required reinforcement.
H. Where required by AWWA M11 design
procedure crotch plate reinforcement shall be furnished.
I. Steel Welding Fittings: Steel
welding fittings shall conform to ASTM A 234.
J. Ends for Mechanical-Type
Couplings: Except as otherwise provided herein, where
mechanical-type couplings are indicated, the ends of pipe shall be
banded with Type C collared ends using double fillet welds. Where
pipe 12 inches and smaller is furnished in standard schedule
thicknesses, and where the wall thickness equals or exceeds the
coupling manufacturer's minimum wall thickness, the pipe ends may be
grooved.
K. Lining: All requirements
pertaining to thickness, application and curing of lining specified
for straight pipe shall apply to specials, with the following
proviso. If the special cannot be lined centrifugally, it shall be
lined by hand. In such case, the lining shall be reinforced with
2-inch x 4-inch x No. 12 welded-wire fabric positioned approximately
in the center of the lining. The wires spaced 2 inches on centers
shall extend circumferentially around the pipe with the fabric
securely fastened to the pipe. Splices shall be lapped 4 inches and
the free ends tied or looped to assure continuity.
L. Coating: All requirements
pertaining to thickness, application and curing of coating specified
for straight pipe shall apply to specials. Unless otherwise shown,
the mortar coating on the buried portion of a pipe section passing
through a structure wall shall extend to the center of the wall, or
to the wall flanges, if one is indicated. Pipe above ground or in
structures shall be field-painted as specified in Section 09800,
Protective Coating.
M. Marking: A mark indicating the
true vertical axis of the special shall be placed on the top and
bottom of the special.
PART 3 - EXECUTION
3.1 GENERAL
A. Unless otherwise provided, the
CONTRACTOR shall furnish and install all fittings, closure pieces,
bends, reducers, wyes, tees, crosses, outlets, manifolds, and other
steel plate specials, bolts, nuts, gaskets, jointing materials, and
all other appurtenances as shown and as required to provide a
complete and workable installation. Where pipe support details are
shown, the supports shall conform thereto and shall be placed as
indicated; provided, that the support for all exposed piping shall
be complete and adequate regardless of whether or not supporting
devices are specifically shown. Where shown, concrete thrusts
blocks and welded joints shall be provided.
B. At all times when the work of
installing pipe is not in progress, all openings into the pipe and
the ends of the pipe in trenches or structures shall be kept tightly
closed to prevent entrance of animals and foreign materials.
C. The CONTRACTOR shall take all
necessary precautions to prevent the pipe from floating due to water
entering the trench from any source, shall assume full
responsibility for any damage due to this cause and shall at its own
expense restore and replace the pipe to its specified condition and
grade if it is displaced due to floating.
D. The CONTRACTOR shall maintain the
inside of the pipe free from foreign materials and in a clean and
sanitary condition until its acceptance by the ENGINEER.
3.2 LAYING
A. Trenches shall be in a
reasonable dry condition when the pipe special is laid. Necessary
facilities including slings shall be provided for lowering and
properly placing the pipe sections in the trench without damage. The
pipe and specials shall be laid to the line and grade shown, and they
shall be closely jointed to form a smooth flowline.
B. Immediately before placing each
section of pipe in final position for jointing, the bedding for the
pipe shall be checked for firmness and uniformity of surface.
No comments:
Post a Comment